Mr.Puneet Khanna (Head-Supply Chain Management)
Worley India Private Limited, New Energy House,RamakrishnaMandir Road, Kondivita, Andheri (East), Mumbai- 400 059, India
EXTENSION AND MODIFICATION - 11KV and 6.6KV HV SWITCHBOARD (INDOOR TYPE)
2020_REFHQ_124223_1
44AD0600-ER-65-0100
Single
Electrical - Cables, Switchgear and Other Control Equipment
Supply
120 days
IOCl GUJARAT REFINERY
3 documents required · 3 mandatory
Exempted
28 Dec 2020
23 Sept 2020
23 Oct 2020
23 Sept 2020
22 Oct 2020
7 Oct 2020
120 days
Extension and Modification - 11kV & 6.6kV HV Switchboard (Indoor Type)
Panel Extension in existing 11kV Switchboard (SW-11) for Two nos. of Distribution Transformers (2.5MVA Each) having following specifications: -1x 630A, 11kV, 3Ph, 50Hz, 40kA/1sec VCB Panels (To be installed on each Bus-Section of Existing Switchgear "SW-11") complete with but not limited to the following: - 1x set of 2500A Main and Transition Busbars - 1x Set of all associated protection, control and indication equipment/items i.e. XFMR Feeder protection relay, Power Meters, Current transformer, Auxiliary Relays, Indicating Lamps, Control Switches etc.
Panel Modification in existing 6.6kV Switchboard (SW-12) : 1x 215kW, 6.6kV, 3Ph, 26.2kA/1sec Motor Starter (To be installed on each dummy panel "SW-12/Unit F10A" and "SW-12/Unit F23A, type M1") complete with but not limited to the following: - 1x set of Main and/or Transition Busbars (As required for integration with existing 2000A main Busbar System) - 1x 630A VCB - 1x Set of all associated protection, control and indication equipment/items i.e. XFMR Feeder protection relay, Power Meters, Motor Protection Relay, Instrument Current XFMRs, Auxiliary Relays, Indicating Lamps, Control Switches etc.
Panel Modification in existing 6.6kV switchboard motor feeder (Motor Tag no. 2071-P-002A and B, panel no.5 and 25, feeder type M1): a. Replacement of existing CT of 40/1 with new CT of rating 75/1-5A, Short Circuit rating 26.2kA for 1 sec. Core-1 : CL-1, 10VA and Core-2 : CL 5P15, 10VA having Insulation Class B. b. Replacement of existing CBCT with new CBCT of rating 10/1A, POC 1.7A
Supply and fixing of new nameplate on the 6.6kV switchboard mentioning revised rating for following motors. a. 2063-P-002C (1260kW) b. 2061-P-001A (630kW) c. 2061-P-001B (630kW) d. 2071-P-002A (450kW) e. 2071-P-002B (450kW)
Supply and installation of bus links, inter panel wiring, required modification in hardware / software inside the panel to hook- up with existing HMI/ECS/RTU system of existing SS-36 with required components and modules.
Installation, Testing and commissioning of 11kV and 6.6kV Switchboard for extension and modification scope as described above including relay setting and coordination with upstream and downstream system at site. The scope also includes Pre-Design site visit to understand the existing installation and hook up requirements of 11kV and 6.6kV HV switchboard.
Description of Work / Item(s)
RECOMMENDED SPARES FOR TWO YEARS O&M – FOR SR NO 1.01 OF BOQ1
RECOMMENDED SPARES FOR TWO YEARS O&M – FOR SR NO 1.02 OF BOQ1
RECOMMENDED SPARES FOR TWO YEARS O&M – FOR SR NO 1.03 OF BOQ1
RECOMMENDED SPARES FOR TWO YEARS O&M – FOR SR NO 1.04 OF BOQ1
RECOMMENDED SPARES FOR TWO YEARS O&M – FOR SR NO 1.05 OF BOQ1
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .