| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.5 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹41.1 L+₹88,915 (2.21%)Rejected-Finance KORAMANGALATH HOUSE TOMY LANE SOUTH PANAMBILLY NAGAR KADAVANTHRA P O KOCHI 682 020 | KOCHI | ERNAKULAM | KERALA | 682020 | L2 | Rejected-Finance L1 being accepted | |
| 3 | L3₹43.8 L+₹3.5 L (8.81%)Rejected-Finance 9 8 B THENGUMTHARAVIL MLA ROAD PANANGAD PO KOCHI 682506 | KOCHI | ERNAKULAM | KERALA | 682506 | L3 | Rejected-Finance L1 being accepted | |
| 4 | Rejected-Technical | - | Rejected-Technical The firm has not been enlisted for eligible category i.e. c(vi) | |
| 5 | Rejected-Technical | - | Rejected-Technical The firm has not been enlisted for eligible category i.e. c(vi) |
Tender Value
Refer Docs
EMD Value
₹79,500
Closing Date
22 Sept 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE Tirunelveli
GE TIRUNELVELI INS KATTABOMMAN NAVAL BASE POST VIJAYANARAYANAM TIRUNELVELI
GE/TVL/8177
2021_MES_471211_1
GE/TVL/8177
Open Tender
Miscellaneous Works
Item Rate
180 days
Vijayanarayanam
As per NIT/ Tender documents
8 documents required · 8 mandatory
₹500
GE Tirunelveli
₹79,500
Yes
14 Oct 2021
27 Aug 2021
24 Sept 2021
27 Aug 2021
22 Sept 2021
10 Sept 2021
27 Aug 2021 - 6 Sept 2021
60 days
Amount
SCHEDULE 'A' PART-I [ FIRE FIGHTING SYSTEM]
Supply,installation,testing and commissioning of Non Return valve PN- 1.6, CI 200 mm dia both ends flanged heavy duty including packing materials, nut bolts washer etc including taking out of old U/S non return valve complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or equivalent in L&T/Leader/Upadhya/Zoloto
Supply,installation,testing and commissioning of Non Return valve PN- 1.6, CI 150 mm dia both ends flanged heavy duty including packing materials, nut bolts washer etc including taking out of old U/S non return valve complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or equivalent in L&T/Leader/Upadhya/Zoloto
Supply,installation,testing and commissioning of Non Return valve PN- 1.6, CI 50 mm dia both ends flanged heavy duty including packing materials, nut bolts washer etc including taking out of old U/S non return valve complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or equivalent in L&T/Leader/Upadhya/Zoloto
Supply,installation,testing and commissioning of Sluice valve size 250 mm dia PN- 1.6 both ends flanged heavy duty including packing materials, nut bolts washer etc and testing including taking out of old U/S valve complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or equivalent in L&T/Leader/Upadhya/Zoloto
Supply,installation,testing and commissioning of Sluice valve size 200 mm dia PN- 1.6 both ends flanged heavy duty including packing materials, nut bolts washer etc and testing including taking out of old U/S valve complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or equivalent in L&T/Leader/Upadhya/Zoloto
Supply,installation,testing and commissioning of Sluice valve size 150 mm dia PN- 1.6 both ends flanged heavy duty including all joints with rubber or fiber board , packing materials, nut bolts washer etc and testing including taking out of old U/S valve complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or equivalent in L&T/Leader/Upadhya/Zoloto
Supply,installation,testing and commissioning of Sluice valve size 100 mm dia PN- 1.6 both ends flanged heavy duty including all joints with rubber or fiber board ,packing materials, nut bolts washer etc and testing including taking out of old U/S valve complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or equivalent in L&T/Leader/Upadhya/Zoloto
Supply,installation,testing and commissioning of Sluice valve size 65 mm dia PN- 1.6 both ends flanged heavy duty including all joints with rubber or fiber board , packing materials, nut bolts washer etc and testing including taking out of old U/S valve complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or equivalent in L&T/Leader/Upadhya/Zoloto
Supply,installation,testing and commissioning of Sluice valve size 50 mm dia PN- 1.6 both ends flanged heavy duty including all joints with rubber or fiber board , packing materials, nut bolts washer etc and testing including taking out of old U/S valve complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or equivalent in L&T/Leader/Upadhya/Zoloto
M & L for replacment of unserviceable flanged Bellow PN 16, size 200 mm to 50 mm, EPDM rubber type, complete all as specified and directed by Engr-in-Charge.
Supply,installation,testing and commissioning of pressure gauge 4'' dial 0-14kg/cm² rating complete all as specified and directed by Engr-in-Charge. Make:- Siemens/Honeywell/Danfoss/Schneider/Rapid Control/L&T
Supply,installation,testing and commissioning of pressure Switch universal type with accessories complete all as specified and directed by Engr-in-Charge. Make: Siemens/Honeywell/Danfoss/Schneider/Rapid Control/L&T
Supply, installation, testing & commissioning of fire hydrant landing Valve Type A (single head outlet) of 63mm dia of size complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or equivalent in L&T/Leader/Upadhya/Zoloto
S & F Double door Hose box made of 18 gauge MS Sheet 750mmx600mmx250mm with double leaf glazed shutter (4mm thick glasses) and door frame made of 16 gauge MS Sheet with locking arrangement including painted with fire red outside and brilliant white inside yard of box complete all as specified and directed by Engr-in-Charge.
S & F CP Hose pipes of size 15 Mtr length, 63mm dia the hose pipe shall be externally elastomeric coated all synthetic jacketed rubberized fabric reinforced ruuber lined (RRL) bearing IS:636 type 'A' mark, fitted with gunmetal instantaneous pattern heavy duty male & female delivery duty hose coupling bearing IS:903 mark complete all as specified and directed by Engr-in-Charge. Make: Minimax/Safex/Cease Fire/Cosmos/Exflame
Supply, installation, testing & commissioning of Butterfly Valve of size 150mm dia complete all as specified and directed by Engr-in-Charge. Make: Kirloskar or equivalent in L&T/Leader/Upadhya/Zoloto
S & F addressable type smoke detector comply to/ certified to EN-45 Photoelectric/optical with base with self built intelligence confirming to IS: 11360 complete all as specified and directed by Engr-in-Charge. Make: Cease Fire or equivalent in Honeywell/Morley/Guru Tronic
S & F addressable type multisensor detector with heat and smoke combination comply to/ certified to EN-45 with base with self built intelligence confirming IS: 11360 complete all as specified and directed by Engr-in-Charge. Make: Cease Fire or equivalent in Honeywell/Morley/Guru Tronic
S & F addressable type heat detector comply to/ certified to EN-45 with base with rate of rise cum fixed temperature as per IS: 2175 complete all as specified and directed by Engr-in-Charge. Make: Cease Fire or equivalent in Honeywell/Morley/Guru Tronic
M & L for checking of 4 Loop addressable fire alarm control panel for sevicing, calibrating, checking for operation, repairing for spare parts if required complete up to satisfaction level complete all as specified and directed by Engr-in-Charge. Note: Cost of spare parts deemed to be included in the quoted unit rate.
Taking down old unserviceable Battery 12 Volts, 150 AH and replacement with new battery of 12 Volts, 150 AH for diesel Engine driven motor pump set complete all as specified and directed by Engr-in-Charge. Make: Exide or equivalent
Material and labour for maintenance and servicing of Diesel Engine driven pump set of capacity 44.1/60 KW/HP, 1800 RPM including checking for lubricants, filters, coolents, starters, complete by draining out the lubricant oil from the sump, open the top cover of the engine head complete, unscrewing of engine mounting such as exhaust manifold, Air cleaner, top cover of acquisetic enclosure, remove the cylinder head by unscrewing nuts, bolts washers etc. tappets valves etc. remove the dust, dirt from the main engine assembly. Check the serviceability of crank shaft assembly, Main bearing assembly, roller bearing assembly, cam shaft, fuel nozzles, piston head cleaning, O rings, piston rings, liner of bore, battery terminals, connecting cables, wiring etc. complete and replacement of U/S accessories. Sending the tapet valves to workshop for lathe work. Calibration of fuel injector pump assembly and changing the worn out/ unserviceable spares, re-assembling, testing on full load complete and checking of Pump impeller, bushing, shaft, gland packing, bearing if required replacement of spares, up to the satisfaction of Engineer-in-Charge for Diesel Engine and pump of capacity 60HP including painting of 2 coat synthatic enamel paint to Diesel Engine and pump complete all as specified and directed by engr-in-Charge. Note: (a) The rate quoted deemed to include all materials required for checking by authorised dealer such as replacement of (i) Lub oil filtr (ii) Fuel filter (iii) All standard spare parts required to replace the U/S spares to make the engine serviceable in all respects. (b) Cost of Lubricating oil, coolant oil etc. deemed to be included in the quoted rate and no extra payment will be paid to contractor in this regard. (c)Necessary arrangement of T&P items required for the job shall be deemed to be included in the quoted rate.
M&L for dismantling of electric driven horizontal induction motor of capacity 75.0 HP of any type and make, by engaging sufficient man power and suitable T&P to ensure safety of pump-motor as well as working persons including disconnecting of electric connections, dismantling of motor, taking out the burnt windings, cleaning and washing of slots and rewinding the same with copper winding wire of existing gauge and quantity (as per original manufacturer design) including replacement of all damaged parts i. e. bearings, bush, thrust plate, thrust bearing, connector plate, insulating materials such as insulating sheets insulating paper (Class "F"), sealing compounds, Shaft etc. and reassembling the motor after varnishing, heating/drying, greasing of moving parts etc.complete reinstallation of motor in original location, checking the alignment, making proper electric connection, testing for smooth operation including painting of 2 coat synthatic enamel paint to motor complete all as specified and directed by engr-in-Charge. Note : (i) The cost of winding wire and all replaced defective parts are deemed to be included in quoted rates and no extra cost shall be paid to the contractor in this effect. (ii) The cost of transportation (to and fro) and other necessary equipment shall be arranged/brought by contractor to complete the job at site or at repair shop and no extra cost shall be paid to the contractor in this effect. (iii)Necessary arrangement of T&P items required for the job shall be deemed to be included in the quoted rate.
M&L for dismantling of electric driven horizontal centrifugal pump of capacity 75.0 HP of any type and make, by engaging sufficient man power and suitable T&P to ensure safety of pump-motor as well as working persons including disconnecting from coupling, dismantling of pump, taking out old unserviceable all damaged parts impellers, glands, bearings, bushing, Shaft and making serviceable as pe satisfaction complete reinstallation of the motor and pump in original location, checking the alignment, making proper electric connection, testing for smooth operation, including painting of 2 coat synthatic enamel paint to pump complete all as specified and directed by engr-in-Charge. Note : (i) The cost of all replaced defective parts are deemed to be included in quoted rates and no extra cost shall be paid to the contractor in this effect. (ii) The cost of transportation (to and fro) and other necessary equipment shall be arranged/brought by contractor to complete the job at site or at repair shop and no extra cost shall be paid to the contractor in this effect. (iii)Necessary arrangement of T&P items required for the job shall be deemed to be included in the quoted rate.
M&L for dismantling of electric driven horizontal induction motor (Jockey Pump) of capacity 9.3/12.5 KW/HP of any type and make, by engaging sufficient man power and suitable T&P to ensure safety of pump-motor as well as working persons including disconnecting of electric connections, dismantling of motor, taking out the burnt windings, cleaning and washing of slots and rewinding the same with copper winding wire of existing gauge and quantity (as per original manufacturer design) including replacement of all damaged parts i. e. bearings, bush, thrust plate, thrust bearing, connector plate, insulating materials such as insulating sheets insulating paper (Class "F"), sealing compounds etc and reassembling the motor after varnishing, heating/drying, greasing of moving parts etc. and repair to pump impellers, glands, bearings complete reinstallation of the motor and pump in original location, checking the alignment, making proper electric connection, testing for smooth operation, including painting of 2 coat synthatic enamel paint to motor complete all as specified and directed by engr-in-Charge. Note : (i) The cost of winding wire and all replaced defective parts are deemed to be included in quoted rates and no extra cost shall be paid to the contractor in this effect. (ii) The cost of transportation (to and fro) and other necessary equipment shall be arranged/brought by contractor to complete the job at site or at repair shop and no extra cost shall be paid to the contractor in this effect.(iii)Necessary arrangement of T&P items required for the job shall be deemed to be included in the quoted rate.
M&L for dismantling of electric driven horizontal centrifugal pump of capacity 12.5 HP (jockey pump) of any type and make, by engaging sufficient man power and suitable T&P to ensure safety of pump-motor as well as working persons including disconnecting from coupling, dismantling of pump, taking out old unserviceable all damaged parts impellers, glands, bearings, bushing, Shaft and making serviceable as pe satisfaction complete reinstallation of the motor and pump in original location, checking the alignment, making proper electric connection, testing for smooth operation, including painting of 2 coat synthatic enamel paint to pump complete all as specified and directed by engr-in-Charge. Note : (i) The cost of all replaced defective parts are deemed to be included in quoted rates and no extra cost shall be paid to the contractor in this effect. (ii) The cost of transportation (to and fro) and other necessary equipment shall be arranged/brought by contractor to complete the job at site or at repair shop and no extra cost shall be paid to the contractor in this effect. (iii)Necessary arrangement of T&P items required for the job shall be deemed to be included in the quoted rate.
Material and labour for maintenance and servicing of resistor LOAD BANK of capacity 2000 KW, checking for preventive maintenanace of system, motor operation, control, blade condition repair/ replacement if required, checking of SFU unit and fuses, serviceability tightness of fuses and terminal, repair/ replacement if required, checking of resistors set, porcelain seperator/insulator seviceabilty and replacement if reqiured, Servicing of ACB and relays, Insulating pad check and repair/replace if required, complete all as specifird and directed by Engr-in-Charge.
M & L for servicing of PLC panel by checking of incoming and outgoing control cable, checking of control supply, checking of UPS backup supply, including repair/replacement of spere parts such as DP 40 A MCB, 230V TP 9A contactor, 24V 4C/O Relay hooters including all necessary accessories including other connected items to functional of panel board , lamp indicators ,meters, replacement of defective fuses , wiring and testing and serviceability check complete all as per the direction of Engineer in Charge and manufacturer instructions.
S & F Highbay luminaire with Al die-cast housing for efficient thermal heat management and secondary modular lense optics for optimised light distribution to improve operational efficiency, with EMC/EMI compliant potted driver, flicker free illumination 100 W LED light fitting complete all as specified and directed. Make:- Bajaj Cat No TENTO NXT B 110L WH MB SD or equivalent Havells/Crompton/Philips
S & F lowbay luminaire with Al die-cast heat sink housing for efficient thermal heat management energy efficient with clear diffuser with IP 65 degree of protection 35 Watt LED light fitting including necessary fixing arrangement with existing down rod complete all as specified and directed by Engr-in-Charge. Make:- Bajaj Cat No BIWDN 35W LED PC WH P or equivalent Havells/Crompton/Philips
SCHEDULE 'A' PART-II [ E/M LIGHTING WORKS]
Supply and fix in repairs for the following items for street light fittings complete all specified and as directed as under :- Make - Bajaj/Philips/Crompton Greaves/Havells
(a) Ballast for HPSV/MH - 400 Watts
(b) Metal halide lamp 400 Watts
(c) Metal halide lamp 250 Watts
(d) Metal halide lamp 150 Watts
Excavation in trenches not exc. 1.5 m wide and not exc.1.5 m deep for laying of cable, pipe and for erecting of steel tubular swaged pole etc, and getting out in hard/dense soil. Complete all as specified and as directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and as directed.
Removing excavated material not exc 50 mtrs and depositing where directed at a level not exceeding 1.5 mtr above the starting points in soil complete all as specified and as directed.
Supply, spreading and compacting of approved river sand in cable ducts / trenches for cable cushion on both top and bottom of cable, including ramming as specified and directed by Engineer-in-Charge. Note :- Punned thickness only shall be measured and paid.
Supply and lay burnt bricks for cable protection of sub class 'B' standard size in trenches complete all as specified and as directed.
Supply and laying LT UG cable, 1100 volts grade, XLPE insulated and PVC sheathed, armoured, multistranded, heavy duty electric cable with aluminium conductor laid in trenches, ducts, on poles, walls, through pipes etc complete for the following sizes including cable glands on both side terminations where necessary etc., complete including taking down the existing cable of following sizes:- Note: Earth work and excavation shall be measured and paid separately.
(a) 2 core 6 Sqmm
(b) 2 core 10 Sqmm
(c) 4 core 10 Sqmm
(d) 4 core 16 Sqmm
Supply and fix in repairs Post top lantern fitting LED type with 40 Watt LED made in cast aluminium spigot housing with decorative opal acrylic diffuser and IP 65 protection complete all as specified and as directed. Make : Bajaj Cat No. BGCL 40W LED or equivalent in CORMPTON/PHILIPS /HAVELLS/C&S as approved by GE
Supply and fix in repairs LED flood light luminarie 100W with pressure die cast aluminium housing including 3 core flexible conductor for light connection complete all as specified and as directed. Make : Bajaj /CORMPTON/PHILIPS/HANELLS/C&S as approved by GE
Supply and fix in repairs LED lamp fitting with 1 x 45 LED and all other accessories complete and Disconnecting and taking down the unserviceable rusted street light fittings from the steel tubular poles including 3 core flexible conductor for light connection complete all as specified and as directed. Make : Bajaj /CORMPTON/PHILIPS/HANELLS/C&S as approved by GE
Supply and fix 40 mm dia light grade GI tube bracket of length 1.5 metre bend to required shape including MS clamp made out of 30 mm x 6 mm MS flat iron and fix on steel tubular poles with necessary GI bolts, nuts and washers - 2 sets for each fittings including taking down the existing GI tube bracket complete set all as specified and directed.
Supply and fix 3 pole power contactor, ML 3 type, AC 440 Volts, 3 phase, coil voltage 440 volts, 40 Amps in the existing street light control switch box complete all as specified and as directed. Make : L & T cat part No S90721 or equivalent in BCH / Siemens.
Supply and fix Timer Switch as per maxirex4 QT(daily) withIP-53 Box complete all as specified and as directed. Make: INDO ASIAN /L&T/Legrand(MDS)/Schnieder.
Supply only IP 66 moduler box made of FRP / impact resistance plastic & heat resistant materials of size 205x255x112 mm including provision of MCB SP 6A, connector terminal block 4 pole 16 A capacity and fixing to the street light or post top light pole with suitable sizes of clamps, nuts and bolts complete all as specified and as directed.
M & L for preparing the surface of steel tubular poles,9/11 mtr long with , cross arms, clamps etc and applying one coat of aluminium paint incl numbering the poles with white colour paints over black back ground etc complete all as specified and as directed by Engr-in-Charge.
Material and labour for providing cement concrete 1:2:4 type B1 using 20 mm graded stone aggregate cast in situ as in copings and the like including weathering, slightly rounded or chamfered or chamfered angles as directed including use of form work as necessary all as specified and as directed.
Material and labour for plain cement concrete 1:4:8, type D-2, using 40mm graded aggregate in foundation filling and mass concrete complete all as specified and as directed.
Material and labour for fixing the new moulded case circuit breakers in the existing feeder pillar box with new bolts and nuts including connecting the incoming and out going cables by using suitable cable glands and jumpers/cable with the bus bar. Taking down burnt out MCCB, and supply and fix new moulded case circuit breakers of following capacity in the existing feeder Pillar box with new bolts complete as specified and directed.
(a) MCCB 4 pole 200 Amps 25 KA.
(b) MCCB 4 pole 100 Amps 18 KA
(c) MCCB 4 pole 63 Amps 18 KA
M&L for Cutting and cleaning the bushes and unwanted plant growth inside E/M installations and depositing at a distance not less than 50 m from perimeter wall / fencing of installation at various places of power house, complete all as specified and directed
M & L for attend breakdown complaints like street lights, street light timer ,replacing of damaged cable if required etc with help of required tools complete all as specified and directed
K.V.GEORGE AND COMPANY
T.I.John and Sons
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .