Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.9 LAccepted-Finance | L1 | Accepted-Finance L1 | |
| 2 | L2₹13.8 L+₹1.8 L (15.4%)Accepted-Finance | L2 | Accepted-Finance L2 | |
| 3 | L3₹13.8 L+₹1.9 L (15.5%)Accepted-Finance | L3 | Accepted-Finance L3 | |
| 4 | L4₹15.9 L+₹4.0 L (33.7%)Accepted-Finance | L4 | Accepted-Finance L4 | |
| 5 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Others-The Bidder has been rejected due to want of Work Experience as per as SBD Clause |
Tender Value
₹20.1 L
EMD Value
₹41,000
Closing Date
25 Aug 2023, 4:00 pmClosed
Executive Engineer
Office of the Executive Engineer Electric Division Vijaypur, JPDCL Jammu
Improvement of HT/LT network by way of shifting of substation along with Laying of HT and LT Line on turnkey basis at village Suchani within the jurisdiction of Electric Division Vijaypur, JPDCL, Jammu
2023_PDD_223545_1
EDV/ 22 of 2023-2024 Dated 03-08-2023
Open Tender
Electrical Works
Turn-key
45 days
Samba District
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,000
Executive Engineer Electric Division Vijaypur
₹41,000
17 Nov 2023
3 Aug 2023
26 Aug 2023
4 Aug 2023
25 Aug 2023
4 Aug 2023
4 Aug 2023 - 25 Aug 2023
Amount
SCOPE OF WORKS FOR DISMANTLING OF EXISTING 100 KVA DISTRIBUTION SUB STATION
Dismantling of 11/0.433 KV, 100 KVA 3-Phase Distribution Transformer .
Dismantling of 9 Mtr Long PCC Pole including back filling of soil & consolidating by ramming, watering etc.
Dismantling of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc including all necessary Nut & Bolts & Washers etc.
Dismantling of 11 KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type
Dismantling of 11 KV Horn Gap Fuse Set, 3 Phase 200A
Dismantling of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Dismantling of 185 mm² Single-Core Cable,1.1kV Grade, PVC InsulatedStranded Conductor FRLS type
Dismantling of Distribution Box for 100 kVA DTR with MCCB for incomer & SFU's for OutgoingCircuits
Dismantling of Earthing of substation
Dismantling of 11kV Polymeric composite Pin Insulator
Dismantling of 11kV Polymeric composite Disc Insulator
Dismantling of Anti Climbing device with Clamps
Dismantling of Danger Plates with Clamps
Dismantling of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm),nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mmdiameter solid GS stay rod & 7/3.15 mm dia GIstranded wire complete
SCOPE OF WORKS RE-ERECTION OF 100 KVA DISTRIBUTION TRANSFORMER AT NEW SITE.
Installation testing & commissioning of 11/0.433 KV,100KVA 3-Phase Distribution Transformer. (Dismantled transformer to be re-erected.)
Re-Erection of 9 Mtr Long PCC Pole (WL-300 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc including all necessary Nut & Bolts & Washers etc.
Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type
Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Installation, Testing & Commissioning of Gapless Surge Arrestor,9 kV ,10 kA ,LA withpolymer housing, Stn. Type
Installation, Testing & Commissioning of PVC Cable 185 mm² alongwith 12 Nos Al. Thimble of 185 mm²
Installation, Testing & Commissioning of LT Distribution Box for 100kVA DTRwith MCCB for incomer & SFU's for OutgoingCircuits
Providing of Earthing of Sub-Station - Excavation of Earth Pit650mm and depth 3000mm , Installation of Earth Pipe of 40 mm of nominal bore & 4 mm wall thickness with length 2.5 Mtr long as per IS 1239, GI Strip for neutral Earthing of Size 25mm x3mm thickness for connection of Transformer Body, GO Set, LA Set as per IS 2629/85 GI nuts and bolts refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover
Providing of Stone pad (300mmx300mmx75mm)
Installation, Testing & Commissioningof 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm
Installation, Testing & Commissioningof 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm
Fixing of Anti Climbing device with Clamps
Fixing of PG Clamps
Fixing of Danger Plates with Clamps
Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm),nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mmdiameter solid GS stay rod & 7/3.15 mm dia GIstranded wire complete
SCOPE OF WORK DISMANTLING OF EXISTING HT LINE ( 2.00 KM)
Dismantelling of 9 Mtr Long PCC Pole (WL-300 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Dismantelling of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Dismantelling of ACSR Weasel Conductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire
Dismantelling of 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm
Dismantelling of 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm
Dismantelling of Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm )complete job
Dismantelling of Danger Plates with Clamps
Dismantelling of Anti Climbing device with Clamps
Dismantelling of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip
Dismantelling of Stone Pad 300 mmx300mmx75mm
Dismantelling of Aluminum Jointing sleeves
Dismantelling of P G Clamps
Carriage of Dismantled material i.e. PCC Poles, Conductor, MS iron, Hardware and Fittings etc to Divisional Store
SCOPE OF WORK FOR LAYING OF HT LINE ON 9 MTR PCC POLES USING ACSR WEASEL CONDUCTOR ( 2.20 Km)
Supply, Transportation, Erection of 9 Mtr Long PCC Pole (WL-300 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Supply, Transportation, Fabrication & Fixing of GI Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Supply, Laying & Stringing of ACSR Weasel Conductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire
Supply Installation, Testing & Commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm
Supply Installation, Testing & Commissioning of 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positiveand 80kV Negative, creepage distance 320mm
Providing & Fixing of Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip
Providing of Stone Pad 300 mmx300mmx75mm
Providing and fixing of Aluminum Jointing sleeves
Providing and fixing of P G Clamps
SCOPE OF WORK FOR LAYING OF LT LINE ON 8 MTR PCC POLES USING ACSR WEASEL CONDUCTOR ( 3 Phase 4 wire)( 0.900 mtr.)
Supply, Transportation, Erection of 8 Mtr Long PCC Pole (WL-200 KG) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
Providing & Fixing of GI U-Clamp with Shackle Insulator (Polymer/Porcelain) along with Nut & Bolt of sorts
Supply, Laying & Stringing of ACSR Weasel Conductor through insulators including proper binding & twisting with soft Aluminium Wire(three Phase four wire)
Providing & Fixing of Galvanised Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing & Fixing of LT Line Spacers
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip
Providing of Stone Pad 300 mmx300mmx75mm
Providing and fixing of Aluminium sleeves
M/S VINAYAK ENGINEERS
M/S DAYAL BUILD TECH
VEENA CONSTRUCTION CO.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .