Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.5 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹12.8 L+₹2,603 (0.20%)Rejected-Finance RZ 18 260 WEST SAGARPUR NEAR MCD SCHOOL NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹13.3 L+₹54,054 (4.22%)Rejected-Finance 131 SHINGANAPUR ROAD KOLKI KOLKI SATARA MAHARASHTRA 415523 | SATARA | MAHARASHTRA | 415523 | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹16.4 L+₹3.6 L (28.4%)Rejected-Finance B 3 105 PASCHIM VIHAR NEW DELHI 110063 | WEST | DELHI | 110063 | L4 | Rejected-Finance Other than lowest | |
| 5 | L5₹16.6 L+₹3.8 L (30.0%)Rejected-Finance WZ 576 577 NANGAL RAYA NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | L5 | Rejected-Finance Other than lowest |
Tender Value
₹20.4 L
EMD Value
₹40,860
Closing Date
24 Nov 2022, 6:00 pmClosed
GE UTILITY PLANT AND MACHINERY DELHI CANTT-10
GE UTILITY PLANT AND MACHINERY KIRBY PLACE DELHI CANTT-10
CERTAIN ESSENTIAL REPAIRS TO CENTRAL AC PLANTS OF CAP 3X60 TR AT HQ CICG TG, 3X22.5 TR AT ADP, 3X15 TR AT CICP IN COD UNDER GE UTILITY PLANT AND MACHINERY DELHI CANTT-10
2022_MES_558137_2
GE(U)/PM/D-46/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
DELHI CANTT-10
MES contractor enlisted under class E category c(i) having deposited standing security of Rs 50000 with department. Contractor not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category.
6 documents required · 6 mandatory
₹500
GE UTILITY PLANT AND MACHINERY DELHI CANTT-10
₹40,860
Yes
26 Dec 2022
3 Nov 2022
26 Nov 2022
3 Nov 2022
24 Nov 2022
10 Nov 2022
Amount
M&L for de-scaling condensers of central AC Plant of capacity 3x60 TR at HQ CICG TG, by opening side plate, flushing the condenser tubes, using de-scaling soluation of suitable gravity, rodding the condenser tubes carefully removing all the deposited materials completely and raising the soluation through condenser tubes till clear water starts to come out from the condenser as complete including re-fixing the side plates by replacing gasket and testing complete for satisfactory working complete all as specified and directed by the Engr-in-Charge.
-diitto- all as per item no 1.00 above but Capacity of AC Plant 3 x 22.5 TR at ADP COD.
-diitto- all as per item no 1.00 above but Capacity of AC Plant 3 x 15 TR at CICP COD.
M&L for machining,Grinding and polishing of crank shaft and making the crank shaft suitable for normal running and matching the dia to the main bush and connecting rod and bearings for the following compressor models.
SMC 8-65. (Make:- ACCEL of capacity 22.5TR)
SMC 4-65 (Make:- ACCEL of capacity 15TR)
Supply and fixing in repair Shaft seal Assembly suitable for SMC 8-65 compressor complete all as specified & directed. (Make: as per sample)
Supply and fixing in repair Shaft seal Assembly suitable for SMC 4-65 compressor complete all as specified & directed. (Make: as per sample)
Supply & fix in repairs Padestal bearing P-207/208 heavy duty of AHU blower of any size as directed by Engr-in-Charge. (Make : NTN/SKF /NBC)
Disconnecting from mains/taking out existing unserviceable/defective Monoblock Pump set of capacity 3/5 HP and repair/ replacement of bushings, worn out nuts, bolts washers, gaskets, gland etc and positioning the pump set and connecting up in existing position and testing complete all as specified and as directed by Engineer-in-Charge.
Disconnecting from mains/taking out existing unserviceable/defective Monoblock Pump set of capacity 7.5/10 HP and repair/ replacement of bushings, worn out nuts, bolts washers, gaskets, gland etc and positioning the pump set and connecting up in existing position and testing complete all as specified and as directed by Engineer-in-Charge.
Material and Labour for frame work with angle iron for frame support, with fabrication, welding joining including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 including taking down old unserviceable one complete all as specified and as directed by Engr-In-charge.
M&L brick work with burnt brick best quality locally available brick old size laid straight or curved on plan to any radius built in cement mortar 1:4, including taking down old unserviceable one complete all as specified and directed
M&L for plastering 10 mm thick on fair faces of brick work in cement mortar 1:4 and finishing the surface even & smooth (without using extra cement), complete all as specified and directed
M&L for Preparation of new plastered surfaces of walls and applying two coats of whitewash complete all as specified and directed by engineer in charge.
S&F in repairs thermostatic expansion valve of suitable for existing AC Plant including cutting, welding, brazing, replacement of new gasket, nut bolt, washer etc all as specified & directed by Engineer-in-Charge, (Make-Sporlon/ Danfoss) Note:- Before disconnecting the existing expansion valve from the system the refrigerant has to be pump down or taken in empty cylinder by help of ICE etc.
Materials and labour for PCC (1:2:4) type B-2 (using 40 mm graded stone aggregate) as in foundation filling and mass concrete including demolition of existing foundation and removing from site complete all as specified and as directed.
M&L for replacing the compressor oil N-68 of compressor including draining & disposing the old compressor oil. (Make:- HPCL(Seetal)/ HP (Seetal)/ Servo). (a) SMC 8-65.Make:ACCEL of capacity 3x22.5TR. (b) SMC 4-65 Make:Accel of capacity 3x15TR.
Disconnecting from mains/taking out existing unserviceable/defective motor of capacity 20/30 HP of any size, type, and make including disconnecting all electrical connections removing from foundation transporting to repair workshop disconnecting unserviceable burn out winding completely including insulating materials and rewinding of the complete stator with super enameled copper wire of existing size applying proper insulation ‘F’ class varnish drying in oven, assembling, transporting back to site, re-installating, testing and commissioning complete all as specified and as directed by Engineer-in-Charge.
Disconnecting from mains/taking out existing unserviceable/defective motor of capacity 7.5/10 HP of any size, type, and make including disconnecting all electrical connections removing from foundation transporting to repair workshop disconnecting unserviceable burn out winding completely including insulating materials and rewinding of the complete stator with super enameled copper wire of existing size applying proper insulation ‘F’ class varnish drying in oven, assembling, transporting back to site, re-installating, testing and commissioning complete all as specified and as directed by Engineer-in-Charge.
Disconnecting from mains/taking out existing unserviceable/defective centrifugal pump of capacity 7.5/10 H.P of Central AC Plant, opening the pump, checking/repairing the impeller for any defects, replace the worn out bearing ring of the impeller, stuffing box, back plates, gland packing mechanical seal and rusted nut, bolts etc assembling properly, greasing all movable parts and connecting up in existing position and testing complete all as specified and as directed by Engineer-in-Charge.
Material and labour for Overhauling and repairing of any size refrigerant suction/ delivery liquid line valve including servicing of valve, replacement of packing material, sealing rings, Teflon washers and testing complete all as specified and as directed by Engineer-in-Charge.
Material and labour for leakage detection of chiller and condensor pipe lines by charging dry Nitrogen Gas and with standing pressure for 24 hours, rectification of leakages, evacuation of the system as per manufacturer’s instruction complete all as specified and directed by Engineer-in- Charge for capacity of 3x15 TR at COD. Note:- The rates quoted by the contractor shall deemed to include the cost of Nitrogen gas, charges for T&P and empty cylinders.
-ditto- all as per item No. 21 above but Capacity of 3 X 22.5 TR AC plant at COD.
M&L for Supply, installation, testing and commissioning in replacement of 3-Way Mixing valve suitable forAccel reciprocating compressor SMC 4-65/8-65 of capacity 15/22.5 TR, complete all as specified and directed by Engineer-in-charge.
Taking down/ removing unserviceable plaster along with glass wool and GI wire mesh and material and labour for glass wool and wrapped with GI wire mesh and rendering 15 mm thick in Cement Mortar (1:4) over newly provided glass wool and wire mesh of 125 mm dia pipe complete all as directed by Engr-in-Charge.
Taking down/ removing unserviceable plaster along with glass wool and GI wire mesh and material and labour for glass wool and wrapped with GI wire mesh and rendering 15 mm thick in Cement Mortar (1:4) over newly provided glass wool and wire mesh of 100 mm dia pipe complete all as directed by Engr-in-Charge.
Taking down/ removing unserviceable plaster along with glass wool and GI wire mesh and material and labour for glass wool and wrapped with GI wire mesh and rendering 15 mm thick in Cement Mortar (1:4) over newly provided glass wool and wire mesh of 80 mm dia pipe complete all as directed by Engr-in-Charge.
Supply and fixing in repairs of basic all purpose surface and wall mounted LED batten 20 Watt with polycarbonate housing & intigrated electronic driver with all necessary fixing accessories complete all as specified and as directed. (Make : Havells/phillips/bajaj)
Supply and topping up of refrigerant Gas R-22/407/410, Make - Mefron or equivalent ISI approved as directed by Engr-in-Charge.
Supply only Compressor Oil RL -170H complete all as specified & directed by Engr-in-Charge. (Make:- HPCL(Seetal)/ HP (Seetal)/ Servo.)
M&L for 100 mm thick cement concrete type C-2, 1:3:6 ( 40 mm graded aggregate) including finishing surface of concrete topping even and fair ( without using extra cement), and finishing surface of concrete in floors including taking down complete all as specified & directed.
S&F Phase indication lights of suitable colour, 240V AC suitable for mounting on LT panel, complete all as specified and directed by Engr-in-Charge. (Make:- ESBEE)
S&F on/off/trip indication lights of suitable colour, 240V AC, suitable for mounting on LT panel compete all as specified and directed by Engr-in-Charge. (Make:- ESBEE)
S&F on/off push buttons suitable for mounting on LT panels, complete all as specified and directed by Engr-in-Charge. (Make:- ESBEE)
S&F in replacement moulded case circuit breakers(MCCB) 125 Amps, adjustible type, 4 Pole, 36 kA, thermal magnetic with rotary handle and spreader compete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in replacement moulded case circuit breakers(MCCB) 100 Amps, adjustible type, 4 Pole, thermal magnetic with rotary handle and spreader compete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in replacement miniature circuit breaker (MCB) 63 Amps, 4 Pole, 25 KA complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in replacement miniature circuit breaker (MCB) 32 Amps, 4 Pole, 25 KA complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in replacement 'C' curve miniature circuit breaker (MCB) 6-32 Amps, single pole (SP), 10 KA complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in replacement power contactor, 32 Amps triple pole (TP), AC 3 duty, complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in replacement power contactor, 25 Amps triple pole (TP), AC 3 duty, complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in replacement power contactor, 18 Amps triple pole (TP), AC 3 duty, with add on block, complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in replacement power contactor, 12 Amps triple pole (TP), AC 3 duty, with add on block, complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in replacement power contactor, 9 Amps triple pole (TP), AC 3 duty, with add on block, complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in repair auxillary contactor (add-on block), suitable for 18-32 amps power contactors, complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in repair overload relay 14-23 amps,complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in repair overload relay 9-15 amps,complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in repair star/delta timer range 3-30 seconds,suitable for LT panels complete all as specified and directed by Engr-in-Charge. (Make:- L&T or equivalent in ABB/Legrand)
S&F in repair solid state single phasing preventer type VSP2 complete all as specified and directed by Engr-in-Charge. (Make:- Minilec/ L&T/ Siemens/Legrand/ ABB/ C & S.)
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, armoured, electric power cables (heavy duty) 1100 Volts grade with aluminium conductor of cross sectional area 150 Sqmm, 3 ½ core with galvanized steel strip or wire including taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make:- RR KABEL./ FINOLEX/ POLYCAB/ KEI INDUSTRIES LTD./ HAVELLS.)
`-ditto- all as per item No. 51 above but cross sectional area 35 Sqmm, 3 ½ core.
`-ditto- all as per item No. 51 above but cross sectional area 16 Sqmm, 4 core.
`-ditto- all as per item No. 51 above but cross sectional area 10 Sqmm, 4 core.
Supply & fixing in repairs aluminium lugs for cable of cross sectional area 10 Sqmm complete all as specified and directed by Engineer-in-charge.
Supply & fixing in repairs aluminium lugs for cable of cross sectional area 16 Sqmm complete all as specified and directed by Engineer-in-charge.
Supply & fixing in repairs aluminium lugs for cable of cross sectional area 25 Sqmm complete all as specified and directed by Engineer-in-charge.
Supply & fixing in repairs aluminium lugs for cable of cross sectional area 35 Sqmm complete all as specified and directed by Engineer-in-charge.
M&L for taking out old MS pipes and Supplying & laying , testing & commissioning mild steel (Heavy) 'C' class pipe of size 80 mm dia on exposed surface / underground (in trenches) including welding works, connections with existing chiller/condenser water line, chiller/condenser pump, fabrication of bends, MS flange, tees, reducers, shoe, support ( brick masonry block & wooden support for underground / MS angle- clamp & wooden support for exposed surface ) along with priming coat of steel primer as per standard specification. Note:- (i) The rates quoted by the contractor shall deemed to include the cost of MS fittings required during laying of MS Pipes. (ii) The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be heavy class of thickness min. 7mm as per IS: 3589 (Make:- TATA/ JINDAL/ PRAKASH SURYA)
-ditto- all as per item No. 59 above but of size 100 mm dia
-ditto- all as per item No. 59 above but of size 125 mm dia
M&L for Taking out old corroded GI water tubing of 40/50 mm dia.
-ditto- all as per item No. 62 above but 25 mm dia.
Supply and laid complete with all fittings in trenches/exposed surface, GI Tubing 'Medium grade' of dia 50 mm. (Make:- JINDAL/ TATA/ PRAKASH SURYA)
-ditto- all as per item No. 64 above but 40 mm dia.
-ditto- all as per item No. 64 above but 25 mm dia.
Supply and fixing in repair humidity self priming motor pump set of cap 0.5 HP single phase 240 volt complete all as specified and directed by Engineer-in-Charge. (Make:- Usha/ M/s Seetal /HP/Amcrate )
Supply and fixing in repairs thermostat for AHU room, as per existing size & specification complete all as specified and as directed. (Make:-SIEMENS/ DANFOSS/ INDFOSS/ANERGY).
Supply and fixing in repairs of Pre filter 10 micron of size 600mm x 600x 50mm made of out of GI wire mesh interspaced with two crimp layers and three flat layers flanged deep box type and efficiency 90% as per existing size and pattern for the all three AC Plant air handling unit complete all as speicifed and directed by Engr-in-charge. (Make:- Athlete or equivalent as approved by Accepting Officer.)
-ditto-all as per item No.69 above but size 600mm x 300mm x 50mm.
-ditto- all as per item No. 69 above but size 300mm x 300mm x 50mm.
Supply and fixing in repairs gun metal gate valves with iron wheel head, screwed both ends for iron pipe, ISI Marked, as per IS:778 of size 25 mm bore complete all as specified and directed. (Make:- KIRLOSKAR/ LEADER/ ZOLOTO)
-ditto- all as per item No. 72 above but of size 40 mm bore
M&L for Dismantling old/Unserviceable/rusted ,Supply/Return/Fresh Air GI Duct of any size/shape/dia with insulation from walls, roofs, ceiling for replacement complete Including Ducting Supports , rubber gaskets, elbows, vanes, & supports etc. from central AC plants, complete all as specified and directed by engineer-in-chrage.
Supply, assemble and errection of ducting, made up of GI Sheets of 1mm (20 guage) thickness as in Air Condition Ducting including fabrication for required size, patch work, fixing on walls, roofs or ceiling or in existing iron frame work including all accessories such as Corner, Cleat, Carriage bolt, Gasket, lap joint, welding, reverting and appropriate sealant on longitudinal joints etc. complete all as specified and as directed by Engr-in-charge. (Make:- TATA/ JINDAL/ SAIL).
M&L for Supply and installation of thermal insulation material 25 mm thick for non-exposed Ducts with closed cell class o nitrile rubber elastomeric insulation of density 40-60 Kg/m3 thermal conductivity of 0.033-0.038 W/mk and µ>=7000 (k-flex st) to be applied on ducts using manufacturers recommended rubber based adhesive as per the approved specification the material should be from global approved & UL approved for new ducts as required at site complete all as specified and directed by engineer-in-charge. (Make : KFLEX/ARMAFLEX/PARAMOUNT)
M&L for Supply and installation in replacement of 50mm thick resin bonded fibre glass wool roll of density 24 kg/Cum, with factory laminated aluminium vapour barrier insulation in existing ducts of AC plants, applying rubber based adhesive CPRX compound including wraping, pasting complete and cover the insulation one side with GI wire Mess netting after cleaning the duct surface (to be insulated ) by scrapping carefully with wire brush etc. to make the surface completely free of millscale, dirt, dust, grease and other foreign materials, sealing of all longitudinal joints and circular overlaps with and including Aluminium foil tape 50 mm wide, to make the insulation leakproof against any leakage and securing the insulation with and including mechanically fastened nylon/ steel straps of size 12 mm/50 mm at maximum intervals of 1.2 mtr, including taking down old unserviceable one, complete all as directed by Engr-in-Charge. (Make:- Shri Fire Pack/ Impex Insulation/ Trans Insulation).
M&L for Dismantling old/Unserviceable/rusted Supply/Return Air Diffuser/Dampers/side Grilles/VCD , of any size, type, shape from any location at Central AC Plants, complete all as specified and directed by engineer-in-charge.
M&L for Supply, fixing of powder coated extruded aluminum rectangular diffusers of required sizes with black anodized extruded aluminum volume control damper, nuts, bolts, screws etc.complete all as specified and directed by engineer-in-charge.
M&L for Supply, fixing of powder coated extruded aluminum rectangular diffusers of required sizes without volume control damper, along with nuts, bolts, screws etc.complete all as specified and directed by engineer-in-charge.
Supply & Fixing of powder coated extruded aluminum supply & return grills complete with fixing accessories like nuts, bolts, screws etc. complete all as specified and directed by engineer-in-charge. (Make:- Mapro/brightflow/ Ravistar)
Supply and fixing in repairs cast iron butter fly valves lever operated SS disc type nitrile/EPDM rubber lining PN 16 of dia 125 mm complete all as specified and directed by the Engr-in-Charge. (Make:- AUDCO/ LEADER/ZOLOTO).
-ditto- all as per item No. 82 above but 100mm dia.
-ditto- all as per item No. 82 above but 80 mm dia.
-ditto- all as per item No. 82 above but 50 mm dia.
Supply and fixing in repairs cast iron Y strainer flanged ends with SS perforated sheet screen of size 125 mm complete all as specified and directed by the Engr-in-Charge. (Make: - ADVANCE/ AUDCO/ LEADER/CASTLE/ NVR/ ZOLOTO).
-ditto- all as per item No. 86 above but 100 mm dia.
-ditto- all as per item No. 86 above but 80 mm dia.
Supply and fixing in repairs cast iron non return valves of dia 125 mm pressure class PN 16 including nuts, bolts, washers, gaskets, etc for Central type AC plants complete all as specifed and directed by Engineer-in-Charge. (Make: - ADVANCE/ AUDCO/ LEADER/CASTLE/ NVR/ ZOLOTO).
-ditto- all as per item No. 89 above but 100 mm dia.
-ditto- all as per item No. 89 above but 80 mm dia.
Supply and fixing in repairs Immersion heaters of cap 6 KW 230/440 volts as required (Make:- Dasspass/crown/Theata)
Supply and fixing in repairs Immersion heaters of cap 5 KW 230/440 volts as required (Make:- Dasspass/crown/Theata)
Supply and fixing in repairs strip heater heaters of cap 3 KW 230/440 volts as required. (Make:- Dasspass/crown/Theata)
Supply and fixing in repairs strip heater heaters of cap 2 KW 230/440 volts as required (Make:- Dasspass/crown/Theata)
S&F in replacement of temeperature Sensors of the chiller and condenser lines operates by mercury liquid of range 0-50⁰C. (Make:- Fiebig/H guru/AE)
S&F in replacement of compound gauges of the chiller and condenser lines of range 0 - 150Psi. (Make:- Fiebig).
Supply & fixing HRFR PVC insulated single core copper conductor cable of size 6 sqmm for connections in LT Panels including copper thimbles including taking down old unserviceable one complete all as specified and directed by Engineer-in-Charge. (Make:- RR KABEL./ FINOLEX/ POLYCAB/ KEI INDUSTRIES LTD./ HAVELLS).
Supply & fixing HRFR PVC insulated single core copper conductor cable of size 10 sqmm for connections in LT Panels including copper thimbles including taking down old unserviceable one complete all as specified and directed by Engineer-in-Charge. (Make:- RR KABEL./ FINOLEX/ POLYCAB/ KEI INDUSTRIES LTD./ HAVELLS).
Supply & fixing HRFR PVC insulated single core copper conductor cable of size 16 sqmm for connections in LT Panels including copper thimbles including taking down old unserviceable one complete all as specified and directed by Engineer-in-Charge. (Make:- RR KABEL./ FINOLEX/ POLYCAB/ KEI INDUSTRIES LTD./ HAVELLS).
Supplying and fixing Fire Extinguisher Carbon dioxide (CO2) extinguishers consisting of welded M.S. cylindrical body, light weight squeeze lever discharge valve fitted with pressure indicating gauge with internal discharge tube, discharge nozzle suspension bracket of capacity 4.5 Kg as per IS: 2878 complete with holding accessories including taking down old unserviceable one complete all as specified & directed by Engineer-in-Charge.
-ditto- all as per item No. 101 above but CO2 of capacity 6 Kg.
Supply and fixing in replacement LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed by Engr-in-Charge. (Make:- HAVELLS/ PHILIPS/ BAJAJ)
Supply and fixing in repairs of brass safety valve complete suitable for compressor Model No. SMC 4-65 of Make-ACCEL complete all as specified and directed by Engr-in-charge.
Supply and fixing in repairs of brass safety valve complete suitable for compressor Model No. SMC 8-65 of (Make:- ACCEL complete all as specified and directed by Engr-in-charge).
Supply and fixing in repair fan belt of size B-43,A-58,A-50.A- 34 to A-41 (Make:- Fenner/ Dunlop)
Supply & fix in repairs fan belt of size B 73 to B-76,B 82,B 92, (Make- Fenner/Dunlop)
M& L for taking out old unserviceable/ burnt out Electronic expansion valve drive for 60 TR AC Plant, Supply and fixing, of new Electronic expansion valve drive including programming for analog signal positioner for motherboard Model No DCO 3000 HSN code - 853700 of Kirlosker.
Supply and fixing in repairs bakelite terminal plate including brass studs, bolts and nuts etc suitable to match any make of 3 phase electric motors and capacity upto 10 HP complete all as specified and directed by Engr-in-Charge.
M&L for taking out burnt SMPS board of hot water generator for AC plant and refixing in original position, after necessary repair by replacing the burnt electronic spares from authorised manufacturer workshop , including reprogramming, resolving the problem and testing complete as directed by Engr-in -Charge
Supply and fixing in repairs Star Delta starters for motors of 10 HP capacity with suitable rating relay, suitable for mounting on existing LT Panels of AC plants and connections with suitable size single core copper conductor wire complete all as specified and directed by Engr-in-Charge. (Make:-L&T/Siemens/Legrand/ ABB/Crompton.)
Supply and fixing in repairs of PVC fins size 600x300x150 for Cooling Tower, Complete all as specified & directed. (Make:- as per sample)
Supply and fixing in repairs of PVC eleminators size 600x300x150 for Cooling Tower, Complete all as specified & directed. (Make:- as per sample)
Supply and fixing in repairs of PVC branch pipe of (set of 4 Nos.) including PVC flaps clamps etc complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repair cooling tower sprincle suitable for 75 TR cooling tower complete all as specified and directed by Engineer-in-Charge.
M &L for dismantling the old broken fan hub assembly including blades of cooling tower and replacement with new fan hub assembly with die cast aluminium blades adjustible pitch axial fan of dia 1200 mm heavy duty as per existing size including U-clamps, nuts, bolts & washersetc.,complete all as specified and directed by Engineer-in-Charge.
-ditto- all as per item No. 116 above but fan of dia 900 mm.
Supply and fix loading coil , 12-15 Watts suitable for 60 TR chiller unit model- CXH0180298Y including taking down old unserviceable one complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repair H.P/L.P cutout type MP15 as specified and as directed. (Make:-Danfoss)
Supply and fixing in repair oil pressure failure switch type MP55 as specified and as directed. (Make:-Danfoss)
Taking down carefully existing surface/ concealed unserviceable aluminum/ copper point wiring (light, fan, socket, power or sunken box) complete including fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings, etc. and making good to disturbed surfaces of walls, floors, ceilings, etc. where required and finished the existing surfaces after complete of new point wiring as specified here-in-after complete all as specified and as directed.
Material and labour for point wiring with 1.5 sqmm (nominal area) PVC insulated and unsheathed single core FRLS (conforming to IS-694) copper cable 1100 volts grade with multi stranded copper conductor in and including PVC casing caping (medium grade) of adequet size dia with all fittings and accessories including 2mm thick sunk MS pressed steel terminal boxes of appropriate size with 3.0mm thick plastic laminated sheet top cover with cadmium plated iron screws complete including PVC insulated and unsheathed FRLS (conforming to IS-694) single core multi stranded copper conductor cable of size 1.5 sqmm green colour as earth continuty conductor connected to common earth dolly for one light/ fan point controlled by one, one way switch complete all as specified and as directed. (Make of Cable:- FINOLEX/ HAVELLS/ POLYCAS)
-ditto- all as per item No. 122 above but one 5/6amps socket outlet point on the same board with other switches complete all as specified and as directed.
Material and labour for point wiring with 1.5sqmm (nominal area) PVC insulated and unsheathed single core FRLS (conforming to IS-694) copper cable 1100 volts grade with multi stranded copper conductor in and including PVC casing caping (medium grade) of adequet size with all fittings and accessories including 2mm thick sunk MS pressed steel terminal boxes of appropriate size with 3.0mm thick plastic laminated sheet top cover with cadmium plated iron screws complete including PVC insulated and unsheathed FRLS (conforming to IS-694) single core multi stranded copper conductor cable of size 1.5sqmm green colour as earth continuty conductor connected to common earth dolly for one 5/6 Amps socket outlet points controlled by one, one way switch on independent board complete all as specified and as directed. (Make of Cable:- FINOLEX/ HAVELLS/ POLYCAS)
Material and labour for point wiring with 2.5sqmm (nominal area) PVC insulated and unsheathed single core FRLS (conforming to IS-694) copper cable 1100 volts grade with multi stranded copper conductor in and including PVC casing caping (medium grade) of adequet size with all fittings and accessories including 2mm thick sunk MS pressed steel terminal boxes of appropriate size with 3.0mm thick plastic laminated sheet top cover with cadmium plated iron screws complete including PVC insulated and unsheathed FRLS (conforming to IS-694) single core multi stranded copper conductor cable of size 2.5sqmm green colour as earth continuty conductor connected to common earth dolly for one 5or6 /15or16 Amps socket outlet points controlled by one, one way switch on independent board complete all as specified and as directed. (Make of Cable:- FINOLEX/ HAVELLS/ POLYCAB)
Supply & fixing switch piano flush type 5 amp single Pole one way complete all as specified and directed by Engr-in-Charge. (Make:- ANCHOR/ LEGRAND/ CONA/ HAVELLS)
Supply and fixing switch socket combination, 2 in 1, 2/3 pin, 5/6 Amp flush type controlled by one switch complete all as specified and directed by Engr-in-Charge. (Make:- ANCHOR/ LEGRAND/ CONA/ HAVELLS)
Supply and fixing switch socket combination 5/6 Amps and 15/16 Amps and 5 in 1, 5 pin flush type universal controlled by one switch complete all as specified and directed by Engr-in-Charge. (Make:- ANCHOR/ LEGRAND/ CONA/ HAVELLS)
Material and labour for ceiling rose PVC/ polycarbonate, isolated body 63.5x23.5mm, 3 terminals complete all as specified and directed by Engr-in-Charge. ((Make:- ANCHOR/ PLAZA/ HAVELLS)
Disconnecting and S&F, in repairs, factory made Sheet metal enclosure, shutter type, for double door distribution board (when MCBs are to be used), single pole and neutral, 8 Way, 240 Volts, with 200 Amp rated busbar, complete all as specified and as directed by the Engineer-in-Charge. (MCBs shall be measured & paid for separately under respective items of this Schedule) (Make:- L&T/ SIEMENS/ LEGRAND)
Disconnecting and S&F, in repairs, factory made Sheet metal enclosure, shutter type, for double door distribution board (when MCBs are to be used), single pole and neutral, 4 Way, 240 Volts, with 200 Amp rated busbar, complete all as specified and as directed by the Engineer-in-Charge. (MCBs shall be measured & paid for separately under respective items of this Schedule) (Make:- L&T/ SIEMENS/ LEGRAND)
Supply only in replacement MCB SPN 32 Amps 230 Volts all as specified. (Make:- L&T/ SIEMENS/ LEGRAND)
Supply and fix auto capacity regulator solenoid valve , 220V, 50 Hz including connecting to inter rack with nut bolts, washer etc including taking down old unserviceable one complete all as specified and directed by Engineer-in-Charge. (Make:- TOTEX/ AVCON/ ACCEL)
P S TRADERS
Vishal Traders
HONEY COLLECTION
Shiv Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .