Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
Tender Value
₹70 L
EMD Value
₹1.4 L
Closing Date
21 Aug 2023, 4:00 pmClosed
Office of Executive Engineer TLMD-II, JKPTCL, Glad
Office of Executive Engineer TLMD-II, JKPTCL, Gladni Jammu
Capital maintenance 1x50MVA, BHEL Power Transformer which includes overhauling replacement of oil at 150MVA, 132/33KV, Grid Station Miransahib
2023_PDD_216492_1
TLMD-II/J/09 of 2023-24 Dated 13.06.2023
Open Tender
Electrical and Maintenance Works
Turn-key
60 days
MIRAN SAHIB JAMMU
AS PER NIT AND SBD
3 documents required · 3 mandatory
₹5,000
Yes
Office of Executive Engineer TLMD-II, JKPTCL, Glad
₹1.4 L
5 Oct 2023
13 Jun 2023
24 Aug 2023
14 Jun 2023
21 Aug 2023
16 Jun 2023
Amount
MATERIAL AND LABOUR CHARGES REQUIRED FOR INTERNAL INSPECTION & MINOR REPAIRS OF 50MVA,132/33KV BHEL MAKE TRANSFORMER
Design, Engineering. Manufacture,workshop testing, supply including packing and forwarded, transportation, delivery at site storage charges of;Main Equipment
HV terminal (145 KV,800 Amp)
LV terminal
HV Neutarl Bushing
LV Neutral Bushing
TJB and M.Box ground mounted
Breathers for transformer
Cooling Fans
COPS Conservator
External Paint
Internal oil resistant paint
Gasket
Set of gaskets(Nitrile+cork)
Set of Valves
Fresh Transformer Oil
Erection charges for supply of material for 132/33 KV 50 MVA, BHEL MAKE TRANSFORMER
HV terminal (145 KV,800 Amp)
LV terminal
HV Neutarl Bushing
LV Neutral Bushing
TJB and M.Box ground mounted
Breathers for transformer
Cooling Fans
COPS Conservator
External Paint
Internal oil resistant paint
Gasket
Set of gaskets(Nitrile+cork)
Set of Valves
Labour Cost for the repair and overhauling of 50 MVA 132/33 KV ,50 MVA Power Transformer
Erection of temporary shed for dehydration of Transformer
Draining of complete oil i.e 22400 L from the Transformer for carrying out Internal inspectiont and for replacement of all the gaskets of Transformer and filling of transformer with Nitrogen gas with a pressure of 0.4kgs per sq cm
Dismantling of transformer Accessiories such as Bushings, bushing turrets, Pipe lines, Inspection covers, OLTC chamber covers, Radiator plugs for replacement of worn out gaskets with new one
Filteration/Dehydration of Transformer oil and step by step filling into the transformer
Erection of all Transformer Accessories such as Bushings, bushing turrets, Pipe lines, Inspection covers, OLTC chamber covers, Radiator plugs after replacement of worn out gaskets with new one and replacement of buccholz relay,PRV,Magnetic oil level gauge ,Prismatic oil level gauge,Temperature indicators(WTI & OTI) ,cooling fans,relay and contactor,etc
Misc. Works such as dismantling of jumpers/connectors and reconnection of same after carrying out job, testing of transformer, carriage/transportation of Filteration Plant, oil storage tanks their loading and unloading at site(L/S)
Repairing or Overhauling of motor in Driving Mechanism of OLTC
Making RTCC Panel functional,checking cables,remote temperature indicators(WTI,OTI) in RTCC panel.Checking Local and remote operation along with AVR relay & other allied works
Checking reparing and making functional auto control operation of cooling fan by way replacement of Main Switch, Contactors, Relay and placing new wiring in the existing old/ replaced fan control cubical
Final Erection Check and conducting various pre-commissioning tests on the Transformer including dissolved gas analysis, BDV of oil, PPM,C & tan delta of oil , Bushings and Windings, interfacial tension, sludge, ratio test, short circuit test, winding resistance ,insulation resistance etc for successful commissioning of transformer after repais/overhauling of the transformer
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .