Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹56.2 LAccepted-AOC | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹74.0 L+₹14.5 L (24.3%)Rejected-Finance 1 14 SUJAL MANSION B BLOCK BHANGWADI KALBADEVI ROAD MUMBAI 400 002 | MUMBAI | MAHARASHTRA | 400002 | L2 | Rejected-Finance Other than being lowest | |
| 3 | L3₹74.2 L+₹14.7 L (24.7%)Rejected-Finance | L3 | Rejected-Finance Other than being lowest | |
| 4 | L4₹79.4 L+₹19.9 L (33.5%)Rejected-Finance SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | L4 | Rejected-Finance Other than being lowest | |
| 5 | L5₹87.0 L+₹27.4 L (46.1%)Rejected-Finance | L5 | Rejected-Finance Other than being lowest |
Tender Value
₹90 L
EMD Value
₹1.6 L
Closing Date
26 Mar 2025, 6:00 pmClosed
CWE (NW) Mumbai
Commander Works Engineer NW Dr Homi Bhabha Road Navy Nagar Colaba Mumbai 05
COMPREHENSIVE MAINTENANCE OF AUTOMATIC FIRE DETECTOR, FIRE ALARM AND FIRE FIGHTING SYSTEM COMPLETE INCLUDING CONTROL WIRING, PIPELINES, VALVES, HYDRANTS, PUMPS AND MOTORS AT VARIOUS OTM AND TECHINICAL ACCOMMODATIONS UNDER GE NW KUNJALI
2025_MES_698902_1
8430/CWE(NW)MUMBAI/E8
Open Tender
Civil Works
Item Rate
180 days
GE (NW) Kunjali
Class C Category cvi
7 documents required · 7 mandatory
₹1,000
GE (NW) Kunjali
₹1.6 L
Yes
19 Jun 2025
21 Feb 2025
28 Mar 2025
21 Feb 2025
26 Mar 2025
14 Mar 2025
21 Feb 2025 - 10 Mar 2025
Amount
Comprehensive maintenance of fire detection/auto fire alarm systems/ fire supression system/ fire hydrant system, connected pump motor of any type, valves, starter panel etc installed at various locations in INS ANGRE including attending of day to day comaplaints and cleaning, inspecting, repair and testing of the equipments to maintain fire detection / supresssion system/fire hydrant system functional. The detail scope of work consists of the following:- Location: HQ MNA, NPO, COMCEN, HQ CE (i) Regular Cleaning inspecting, checking and repairing if required all the equipments of fire detection / supresssion system and maintaining the system functional. (ii) Operational test of all the equipment of fire detection and fire fighting sytem in presence of rep of users and Engr-in-charge. (iii) The contractor will submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through skilled technician having 3-5 years experience and one helper on daily basis in general shift of 0900 hrs to 1700 hrs except sunday . Daily attendence register and routine maintanence record as per the format approved by Engineer-in-charge shall be prepared/ maintained and kept on record duly signed. Complaints shall be attended within 4 hours after receipt as recorded in complaint register. In case of failure within specified time, recovery shall be effected @ Rs.1000/- per hour beyond 4 hrs. (v) Emergency visit will be carried out when called in addition to the routine monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Material required for replacement shall be measured and paid separately under respective items of this schedule as SUPPLY ONLY. However, minor spares such as screw, nut, bolts, wire, washer, coupling of motors, tool and plants etc required are included in the quoted rate.
-Ditto- all as per item No 1.00 above but for various building at Naval Dockyard area as under: Location: Vajrabahu, FMU, CG Complex, NRML, DGNP
Material & labour for locating faults and testing of all loops for smoke detectors, heat detectors, beam detectors, hooters, response indicator, manual call points etc, checking and testing of electric wiring connection for each devices, cleaning of all connected devices with AFDS system manually/ mechanically , re-numbering for each devices for programming in the AFDS panels with configuration of connected devices as per exact location of detectors indicating the same location in control panel and updating of software for AFDS panel of any make as per site requirement including testing in presence of user rep and Engr in Charge complete all as specified and directed. Note : (i) Test report shall be submitted after completion separately for each panel and cost of the same is deemed to be included in quoted rate. (ii) All devices connected with each AFDS Panel of any loop capacity as per existing for Loop testing, electric wiring testing, cleaning of all devices such as smoke cum thermal detectors, response indicators, manual call points, beam detector, flame detector etc, re-numbering of devices and its configuration and programming with AFDS panel including software update is deemed to be considered as one job.
Supply only photo electric smoke cum thermal detectors with mounting basecomplete all as specified.
Supply only addressable Manual call point resettable type complete all as specified.
Supply only conventional Manual call point resettable type complete all as specified.
Supply only intelligent addressable monitor module complete all as specified.
Supply only fault isolator module with automatic resetting arrangement complete all as specified.
Supply only response indicator (RI) complete all as specified.
Supply only control module (HZM) suitable for flame detectors complete all as specified.
Supply only hooter with control module complete all as specified.
Supply only addressable/conventional type heat detector with base complete all as specified.
Supply only addressable/ conventional Beam master detector with transmitter and receiver complete all as specified.
Supply only Flame detector complete all as specified.
Supply and fixing in repairs addressable Fire alarm control panel complying with BSEN54/UL single loop panel of capacity from 126 detectors & 126 modules complete all as specified.
Supply and fixing in repairs addressable Fire alarm control panel complying with BSEN54/UL double loop panel of capacity from 126 detectors & 126 modules complete all as specified.
Supply and fixing in repairs addressable Fire alarm control panel complying with BSEN54/UL four loop panel of capacity from 126 detectors & 126 modules complete all as specified.
Supply and fixing in repairs addressable Fire alarm Repeater panel complete all as specified.
Material & labour for taking out unserviceable repeater fault control panel of existing fire detector and repairing the repeater panel including replacement of unserviceable parts complete and refixing the same in its original position including testing, commissioning complete all as specified and directed.
Supply and fixing in repairs PCB loop cord suitable for self addressable fire finder system complete all as specified. Make : Honey well/ Bosch/Notofire
Supply, laying and connecting PVC insulated PVC sheathed copper conductor cable of size 1.5 Sqmm 2 core FRLS grade 1100 volts drawn through existing MS/ PVC conduit fixed on wall/celling of the Bldg complete all as specified.
Supply and fixing in repairs stove enamelled steel conduit of size 20 mm bore including accessories like saddles, couplers, bends tees etc complete all as specified and directed.
Supply and fixing in repairs UPS 1.0 KVA suitable for working on 230 Volts, 50 Hz AC supply complete all as specified.
Supply and fixing in repairs 12 V 7 AH Battery complete all as specified.
Supply and fixing in repairs mother board for two Nos loops cards suitable for self addressable fire finder of existing make.
Material & labour for refilling Sinorix 1230 (Make- Siemens) or FK-5-1-12 (Make- Rotarex) gas in cylinder including disconnecting and taking out existing cylinders carefully of any capacity and size from work site to the factory for refilling and taking back the same including replacing unserviceable pressure gauges/ connector pipes, nozzles and other connected items including testing in presence of Engr-in-Charge complete all as specifed and directed. Note : The cost of transportation of gas cylinder to the factory/workshop and back is included in the quoted rate.
Material & labour for HPT (hydro pressure test) of cylinder of existing capacity in factory workshop and punching year after sucessfully test including applying two coats of synthetic enamel paint on cylinders complete all as specified and directed.
Supply only cylinder of 68 ltr capacity of punching year 2024 suitable for re-filling of FM 200 or Novec 1230 gas as per OEM recommendation complete all as specified and directed.
Material & labour for servicing of solenoid valves assembly including connected pipe suitable for FM 200 gas cylinder at OEM workshop complete all as specified and directed.
Supply and fixing in repairs solenoid valves assembly including connected pipe and all accessories suitable for re-filling of FM 200 or NOVEC 1230 gas in cylinders as per OEM recommendation complete all as specified and directed.
Material & labour for weightloss device for cylinder (realtime) complete as per OEM recommendaiton all as specified and directed
Supply and fixing in repairs nozzle / sensor of fire supression system at various buildings complete all as specified.
Supply and fixing in repairs 20mm bore MS pipe medium grade for fire suppression system at various buildings complete all as specified.
Supply only conventional Gas release Fire alarm control panel complying with BSEN54/UL single loop panel of capacity from 126 detectors & 126 modules complete all as specified.
Supply only conventional Fire alarm control panel complying with BSEN54/UL single loop panel of capacity from 126 detectors & 126 modules complete all as specified.
Disconnecting horizontal / vertical split casing pump of 60/75 HP motor any make/model, dismantling and taking out pump shaft assembly complete and providing new pump bearing DE or NDE, pump gasket, gland packing, nut bolts, flanges of required size including servicing the pumpset connecting to coupling, testing & commissioning complete all as specified and directed Note :- Rates deemed to be included for decoupling and coupling pump with motor.
-Ditto- all as per item No 36.00 above but for 10/12.5 HP motor.
Supply & fixing in repair pressure gauge 150/100 mm dia range 0-10 kg/Sqcm complete all as specified. Note : Rate quoted shall deemed to be included for providing adopter/Ferrule/check nut etc required for fixing of pressure guage.
Supply & fixing in repairs MS coupling suitable to 100 HP pumps at various installations.
Supply & fixing in repairs MS coupling suitable to 45 to 60 HP pumps at various installations.
Supply & fixing in repairs MS coupling suitable to 5 to 25 HP pumps at various installations.
Disconnecting electric connections from 100 HP Capacity electric motor and dismantling from the pumping sets , removing and taking down carefully and transporting to authorised workshop for rewinding strip opening and dismantling complete rotor and stator assemby , cutting and taking out old burnt copper winding from the stator assembly and cleaning the slots of stator with carbon tetra chloride solution and rewinding complete stator assembly with and including super enamelled copper winding wire of existing gauge , applying minimum two coats of insulation varnish and keeping the stator assembly in heating chamber to improve for insulation value, assemblyling the motor , transporting to site of work, coupled with the pumping sets aligments properly , connecting the LT cables and testing and commissioning complete all as specified
- Ditto- all as per item No 42.00 above but 75 HP Capacity
- Ditto- all as per item No 42.00 above but 45 HP Capacity
- Ditto- all as per item No 42.00 above but 25 HP Capacity
- Ditto- all as per item No 42.00 above but 7.5 HP Capacity
Supply & fixing in repairs main contactor suitable for 100 HP motor, MNX 140, 3 pole, 415V, 50 Hz complete all as specified.
Supply & fixing in repairs main contactor suitable for 75/60 HP motor, MNX 95 , 3 pole, 415V, 50 Hz complete all as specified.
Supply & fixing in repairs main contactor suitable for 12.5/10/7.5 HP motor, MNX 18, 3 pole, 415V, 50 Hz complete all as specified.
Supply & fixing in repairs MCCB 3 Phase (TP) 400 A, 35 KA, 415 Volts, Adjustable type fixed in existing panel board of existing make.
Supply & fixing in repairs MCCB 3 Phase (TP) 200A 50Hz, 35 KA, 415 Volts Adjustable type fixed in existing panel board of existing make.
Supply & fixing in repairs MCCB 3 Phase (TP) 100A 50Hz, 25 KA, 415 Volts Adjustable type fixed in existing panel board of existing make.
Supply & fixing in repairs MCCB 3 Phase (TP) 63A 50Hz, 16 KA, 415 Volts Adjustable type fixed in existing panel board of existing make.
Supply & fixing in repairs pump & line shaft suitable for 100 HP capacity pump sets .
Supply & fixing in repairs pump & line shaft suitable for 75 HP capacity pump sets .
Supply & fixing in repairs pump & line shaft suitable for 25 HP capacity pump sets .
Supply & fixing in repairs impeller including impeller ring, casing ring and balancing of rotating assembly with impeller as per existing suitable for 100 HP capacity pump sets .
- Ditto- all as per item No 57.00 above but 75 HP capacity.
- Ditto- all as per item No 57.00 above but 25 HP capacity.
Supply & fixing in repairs Stainless steel air release valve including providing new gaskets , SS nuts, SS bolts, washers etc.suitable for 75 HP pump set complete all as specified.
Supply anf fixing in repair direct on line (DOL) starter 3 phase 415 Volts suitable for 7.5 HP to 05 HP capacity motpr
Material and labour for disconnecting 100 HP capacity pump set, transporting to civil workshop for repairing, metal filling, turning and grinding on lathe machine shafts and re-installing after repair complete all as specified and directed.
- Ditto- all as per item No 62.00 above but 75 HP capacity.
- Ditto- all as per item No 62.00 above but 25 HP capacity.
Supply & fixing in repairs gland packing suitable for pump set and sluice valves of any capacity complete including cleaning and testing complete all as specified and directed.
Supply and fixing in repairs Star Delta Starter suitable for 60/75 HP Motor, 415V, 50 Hz of existing make
Supply and fixing in repairs Star Delta Starter suitable for 12.5/10/7.5 HP Motor, 415V, 50 Hz of existing make
Taking down and dismantling centrifugal pump set of 100 HP capacity installed at various water supply installations for servicing/overhauling , greasing, replacing bearing and replacement of worn out parts which shall be measured and paid separately under the relevant items of Sch `A' :- Note : Cost of minor spare parts such as gland packing, rubber packing, nut bolts, washers etc is included in quoted rate by the contractor
- Ditto- all as per item No 68.00 above but 75/60 HP pump
- Ditto- all as per item No 68.00 above but 25/20 HP pump
- Ditto- all as per item No 68.00 above but 15 to 7.5 HP pump
Supply & fixing in repair 150 mm bore sluice valves flanged end, cast iron body, flanged and drilled and non rising type brass spindle with nut, long body, class P N 16, conforming to IS 14846 of 2000 including all flange joint with rubber or fiber board, bolts, nuts and washers complete including pumping out accumulated water complete all as specified and directed .
- Ditto- all as per item No 72.00 above but 100 mm bore
Supply & fixing in repair 150mm bore Non Return sluice Valve flanged end, cast iron body, flanged and drilled and non rising type brass spindle with nut, long body, class P N 16, conforming to IS 14846 of 2000 including all flange joint with rubber or fiber board, bolts, nuts and washers complete including pumping out accumulated water complete all as specified and directed .
- Ditto- all as per item No 74.00 above but 100 mm bore
M & L for construction of brick masonry valve chamber of size 1200mm x 1200mm x 1200mm (internal dimension) (above GL 0.30 mtr) comprising of 15cm thick PCC 1:4:8 type D-2 foundation over 15cm thick hardcore of broken stone, 23cm thick brick walls built in cement and sand mortar 1:4, 15mm thick internal and external plaster, top of floor 15mm thick in cement and sand mortar 1:3 finished even and smooth without using extra cement, 5 mm thick MS plate cover over complete chamber fixed on 50mm x 50mm x 6mm MS angle frame welded to MS hold fasts embeded in 50mm thick 1:2:4 type B-1 coping, having rectangular, hinged, opening of size 150 x 100mm with locking arrangements and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer including necessary excavation and earth work in any type of soil and demolition of existing valve chamber and removing debries outside MD land complete all as specified. Note: The place of disposal shall be find out by the contractor.
Supply, lay/fix, connect and testing 150 mm bore MS ERW pipe, in any length, including supply and fixing all fittings, ISI marked conforming to IS-1239 and fixed to wall/ceiling or laid in trenches/floors including taking down old pipe complete all as specified and directed by the Engineer-in-Charge.
- Ditto- all as per item No 77.00 above but 100 mm bore
- Ditto- all as per item No 77.00 above but 80 mm bore
Supply and fix 80mm bore MS Pipe heavy grade including all fittings like; union, tee, bend, elbow, reducer, socket and fixed on wall and ceilings or laid in floors/trenches including taking down old pipe complete all as specified and directed by the Engineer-in-Charge. Note : Cost of fixing supporting GI clamps of required size for support, nut, bolts etc are deemed to be included in the quoted rate.
- Ditto- all as per item No 80.00 above but 100 mm bore
Supply & fixing 40mm bore gunmetal gate valve, conforming to IS-778, ISI marked, with iron wheel head screwed at both ends for iron pipes or ferrule and fixing including necessary fittings like unions, check nuts, etc and any addition / alteration required for fixing complete all as specified and as directed by the Engineer-in-charge.
- Ditto- all as per item No 82.00 above but 50 mm bore
- Ditto- all as per item No 82.00 above but 80 mm bore
Taking down corroded MS sections and Supply & fixing angle iron frame work of any size including necessary fabrication work with two coats of synthetic enamel paint over a coat of redoxide complete all as specified
Material and labour for preperation of steel/iron surface of old painted surface of any size Pipeline upto 200mm dia otherwise described, painting one coat with red oxide zinc chrome paint and 2 coat with anticorrosive paint for protection against sea water (existing pattern) including writing name and arrow marking with synthetic emanel paint complete all as specified and directed by Engineer-in-Charge.
Supply & fixing in repair rubber hose pipe 30 mtr long,20mm dia plain 2 ply rayon braided high pressure ISI Marked .
Supply & fixing in repair canvas fire hose 63mm bore 15 m long conforming to IS Having male/female brass coupling on both ends complete all as specified.
Supply & fixing in repair Stainless steel Nozzle 25 mm bore suitable for 63mm dia canvas pipe complete all as specified .
Supply & fixing in repair hose Reel drum suitable for 30 mtrs X 20 mm dia rubber hose pipe complete all as specified .
Supply & fixing in repairs Branch pipe gun metal 63mm instantaneous inlet, made threaded outlet, 15mm bore nozzle complete all as specified .
Supply & fixing in repair twin outlet Brass hydrant valve 100mm having 65mm outlet with lock pin wheel complete all as specified and directed by Engineer-in-charge.
Supply & fixing in repair single outlet hydrant valve 100mm having 65mm outlet with lock pin wheel complete all as specified and directed by Engineer-in-charge.
Supply & fixing in repair gun metal Two way fire brigade inlet conection with adaptor of size 80 mm dia x 63 mm dia complete all as specified .
Excavating in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for foundation/ laying of pipe etc and getting out in hard/ dense soil complete all as specified.
Returning filling in , including spreading, leveling, watering and well ramming in layers not exc 25 cm.
Removing surplus excavated soil to a distance not exceeding 50 m and deposited where directed complete all as specified.
Supply and fixing in repairs factory made Hose box wall mounted of size 800mm x 600mm x 250mm made out of 16 gauge MS sheet, powder coated with post office red colour for housing 02 Nos in lengths of 15 mt long each canvas hoses and branch pipes with glass and locking arrangement, painted fire red out side and brilliant white inside complete all as specified and as directed by Engineer-in-Charge
Supply and fixing in repairs damaged glass panes 6 mm thick suitable for existing fire cabinet indoor type complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in repairs mouth washers for 63 mm size fire hydrent complete all as specified and as directed by Engineer-in-Charge
Supply , fixing, testing JEF ECO SAFE Maintenance Free Grounding Solution set comprising of High tensile low carbon steel rod of 3 Mts length & 25 mm dia with 250 micron ( averaSchneider ) molecularly bonded copper on the outer surface to confirm with requirements of UL467 along with Back-fill compound strictly be a Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr as per Clause 14.5D of IEEE : 80 standard. Back-fill compound should be electronically conductive ( Like in metals ) and should not depend on moisture for conduction. JEF Powerfill Loresco compound shall be supplied in 50 Pound Bag. ( 1 Bag of 50 Pounds required per earthing set). Back-fill comound should be environment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground. A suitable earth terminaton clamp should also be supplied along with the set alongwith earth pit weatherproof including demolition of existing earthing and removing debries out side MD land complete all as specified . Note : Back-fill compund shall not be mixed with any soil while pouring in the bore hole.
Material & labour for 25 x 3 mm galvanised iron strip earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing complete all as specified.
Supply & fixing in repairs 80 mm bore heavy duty ball type MS foot valves flanged end swing type operation with rubber seat as per IS 4038 including nuts, bolts and washers etc complete all as specified
- Ditto- all as per item No 103.00 above but 100 mm bore
- Ditto- all as per item No 103.00 above but 150 mm bore
Supply, Laying, commissioning and testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 4 core 16 Sqmm laid in trenches, passing through pipes, fixed along wall/floor with suitable size GI clamps complete including connecting properly by using copper thimble, lugs, glands etc including taking out damaged unserviceable cable complete all as specified.
-Ditto- all as per item No 106.00 above but cable size 3.5 core 25 Sqmm
-Ditto- all as per item No 106.00 above but cable size 3.5 core 35 Sqmm
-Ditto- all as per item No 106.00 above but cable size 3.5 core 50 Sqmm
-Ditto- all as per item No 106.00 above but cable size 3.5 core 95 Sqmm
Material & labour for periodic and preventive service of diesel engine driven pump installed at various locations complete including the following : (a) Replacement of oil filters (b) Replacement of air filter (c) Replacement of fuel filter (d) Caliberation, servicing, cleaning of fuel injector pump (e) Replacement of belt drive (f) Replacement of engine oil, coolent (g) Repair/service of radiator assembly (h) Replacement of 4 Nos of vibration pads for each diesel engine pump Note : (i) Any part/accessories required to make engine pump serviceable and functional all as specified and directed by Engr in Charge is deemed to be included in the quoted rate. (ii) Cost of dismantling and taking out carefully diesel engine driven pump of any make and capacity for fixing of anti vibration pads approved by Egineer in Charge including minor spare parts, T&P etc and reconnecting as per existing is deemed to be included in the quoted rate.
Chakshu Enterprise (BID ID -3266446)
Hardik Engineers (BID ID -3266136)
Shree Ayyappa Engineering (BID ID -3266523)
Shetty Construction Co (BID ID -3271282)
AGRAWAL ASSOCIATES (BID ID -3266552)
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .