Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.9 LAdmitted-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹24.9 L | L1 | Admitted-Finance |
| 2 | L2₹29.0 L+₹4.1 L (16.5%)Admitted-Finance SECTOR 10 PANCHKULA | PANCHKULA | PANCHKULA | HARYANA | ₹29.0 L+₹4.1 L (16.5%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/s Friends Engineering Works L2 | R D Bansal L1 |
|---|---|---|---|---|---|
| 1.00 | Suppy, installing, connecting, commissioning and testing of energy effficient transformer (level 2 of IS 1180 as per latest amendments of 2014) of capacity 400 KVA outddoor type, mounted on four pole structure, step down 11/0.433 KV, core type oil immersed, copper wound, natural oil cooled with external cooling tubes/radiators, having 3 phase 50 Hz AC supply, DYn-11 design, off load tap changer on HT side to vary secondary voltage ±7.5% in steps of 2.5% as per IS 1180 (Pt-I to III) with all standerd accessories including bushing on HT side, cable box on LT side, including first filling of new transformer oil (of di-electric strength not less than 60 KV) upto required level in conservator tank , complete all as specified and directed by Engineer-in-Charge. with and including the following :-
(a) One No 100 mm dia, dial type thermometer with resetting device vapour pressure type having range 0 to 120 degree centigrade.
(b) Rating plate and terminal marking plate.
(c) Two earthing terminals for body earthing and two additional for neutral brought out on a bushing.
(d) Oil level gauge with max & min level marking.
(e) Oil filter valve.
(f) Oil drain valve. | 1 | Each | 13,75,000 ₹13,75,000 | 13,45,000 ₹13,45,000 Lowest |
| 2.00(g) Lifting hooks. (h) Oil conservator with filling hole and cap. (j) Air relief valve plug. (l) Earth bushing for neutral outside the LT cable box for providing independent earthing for neutral. (m) Clear view type silica gel breather with first fill of fresh bluish color silica gel. Note :- [1] The transformer should be as per level 2 of IS 1180(2014) and energy conservation (Energy conservation Binary Corps) for which necessasry test certificate to be produced by contractor from manufacturer of the transformer. [2] Four pole structure and related items shall be measured and paid separately under respective items. [3] Pre dispatch inspection of transformer shall be carried out by the Rep of Accepting officer. All factory inspeection arrangments will be co-ordinated by the contractor. [4] Transformer shall be tested and commissioned by SEI after installing at site.All the T&P,testing equipments required for the same shall be arranged by the contractor and unit rate quoted will be deemed to included the cost of the same. | |||||
| 3.00 | Supply and laying of HT electric power cable crossed linked polyethylene XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, (heavy duty) with aluminium conductor, 11000 volts Earthed, grade of size 95 sqmm cross sectional area, 3.0 core ,laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers including jointing and testing , complete all as specified and directed by Engineer-in- Charge.
Note: Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items. | 100 | RM | 1,600 ₹1,60,000 | 1,039 ₹1,03,900 Lowest |
| 4.00 | Supply and laying of HT electric power cable crossed linked polyethylene XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, (heavy duty) with aluminium conductor, 11000 volts Earthed, grade of size 120 sqmm cross sectional area, 3.0 core ,laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers including jointing and testing , complete all as specified and directed by Engineer-in- Charge.
Note: Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items. | 488 | RM | 1,750 ₹8,54,000 | 1,100 ₹5,36,800 Lowest |
| 5.00 | Supply and laying of LT under ground electric power cable crossed linked polyethylene ( XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 120 sqmm cross sectional area, 3.5 core ,laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers including jointing and testing , complete all as specified and directed by Engineer-in- Charge.
Note: Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items. | 70 | RM | 850 ₹59,500 | 580 ₹40,600 Lowest |
| 6.00 | Supply and fixing of Outdoor end termination joint kit (heat shrinkable) complete with jointing material and accessories suitable for 3wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 95 Sqmm size cable in and including jointing & testing ,complete all as specified and as directed by Engineer in charge. | 1 | Each | 3,000 ₹3,000 | 2,000 ₹2,000 Lowest |
| 7.00 | Supply and fixing of Outdoor end termination joint kit (heat shrinkable) complete with jointing material and accessories suitable for 3 wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 120 Sqmm size cable in and including jointing & testing ,complete all as specified and as directed by Engineer in charge. | 2 | Each | 3,000 ₹6,000 | 2,000 ₹4,000 Lowest |
| 8.00 | Supply and fixing of Indoor end termination joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 3 wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 95 Sqmm size cable in and including jointing & testing ,complete all as specified and as directed by Engineer in charge. | 1 | Each | 3,000 ₹3,000 | 1,800 ₹1,800 Lowest |
| 9.00 | M&L for Earthing complete with galvanised steel plate earth electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25 meter below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to GI strip 32x6mm at two points by means of bolts and nut, check nut and washers including charcoal dust, common salt, necessary excavation in hard/dense soil, returning filling in and removal of surplus soil to a distance up to 50metres, PCC pit in 1:3:6 type CI (using 20mm grade stone aggregate) RCC 1:2:4 type B-1 (using 20mm grade stone aggregate ) 80mm thick pit cover, reinforced XPM of weight not less than 4 kg/ Sqm, complete all as specified and as directed by Engineer-in-Charge, both ways MS handle 12mm dia, GI funnel, wire mesh and GI watering pipe of 20mm bore GI (light grade) and earth lead protection pipe 40mm bore (light grade) all as specified, directed and shown in electrical plate No 3 of SSR Part-I and testing , complete all as specified and as directed by Engineer-in-Charge.
Note :- (i) The unit rate includes earth lead and protection pipe up to maximum 7.5 metre from earth plate to earth point/test point.
(ii) Earth pit shall be constructed minimum 0.5 metre away from earth.
(iii) Quoted rate of this item is deemed to inclusive cost of all the itmes mentioned therein such as earth work, PCC ,Form work etc and nothing extra shall be admissible on this account . | 4 | Each | 5,500 ₹22,000 | 4,000 ₹16,000 Lowest |
| 10.00 | M& L for earthing complete with using copper plate 90×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead , buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to 20x3.15mm copper strip by means of exothermic brazing & protected by GI pipe light grade 40mm bore all as shown in electrical plate No. 3 connected to earthing test point and including necessary excavation and earth work in any type of soil,20 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, pit cover of precast RCC (1;2:4), type B-1 reinforced XPM of weight not less than 4 Kg/Sqm and MS frame etc, complete & connected to earthing test point all as specified or indicated inculding brazing/testing on completion.
Notes:-
(i) The unit rate includes Copper strip and protection pipe upto (maximum 7.5 metre from earth plate) earth point/test point.
(ii) The complete earth system shall be guaranteed to give result less than 1 ohm resistance. | 2 | Each | 25,000 ₹50,000 Lowest | 76,000 ₹1,52,000 |
Tender Value
Refer Docs
EMD Value
₹48,520
Closing Date
25 Aug 2026, 6:00 pmClosed
CWE AF CHANDIGARH
Headquarters Commander Works Engineers (AF) Chandigarh-160003
PROVN OF CHARGING STATION OF 240KW AND SHIFTING OF OH HT LINE TO UG WITH ALLIED WORKS AT GE (AF) CHANDIGARH
2026_MES_781352_1
CWE/AF CHD/CHD/T-14/2026-2027
Open Tender
Civil Works
Item Rate
180 days
Chandigarh
As per NIT
8 documents required · 8 mandatory
₹500
GE (AF) Chandigarh
₹48,520
3 Sept 2026
28 Jul 2026
1 Sept 2026
28 Jul 2026
25 Aug 2026
11 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Suppy, installing, connecting, commissioning and testing of energy effficient transformer (level 3 of IS 1180 as per latest amendments of 2014) of capacity 400 KVA outddoor type, mounted on four pole structure, step down 11/0.433 KV, core type oil immersed, copper wound, natural oil cooled with external cooling tubes/radiators, having 3 phase 50 Hz AC supply, DYn-11 design, off load tap changer on HT side to vary secondary voltage ±7.5% in steps of 2.5% as per IS 1180 (Pt-I to III) with all standerd accessories including bushing on HT side, cable box on LT side, including first filling of new transformer oil (of di-electric strength not less than 60 KV) upto required level in conservator tank , complete all as specified and directed by Engineer-in-Charge. with and including the following :-
(a) One No 100 mm dia, dial type thermometer with resetting device vapour pressure type having range 0 to 120 degree centigrade.
(b) Rating plate and terminal marking plate.
(c) Two earthing terminals for body earthing and two additional for neutral brought out on a bushing.
(d) Oil level gauge with max & min level marking.
(e) Oil filter valve.
(f) Oil drain valve. | 1 | Each | - | - |
| 2 | (g) Lifting hooks.
(h) Oil conservator with filling hole and cap.
(j) Air relief valve plug.
(l) Earth bushing for neutral outside the LT cable box for providing independent earthing for neutral.
(m) Clear view type silica gel breather with first fill of fresh bluish color silica gel.
Note :-
[1] The transformer should be as per level 3 of IS 1180(2014) and energy conservation (Energy conservation Binary Corps) for which necessasry test certificate to be produced by contractor from manufacturer of the transformer.
[2] Four pole structure and related items shall be measured and paid separately under respective items.
[3] Pre dispatch inspection of transformer shall be carried out by the Rep of Accepting officer. All factory inspeection arrangments will be co-ordinated by the contractor.
[4] Transformer shall be tested and commissioned by SEI after installing at site.All the T&P,testing equipments required for the same shall be arranged by the contractor and unit rate quoted will be deemed to included the cost of the same. | - | - | - | - |
| 3 | HT electric power cable crossed linked polyethylene XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, (heavy duty) with aluminium conductor, 11000 volts Earthed, grade of size 95 sqmm cross sectional area, 3.0 core ,laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers including jointing and testing , complete all as specified and directed by Engineer-in- Charge.
Note: Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items. | 100 | RM | - | - |
| 4 | HT electric power cable crossed linked polyethylene XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, (heavy duty) with aluminium conductor, 11000 volts Earthed, grade of size 120 sqmm cross sectional area, 3.0 core ,laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers including jointing and testing , complete all as specified and directed by Engineer-in- Charge.
Note: Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items. | 488 | RM | - | - |
| 5 | LT under ground electric power cable crossed linked polyethylene ( XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 120 sqmm cross sectional area, 3.5 core ,laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers including jointing and testing , complete all as specified and directed by Engineer-in- Charge.
Note: Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items. | 70 | RM | - | - |
| 6 | Outdoor end termination joint kit (heat shrinkable) complete with jointing material and accessories suitable for 3wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 95 Sqmm size cable in and including jointing & testing ,complete all as specified and as directed by Engineer in charge. | 1 | Each | - | - |
| 7 | Outdoor end termination joint kit (heat shrinkable) complete with jointing material and accessories suitable for 3 wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 120 Sqmm size cable in and including jointing & testing ,complete all as specified and as directed by Engineer in charge. | 2 | Each | - | - |
| 8 | Indoor end termination joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 3 wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 95 Sqmm size cable in and including jointing & testing ,complete all as specified and as directed by Engineer in charge. | 1 | Each | - | - |
| 9 | Earthing complete with galvanised steel plate earth electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25 meter below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to GI strip 32x6mm at two points by means of bolts and nut, check nut and washers including charcoal dust, common salt, necessary excavation in hard/dense soil, returning filling in and removal of surplus soil to a distance up to 50metres, PCC pit in 1:3:6 type CI (using 20mm grade stone aggregate) RCC 1:2:4 type B-1 (using 20mm grade stone aggregate ) 80mm thick pit cover, reinforced XPM of weight not less than 4 kg/ Sqm, complete all as specified and as directed by Engineer-in-Charge, both ways MS handle 12mm dia, GI funnel, wire mesh and GI watering pipe of 20mm bore GI (light grade) and earth lead protection pipe 40mm bore (light grade) all as specified, directed and shown in electrical plate No 3 of SSR Part-I and testing , complete all as specified and as directed by Engineer-in-Charge.
Note :- (i) The unit rate includes earth lead and protection pipe up to maximum 7.5 metre from earth plate to earth point/test point.
(ii) Earth pit shall be constructed minimum 0.5 metre away from earth.
(iii) Quoted rate of this item is deemed to inclusive cost of all the itmes mentioned therein such as earth work, PCC ,Form work etc and nothing extra shall be admissible on this account . | 4 | Each | - | - |
| 10 | M& L for earthing complete with using copper plate 90×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead , buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to 20x3.15mm copper strip by means of exothermic brazing & porected by GI pipe light grade 40mm bore all as shown in electrical plate No. 3 connected to earthing test point and including necessary excavation and earth work in any type of soil,20 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, pit cover of precast RCC (1;2:4), type B-1 reinforced XPM of weight not less than 4 Kg/Sqm and MS frame etc, complete & connected to earthing test point all as specified or indicated inculding brazing/testing on completion.
Notes:-
(i) The unit rate includes galvanised Iron strip and protection pipe upto (maximum 7.5 metre from earth plate) earth point/test point.
(ii) The complete earth system shall be guaranteed to give result less than 1 ohm resistance. | 2 | Each | - | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.47 MB
TenderDocumentsT14.pdf
Tender Documents • 1.13 MB
BOQ_875324.xls
BOQ • 1.20 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .