Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.1 LAdmitted-Finance 508 C WING SRA BUILDING NO 6C OPP DURGA MANDIR MALAD EAST MUMBAI 400 097 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400097 | ₹10.1 L | L1 | Admitted-Finance |
| 2 | L2₹13.3 LAdmitted-Finance 10TH FLOOR UNIT 2 TECHNIPLEX 2 VEER SAVARKAR FLYOVER S V ROAD GOREGOAN WEST MUMBAI 400 062 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400062 | ₹13.3 L | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | VAV Airconditioning L2 | V S Engineering L1 |
|---|---|---|---|---|---|
| 1.00SITC of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units (suitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressors), minimum two compressors (with individual seperate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing units), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condensor fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius outdoor temperature. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50HzAC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 7.4, Capacity > 40 and <70 ISEER 7.5, Capacity > 70 ISEER 7.6 for Super ECSBC Building) Make - Toshiba, Mitsubishi, Trane, Hisense. | |||||
| 1.01 | 20 HP (10HP + 10 HP) | 2 | Nos | 2,57,575 ₹5.2 L | 2,50,000 ₹5 L |
| 2.00SITC of following minimum capacity and external static pressure VRF/VRV celling mounted cassette unit type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration Isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC supply 230 V ≤ 10%, 50 Hz complete as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) Make - Toshiba, Mitsubishi, Trane, Hisense. | |||||
| 2.01 | 3 TR Cassette type | 5 | Nos | 61,175 ₹3.1 L | 57,000 ₹2.9 L |
| 3.00SITC including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRVVRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required. Make - Mandev, Maxflow, Hari Om Metals. | |||||
| 3.01 | Copper Piping 9.5 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation | 38 | Rmt | 712 ₹27,056 | 425 ₹16,150 |
| 3.02 | Copper Piping 12.7 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation | 13 | Rmt | 980 ₹12,740 | 480 ₹6,240 |
| 3.03 | Copper Piping 15.9 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation | 38 | Rmt | 1,445 ₹54,910 | 630 ₹23,940 |
| 3.04 | Copper Piping 19.1 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation | 13 | Rmt | 1,734 ₹22,542 | 735 ₹9,555 |
| 3.05 | Copper Piping 25.4 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation | 13 | Rmt | 2,004 ₹26,052 | 880 ₹11,440 |
Tender Value
₹13.0 L
EMD Value
₹25,940
Closing Date
7 Jan 2026, 6:55 pmClosed
OIC, Engineering, TMC on behalf of Director, TMC
Engineering Department, 6th floor, Service Block, TMH, Parel
SITC of Airconditioning work for Creche, 1st floor, Doctors Hostel, Parel, Mumbai
2025_TMC_891391_1
TMC/ENG/Mech/SITC AC/Creche/49
Open Tender
Machineries/ Mechanical Engg Items
60 days
TMH, Parel
As per tender document
6 documents required · 6 mandatory
₹0
₹25,940
TMH, Parel
24 Feb 2026
26 Dec 2025
9 Jan 2026
26 Dec 2025
7 Jan 2026
2 Jan 2026
26 Dec 2025 - 30 Dec 2025
31 Dec 2025
SITC of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units (suitable for cooling/heating having 100% hermetically sealed inverter type twin Rotary/Scroll Compressors), minimum two compressors (with individual seperate PCB) for above 14HP modules, microprocessor based Controller, top discharge type condensing units), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condensor fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius outdoor temperature. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50HzAC power supply and BMS compatible. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. The Indian Seasonal Energy Efficiency Ratio (ISEER) of the unit shall be as per Energy Conservation and Sustainable Building Code (ECSBC) 2024 as below and complete as per CPWD specification, connections, inter connections etc. as required. (For capacity <40 kWr ISEER 7.4, Capacity > 40 and <70 ISEER 7.5, Capacity > 70 ISEER 7.6 for Super ECSBC Building) Make - Toshiba, Mitsubishi, Trane, Hisense.
20 HP (10HP + 10 HP)
SITC of following minimum capacity and external static pressure VRF/VRV celling mounted cassette unit type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration Isolators, drain pan, drain pump, other necessary supports etc., suitable for operation on single phase AC supply 230 V ≤ 10%, 50 Hz complete as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Singnals. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) Make - Toshiba, Mitsubishi, Trane, Hisense.
3 TR Cassette type
SITC including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRVVRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required. Make - Mandev, Maxflow, Hari Om Metals.
Copper Piping 9.5 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation
Copper Piping 12.7 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation
Copper Piping 15.9 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation
Copper Piping 19.1 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation
Copper Piping 25.4 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation
Copper Piping 28.6 mm dia (OD) with tube thickness 1.2 mm with 19 mm Thick AL backed nitrile insulation
SITC of Y/T/Multi Joints. Joints shall be of same Original Equipment Manufacturer (OEM) make as of ODUs and IDUs
SITC of PVC drain pipe having pressure holding of 8kg/cm2. drain piping complete with all accessories with 9mm Nitrile Rubber Insulation with supports.
SITC of GI Perforated cable tray with cover (medium duty) with all necessary suspendors from ceiling and fittings
100 mm X 75 mm (1.6mm thick)
300 mm X 75 mm (1.6mm thick)
SITC of suitable 32 Amps RCBO (MCB + ELCB) with waterproof enclosure for 10 HP outdoor
SITC of power cabling for outdoor - 4C X 6 sq.mm
SITC of power cabling for Indoor - 3C X 2.5 sq.mm
SITC of control cabling between indoor and outdoor units
SITC of 10g copper earthing for outdoor units
SITC of Cowl piece for outdoor units (20 gauge 120 gsm)
Filling-up of Financial Bid: Unless otherwise called for, any tender containing percentage below / above the estimated cost put to tender is liable to be rejected. All rates shall be quoted on the tender form by the tenderers in figures and words shall be accurately filled in, so that there is no discrepancy in the rates written in figures and in words. The amount for each item should be worked out and requisite totals given. However,
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.84 MB
techspecifications.pdf
Tender Documents • 0.15 MB
techdocumentchecklist.xls
Tender Documents • 0.03 MB
BOQ_936928.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid