GE Jammu
GE Jammu c/o 56 APO Pin-900277
REPAIR AND REPLACEMENT OF LED LIGHT, OH TANK LIGHT AND LT DISTRIBUTION NETWORK AT DAMANA UNDER GE JAMMU
2023_MES_592735_1
GEJC-05/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AoR of GE Jammu
Please refer Tender Documents
8 documents required · 8 mandatory
₹500
GE Jammu
₹1 L
Yes
23 Jun 2023
2 May 2023
29 May 2023
2 May 2023
27 May 2023
15 May 2023
Amount
Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr deep in loose/soft soil and getting out for underground cable/erection of poles, stays etc complete all as specified and as directed by Engineer-in-Charge.
Description all as per serial item no 1 above but for exceeding 1.5 mtr deep but not exc 3.0 mtr deep complete all as specified and directed.
Material and labour for sand cushioning for cable with river washed sand and punning to provide required cover as per SSR part I complete all as specified and directed by Engineer-in-Charge.
Supplying and laying in replacement of bricks common burnt clay sub class 'B' old size for cable protection complete all as specified and directed.
Material and labour for PCC (1:4:8) type D-2 (using 40mm graded crushed stone aggregate) mechanically crushed stone for mass filling in pole pit and foundation etc including provision of necessary form work to achieve fair finished surfaces complete all as specified and directed.
Material and labour for PCC (1:3:6) type C-2 (using 40 mm graded crushed stone aggregate) as in pole foundation, stay pits etc including provision of necessary form work to aachieve fair finishes surfaces complete all as specified and directed.
Material and labour for PCC (1:2:4) type C-2 (using 40 mm graded crushed stone aggregate) as in pole foundation, coping, stay pits etc including provision of necessary form work to aachieve fair finishes surfaces, complete all as specified and directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers n.exc 25 cm thick layers complete all as specified and directed by Engineer-in-Charge.
Removal of excavated material n.exc 50 mtr away and depositing where directed at a level not exceeding 1.5 mtr above from starting point complete all as specified and directed by Engineer-in-Charge.
Dismantling and taking down old unserviceable steel poles any type after disconnecting all electrical connection incl clearance of site complete all as specified and directed by Engineer-in-Charge.
Supply and erection of steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP 31, 9 meter long incl providing synthetic enamel aluminium paint over one coat of red oxide and black and white strips with synthetic enamel paint 30 cm each alternatively upto 1.5 mtr above the coping of pole starting with black strip complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4.0 x 10-50 Sqmm complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-300 Sqmm complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 400 Sqmm complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5/4 x 25-50 Sqmm complete all as specified and directed by Engineer-in-Charge. Note: Earth work will be measured and paid separately.
Supply and fixing in replacement straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 70-150 Sqmm complete all as specified and directed by Engineer-in-Charge. Note: Earth work will be measured and paid separately.
Supply and fixing in replacement straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-400 Sqmm complete all as specified and directed by Engineer-in-Charge. Note: Earth work will be measured and paid separately.
Disconnecting & taking out defective underground cable any size and any type from trenches, pole, pipe, floor, wall etc complete all as specified and directed by Engineer-in-Charge.
Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 16 sqmm 4.0 core laid in trenches/ on poles/ road crossing or passing through existing/new pipe under road crossing, clamping on wall etc. complete all as specified and directed by Engineer-in-Charge. Note: (i) Earth work, sand, bricks , removing, returning filling Aluminium thimbles/lugs will be paid separately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii) All equipments , machinery or tools if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
Description all as per Item Ser No 20 here in before but for 3.5 core 25 Sqmm complete all as specified and directed by Engineer-in-Charge.
Description all as per Item Ser No 20 here in before but for 3.5 core 35 Sqmm complete all as specified and directed by Engineer-in-Charge.
Description all as per Item Ser No 20 here in before but for 3.5 core 50 Sqmm complete all as specified and directed by Engineer-in-Charge.
Description all as per Item Ser No 20 here in before but for 3.5 core 70 Sqmm complete all as specified and directed by Engineer-in-Charge.
Description all as per Item Ser No 20 here in before but for 3.5 core 95 Sqmm complete all as specified and directed by Engineer-in-Charge.
Description all as per Item Ser No 20 here in before but for 3.5 core 120 Sqmm complete all as specified and directed by Engineer-in-Charge.
Description all as per Item Ser No 20 here in before but for 3.5 core 150 Sqmm complete all as specified and directed by Engineer-in-Charge.
Description all as per Item Ser No 20 here in before but for 3.5 core 185 Sqmm complete all as specified and directed by Engineer-in-Charge.
Disconnecting & taking out defective underground cable any size and any type from roof, pole, pipe, floor, wall etc complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 Sq mm, 2 core, complete all as specified and directed by Engr-in-Charge. Note: Wherever cable fixing/connection, suitable thimble should be used as per site situation.
Description all as per Item Ser No 30 here in before but for 4 core 10 Sqmm complete all as specified and directed by Engineer-in-Charge.
Description all as per Item Ser No 30 here in before but for 2 core 16 Sqmm complete all as specified and directed by Engineer-in-Charge.
Material and labour for drilling hole of any size manually as per site requirement, drilling for laying pipes under the road for crossing electrical cables complete all as specified and directed by Engineer-in-Charge. Note: Pipe will be measured and paid for separately.
Repair/maint of existing burnt defective UG XLPE cable 1100 volt grade cable of any size complete with charges for trace out the fault, cutting/repair and jointing complete with using insulation tape, aluminium thimble, lugs, fitment of jointing kit, thimbles, necessary earth work complete all as specified and directed. Note: Aluminium thimble, lugs, jointing kit, thimbles, earth work shall be measured and paid seperately.
Supply and fixing in replacement of stay assembly complete with all accessories, such as stay plate 230X230X6 mm3, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc. all as per electrical plate No 1 orr SSR part 1 complete all as specified and directed by Engineer-in-Charge. Note: Only excavation and PCC work will be measured and paid separately.
Material and labour in replacement incl dismantling and taking down old cross arms, bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated and inclusive of one primercoat, one under coat and one finishing coat of paint complete all as specified and directed by Engineer-in-Charge.
Material and labour in replacement for shackle type porcelain vitreous white or brown insulator including GI straps, washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm height, 90 mm dia, section of strap 30mmx3mm & dia of bolt 12 mm complete all as specified and as directed by Engineer-in-Charge.
Material and labour in replacement for pin type insulator porcelain vitreous white or brown 1100 volts grade 100 mm height and 65 mm dia with GI spindle two GI washer and one GI nut complete all as specified and as directed by Engineer-in-Charge.
Dismantling and taking down old unserviceable ACSR conductor incl cutting, welding complete all as specified and directed by Engineer-in-Charge.
Material and labour for aluminium conductor steel reinforced (ACSR) including fixing, stretching on poles and proper noseling with binding wire with insulator of any size as required at site complete all as specified and as directed by Engineer-in-Charge.
Material and labour in replacement for 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm GI suspension wire, one twin core cable flat or circular of size 10 sqmm 2 core complete all as specified and directed by Engineer-in-Charge.
Material and labour in replacement for 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm GI suspension wire, one twin core cable flat or circular of size 6 sqmm 2 core complete all as specified and directed by Engineer-in-Charge.
Material and labour in replacement for 1100 volts grade heavy duty cable PVC insulated solid aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm GI suspension wire, one twin core cable flat or circular of size 4 sqmm 2 core complete all as specified and directed by Engineer-in-Charge.
Dismantling and taking down old u/s earthing and Material & labour for earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick buried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth strip of size 25x4mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, pit cover 50mm thick RCC 1:2:4 type B-1 using 8mm tor steel bars @10cm C/C both ways, 40mm bore medium grade GI protection pipe, watering pipe 20mm bore medium grade, funnel, wire mesh, also including earth work, common salt, charcoal dust complete all as specified and as directed by Engineer-in-Charge.
Dismantling and taking down old u/s earthing and Material & labour for earthing complete with galvanized steel earth electrode plate of size 60x60x6mm thick buried directly in ground/earth pit not less than 2.25 mtr deep below normal ground level and top edge of earth electrode not less than 1.5 mtr below normal ground level and connected with GI earth wire of size 4 mm by means of nut, bolts, washers etc to eqpt/machinery all as shown in electric plate No 3 of SSR Pt I including PCC (1:3:6) pit, pit cover 50mm thick RCC 1:2:4 type B-1 using 8mm tor steel bars @10cm C/C both ways, 20 mm bore medium grade GI protection pipe, watering pipe 20mm bore medium grade, funnel, wire mesh, also including earth work, common salt, charcoal dust complete all as specified and as directed by Engineer-in-Charge.
Material and labour for fixing in replacement GI tubing 50 mm bore light grade, on poles,on walls, under floors, road crossing, as reqd at site complete all as specified and directed by Engineer-in-Charge. Note: Clamps, Nut bolts, saddle etc will be measured and paid separately.
Material and labour for fixing in replacement GI tubing 80 mm bore light grade, on poles,on walls, under floors, road crossing, as reqd at site complete all as specified and directed by Engineer-in-Charge. Note: Clamps, Nut bolts, saddle etc will be measured and paid separately.
Supply and fixing in replacement MCCB TPN 400 Amps , 415 Volts, 50 KA ,4 POLE, Ics=100% Icu ,overload adjustable short circuit adjustable type incl complete connection complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement MCCB TPN 250 Amps , 415 Volts, 40 KA ,4 POLE, Ics=100% Icu , overload adjustable short circuit adjustable type incl complete connection complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement MCCB TPN 200 Amps , 415 Volts, 25 KA ,4 POLE, Ics=100% Icu , overload adjustable short circuit adjustable type incl complete connection complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement MCCB TPN 160 Amps , 415 Volts, 25 KA ,4 POLE, Ics=100% Icu , overload adjustable short circuit fixed type incl complete connection complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement MCCB TPN 100 Amps , 415 Volts, 25 KA ,4 POLE, Ics=100% Icu , overload adjustable short circuit fixed type incl complete connection complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of PVC fibre separator for LT line 1100 volt OH conductor 3 wire system for maintaining horizontal spacing of conductor complete with nut and bolt in a span complete all as specified and directed.
Supply and fixing in replacement of PVC fibre separator for LT line 1100 volt OH conductor 4 wire system for maintaining horizontal spacing of conductor complete with nut and bolt in a span complete all as specified and directed.
Supply and fixing in replacement of PVC fibre separator for LT line 1100 volt OH conductor 5 wire system for maintaining horizontal spacing of conductor complete with nut and bolt in a span complete all as specified and directed.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 50 sqmm incl dismantling old thimbles of any type complete all as specified and directed.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 70-185 sqmm incl dismantling old thimbles of any type complete all as specified and directed.
Material and labour for fixing aluminium terminals (thimbles) in 1100 volt LT XLPE cable upto size 240-400 sqmm incl dismantling old thimbles of any type complete all as specified and directed.
Material and labour for shifting heavy items / excavating / cleaning areas / clearing site by providing crane/hydra/excavators/tractors/trolley etc as required at site complete all as specified and as directed.
Supply and fixing in replacement unsv indicators LED set of three as per existing size and sample complete all as specified and directed by Engr-in-Charge.
Material & Labour for surface cleaning of steel tubular poles LT 9 mtrs long including removing rusted particles and painting with two coats of synthetic enamel aluminium paint including cross arms, bracing, supports, clamps, eye hooks, security light bracket, clamp etc and providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl repairing and painting on coping with cement base white paint complete all as specified and directed by Engr-in-Charge. Note: (i) The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the repairing of coping with cement / PCC.
Material & Labour for cement based white/off white paint for PCC pole 9 mtr long, top to bottom and above 1.5 mtr from GL including black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint including cross arms, bracing, supports, clamps, eye hooks, security light bracket, clamp etc incl repairing and painting on coping with cement base white paint complete all as specified and directed by Engr-in-Charge. Note: (i) The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the repairing of coping with cement / PCC.
Supply and fixing in repair On load change over switch with Sheet Steel Enclosure 415 V, 4 pole, 100 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cables from LT panels to change over switches complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair On load change over switch with Sheet Steel Enclosure 415 V, 4 pole, 200 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cables from LT panels to change over switches complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair On load change over switch with Sheet Steel Enclosure 415 V, 4 pole, 315 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cables from LT panels to change over switches complete all as specified and directed by Engr-in-Charge.
Supply and fixing and fabrication Street light bracket made out of GI tubing suitable for 45/60/90 watt LED light light grade upto 1.2 mtr length, bend to shape suitable for security light fitting with necessary MS clamps with one coat of red oxide and two coats of aluminium paint including nut, bolt, washers etc and including taking out unserviceable bracket and removing from site of work complete all as specified and directed.
Labour for repair/maint to Old/Unserviceable LED security/Street/flood light of any capacity incl taking down existing fitting from pole/Bldg for repair of driver ,cable terminal block and connection wire and refixing the same in position after repair incl testing complete all as specified and directed by Engr-in-Charge. Note: spares shall be measured and paid seperately under respective item.
Taking down unserviceable Street/Security light fitting of any type from the pole/bldg after disconnecting electric connection carefully for repl of drivers complete all as specified and directed (Note: Repair/replacement of spares shall be measured seperately)
Supply and fixing in replacement of electronic driver of cap 45 watt of existing make for LED street light fitting complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of electronic driver of cap 60 watt of existing make for LED street light fitting complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of electronic driver of cap 90 watt of existing make for LED street light fitting complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of electronic driver of cap 120 watt of existing make for LED street light fitting complete all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of electronic driver of cap 200 watt of existing make for LED Flood light fitting complete all as specified and directed by Engr-in-Charge.
Dismantling and taking down old unsv street/security lights and Material and labour for new LED street light fittings of 30 watt, suitable for upto 50 mm OD holder fixed on existing pole, system wattage and high preesure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66 protection suitable for pole mounting SMD led array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -20ºC to 60ºC,built in surge protection more than 10kV with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engr-in-Charge.
Dismantling and taking down old unsv street/security lights and Material and labour for new LED street light fittings of 45 watt, suitable for upto 50 mm OD holder fixed on existing pole, system wattage and high preesure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66 protection suitable for pole mounting SMD led array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -20ºC to 60ºC,built in surge protection more than 10kV with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engr-in-Charge.
Dismantling and taking down old unsv street/security lights and Material and labour for new LED street light fittings of 60 watt, suitable for upto 50 mm OD holder fixed on existing pole, system wattage and high preesure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66,TOP opening separate driver compartment with frame, suitable for pole mounting SMD led array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -20ºC to 60ºC,built in surge protection more than 10kV with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engr-in-Charge.
Dismantling and taking down old unsv street/security lights and Material and labour for new LED street light fittings of 90 watt, suitable for upto 50 mm OD holder fixed on existing pole, system wattage and high preesure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66,TOP opening separate driver compartment with frame, suitable for pole mounting SMD led array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -20ºC to 60ºC,built in surge protection more than 10kV with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engr-in-Charge.
Dismantling and taking down old unsv street/security lights and Material and labour for new LED street light fittings of 120 watt, suitable for upto 50 mm OD holder fixed on existing pole, system wattage and high preesure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66,TOP opening separate driver compartment with frame suitable for pole mounting SMD led array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -20ºC to 60ºC,built in surge protection more than 10kV with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engr-in-Charge.
Dismantling and taking down old unsv street/security lights and Material and labour for new LED flood light fittings of 120 watt, system wattage and high preesure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66 protection suitable for pole mounting SMD led array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 90 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -20ºC to 60ºC,built in surge protection more than 10kV with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engr-in-Charge.
Dismantling and taking down old unsv street/security lights and Material and labour for new LED flood light fittings of 200 watt system wattage and high preesure die cast aluminium housing with sealed toughened glass cover, silicon gasket for IP-66 protection suitable for pole mounting SMD led array with lense, cool white 6500 K, LED efficacy >120 lm/W and system efficacy 90 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -20ºC to 60ºC,built in surge protection more than 10kV with facility of power supply shall be removed without removing light fitting from pole incl make proper connection complete including cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engr-in-Charge.
Taking down old unsv timer switches and Supply and fixing of Automatic street light control with infrared sensor based NATURE SWITCH and VOLTAGE MONITORING SYSTEM (VMS) Single phase load of 8 KW for automation of street lights. Nature Switch operation should be based on Natural light Lux level. Required illuminance level for switching ON is < 30 Lux and for switching OFF > 30 Lux. The sensor should also have part night operation facility of min. 4 hrs. to max. 12 hrs. VMS should have adjustable over & under Voltage trip level and protection against phase loss, neutral loss & Phase reverse incl Power contactors (1 nos of capacity 63 amps per phase each) and incoming (1 nos of capacity 63 amps each)- outgoing MCB(1 nos of capacity 63 amps each) & main load circuit wiring (Copper) of minimum 16 sqmm. The sensor , VMS, Power contactor, MCBs incl connected items should be enclosed in a Pole/wall mountable enclosure made of rust proof, electric shock proof,termite proof and FR grade SMC junction box conforming to IP54 complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repair SMC Pole mounted box of size 10"x 8"x 4" with hinged door incl Clamp, nuts, bolts and washers, Make:- Syntex or equivelent of Hansel / Press fit complete all as specified and directed The Box includes :(a) MCB SP 10 Amp, 10 kA 'C' Series mounted on din rail-1 No. (b) Connector block suitable for 3ph, 4 wire min 16 sqmm cable-1 No
Material and labour in replacement of PVC insulated and sheathed cable of size 1.5 sqmm 3 core copper conductor multistranded 1100 volt grade 230 volts running through PVC conduit of dia 20 mm with strip clamping on poles at 3 places complete all as specified and directed by Engr-in-Charge.
Supply and installation including replacement of all in one integrated Solar street light 30 watt compact, aesthetic, eco friendly and modern integrated solar street light in extruded aluminium housing with high efficiency monocrystlline silicon photo voltaic panel, high efficiency SMD LED 6500K having secondary lens optics for street light distribution, high performance lithium battery, MPPT charge controller and intelligent control module/sensor with higher reliability, long service life, incl pole upto 4 mtr height for mounting of solar lights, suitable for easy and quick installation, PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) complete all as specified and directed.
Supply and fixing in replacement of 1100 Volt Arial bunched cable having 4 core conductor equal size of multistranded compacted circular aluminium conductor screen of extruded semi conducting compound extruded XLPE insulated , insulation screen of extruded semi conducting compound over all metellic screen of copper tape extruded PVC type ST-2 sheathed twisted around bare aluminium alloy messenger generally as per IS 7098 Part-II of size 4x50 sqmm + 1 x 35 sqmm ACSR messenger conductor complete with dead end clamp,suspension clamp,Eye Hook ,welding and cable Jointing Kit as per site requirement with the existing LT disribution system complete all as specified and directed by Engr-in-Charge.
Description all as per srl item No-87 above size 4x 70 sqmm + 1 x 50 sqmm complete all as specified and directed by Engr-in-Charge.
Description all as per srl item No-87 above size 4x 95 sqmm + 1 x 70 sqmm complete all as specified and directed by Engr-in-Charge.
Sarbat Construction Co
M/s Sahib Construction and engineers
M/S RAJ ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .