Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.6 LAccepted-AOC SHOP NO 259 LOHOGAON ROAD KALWAD KHANDVE NAGAR PUNE 411032 | PUNE | MAHARASHTRA | 411032 | ₹38.6 L Quoted ₹43.7 L | L1 | Accepted-AOC BEING LOWEST |
| 2 | L2₹44.7 L+₹1.1 L (2.49%)Rejected-Finance | ₹44.7 L+₹1.1 L (2.49%) | L2 | Rejected-Finance NOT LOWEST |
| 3 | L3₹48.8 L+₹5.2 L (11.8%)Rejected-Finance 3RD FLOOR BHAKTAMAR RESIDENCY SOMNATHNAGAR ROAD PUNE 411014 | PUNE | PUNE | MAHARASHTRA | 411014 | ₹48.8 L+₹5.2 L (11.8%) | L3 | Rejected-Finance NOT LOWEST |
| 4 | L4₹49.2 L+₹5.6 L (12.8%)Rejected-Finance 1101 A WING SACHDEV COMPLEX JANGAL MANGAL RAOD BHANDUP W MUMBAI 400078 | MUMBAI SUBURBAN | MAHARASHTRA | 400078 | ₹49.2 L+₹5.6 L (12.8%) | L4 | Rejected-Finance NOT LOWEST |
| 5 | L5₹53.1 L+₹9.4 L (21.5%)Rejected-Finance | ₹53.1 L+₹9.4 L (21.5%) | L5 | Rejected-Finance NOT LOWEST |
| Sl No | Description | Qty | Unit | SHRI SULAI ELECTRICALS L6 | Maruti Abhiyantriki L2 | Rama Electricals L1 | sapana enterprises L4 | United Enterprises L5 | Adinath Technical Services L3 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Preventive maintenace/ servicing of 11KV VCBs of make CG/ABB of capacity 400Amp/ 800Amps by dismantling of breaker mechanism checking the various critical setting in mechanism, checking of spring charging mechanism, checking of pole contact setting, greasing/ lubricating of mechanism moving parts, checking of contact pressure, alignment and adjusting the same, adjusting of spring charging mechanism & triping test trial & testing of VCBs for smooth and correct fuctioning. Calibration of over load current and earth fault relay of make L&T/ Ashida/ CG through secondry injection method with artificial load for 11 KV all as specified & directed. | 16 | Job | 4,500 ₹72,000 | 4,000 ₹64,000 | 2,500 ₹40,000 Lowest | 5,500 ₹88,000 | 5,598 ₹89,568 | 5,500 ₹88,000 |
| 2.00 | Preventive maintenace/ servicing of 33 KV VCBs/ 400 Amps of make ALSTOM/CG/ABB by dismantling of breaker mechanism checking the various critical setting in mechanism, checking of spring charging mechanism, checking of pole contact setting, greasing/ lubricating of mechanism moving parts, checking of contact pressure, alignment and adjusting the same, adjusting of spring charging mechanism & triping test trial & teting of VCBs for smooth and correct fuctioning. Calibration of over load current and earth fault relay of make L&T/ Ashida/ CG through secondry injection method with artificial load for 33 KV all as specified & directed. | 4 | Job | 5,000 ₹20,000 | 4,000 ₹16,000 | 3,000 ₹12,000 Lowest | 5,500 ₹22,000 | 5,712 ₹22,848 | 5,500 ₹22,000 |
| 3.00 | M&L for replacement of old silica gel breather container with new one of suitable capacity (500g-1000g) complete all as specified for trasformer 63 KVA to 500 KVA all as directed. | 20 | Each | 310 ₹6,200 | 1,000 ₹20,000 | 300 ₹6,000 Lowest | 600 ₹12,000 | 540 ₹10,800 | 1,500 ₹30,000 |
| 4.00 | Supply and fill silica gel crystal in the transformer breather container all as directed at site | 18 | Kg | 100 ₹1,800 Lowest | 250 ₹4,500 | 100 ₹1,800 Lowest | 450 ₹8,100 | 214 ₹3,852 | 500 ₹9,000 |
| 5.00 | Filtration of Oil of serviceable distribution/power transformers at site in running condition by heating process taking out the moisture and impurities under vacuum and refilling in transformer upto required level having Die-electric strength not less than 40 KV for 2.5 mm Gap all as specified and directed | 35,000 | Ltrs | 10 ₹3,50,000 | 6 ₹2,10,000 | 3 ₹1,05,000 Lowest | 7 ₹2,45,000 | 8 ₹2,80,000 | 5 ₹1,75,000 |
| 6.00 | M&L replacement of Drain Plug of Transformers as per existing size and make up to 500 KVA all as specified and directed | 3 | Nos | 60 ₹180 Lowest | 500 ₹1,500 | 200 ₹600 | 300 ₹900 | 332 ₹996 | 300 ₹900 |
| 7.00 | M&L for repairs to leaking trasformers at site up to 500 KVA by opening the top cover, draining the transformer oil to the level just below the bushing, replacing the unserviceable bushings on HT< side with connecting rod, replacing the oil gaskets of bushings on HT & LT side, replacing the top oil gasket, reassembling, testing etc complete including all materials required at site all as directed by Engr-in-Charge | 8 | Job | 7,500 ₹60,000 | 5,000 ₹40,000 | 2,000 ₹16,000 Lowest | 3,000 ₹24,000 | 2,688 ₹21,504 | 2,500 ₹20,000 |
| 8.00 | M&L for Filling/topping of new transformer oil at various locations at site as directed, transformer oil Confirming to IS: 335 having dielectric strength not less than 40 KV complete including centrifuging of oil (if required) to acheive required dielectric strength not less tha 40 KV for 2.5mm gap all as specified and directed by the Engineer-in-Charge
Note : Transformer oil shall be supply only in sealed barrel/containers and the quoted rates deemed to include the cost of all required T&P & transportation | 1,000 | Ltr | 200 ₹2,00,000 | 90 ₹90,000 Lowest | 90 ₹90,000 Lowest | 110 ₹1,10,000 | 106 ₹1,06,000 | 140 ₹1,40,000 |
| 9.00 | Supply and fix in replacement control switch (T&C), 4 pole, 25 Amps for 11 KV VCB all as specified and directed | 4 | Each | 1,250 ₹5,000 | 1,500 ₹6,000 | 5,000 ₹20,000 | 3,000 ₹12,000 | 2,976 ₹11,904 | 900 ₹3,600 Lowest |
| 10.00 | S&F in replacement Ammeter digital type with 3 Ph( R-Y-B) of rating 0-100 Amps, digital type of make- ELMEASSURE Model no- SL 1330 for existing 11 KV VCBs, of make- CG and making all necessary electrical connections all as specified and directed by Engineer-in-charge. | 2 | Each | 1,200 ₹2,400 | 1,500 ₹3,000 | 1,100 ₹2,200 | 1,550 ₹3,100 | 1,485 ₹2,970 | 500 ₹1,000 Lowest |
Tender Value
₹61.8 L
EMD Value
₹1.2 L
Closing Date
17 Jul 2026, 6:00 pmClosed
CWE DEOLALI
HQ CWE DEOLALI, ONSLOW ROAD, DEOLALI (MH) 422401
AS PER TENDER DOCUMENTS
2026_MES_771717_1
86103/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE DEOLALI
AS PER NIT
7 documents required · 7 mandatory
₹1,000
Yes
GE DEOLALI
₹1.2 L
Yes
18 Sept 2026
12 Jun 2026
24 Jul 2026
12 Jun 2026
17 Jul 2026
3 Jul 2026
13 Jun 2026 - 26 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Preventive maintenace/ servicing of 11KV VCBs of make CG/ABB of capacity 400Amp/ 800Amps by dismantling of breaker mechanism checking the various critical setting in mechanism, checking of spring charging mechanism, checking of pole contact setting, greasing/ lubricating of mechanism moving parts, checking of contact pressure, alignment and adjusting the same, adjusting of spring charging mechanism & triping test trial & testing of VCBs for smooth and correct fuctioning. Calibration of over load current and earth fault relay of make L&T/ Ashida/ CG through secondry injection method with artificial load for 11 KV all as specified & directed. | 16 | Job | 100 | ₹1,600 |
| 2 | Preventive maintenace/ servicing of 33 KV VCBs/ 400 Amps of make ALSTOM/CG/ABB by dismantling of breaker mechanism checking the various critical setting in mechanism, checking of spring charging mechanism, checking of pole contact setting, greasing/ lubricating of mechanism moving parts, checking of contact pressure, alignment and adjusting the same, adjusting of spring charging mechanism & triping test trial & teting of VCBs for smooth and correct fuctioning. Calibration of over load current and earth fault relay of make L&T/ Ashida/ CG through secondry injection method with artificial load for 33 KV all as specified & directed. | 4 | Job | 100 | ₹400 |
| 3 | M&L for replacement of old silica gel breather container with new one of suitable capacity (500g-1000g) complete all as specified for trasformer 63 KVA to 500 KVA all as directed. | 20 | Each | 10 | ₹200 |
| 4 | Supply and fill silica gel crystal in the transformer breather container all as directed at site | 18 | Kg | 10 | ₹180 |
| 5 | Filtration of Oil of serviceable distribution/power transformers at site in running condition by heating process taking out the moisture and impurities under vacuum and refilling in transformer upto required level having Die-electric strength not less than 40 KV for 2.5 mm Gap all as specified and directed | 35,000 | Ltrs | 10 | ₹3,50,000 |
| 6 | M&L replacement of Drain Plug of Transformers as per existing size and make up to 500 KVA all as specified and directed | 3 | Nos | 10 | ₹30 |
| 7 | M&L for repairs to leaking trasformers at site up to 500 KVA by opening the top cover, draining the transformer oil to the level just below the bushing, replacing the unserviceable bushings on HT< side with connecting rod, replacing the oil gaskets of bushings on HT & LT side, replacing the top oil gasket, reassembling, testing etc complete including all materials required at site all as directed by Engr-in-Charge | 8 | Job | 10 | ₹80 |
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
BOQ_864169.xls
BOQ • 0.30 MB
86103TENDERDOCSALL.pdf
Tender Documents • 1.92 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .