| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.0 LAccepted-AOC | L1 | Accepted-AOC Found lowest and reasonable | |
| 2 | L2₹29.9 L+₹2.9 L (10.8%)Rejected-Finance 114 SHASTRI NAGAR MEERUT | MEERUT | UTTAR PRADESH | 245206 | L2 | Rejected-Finance Rejected Being not L1 | |
| 3 | L3₹31.2 L+₹4.2 L (15.6%)Rejected-Finance RADHA NIKUNJ L 2 SOUTH CIVIL LINES ROORKEE HARIDWAR UTTARAKHAND 247667 | ROORKEE | HARIDWAR | UTTARAKHAND | 247667 | L3 | Rejected-Finance Rejected Being not L1 | |
| 4 | L4₹35.5 L+₹8.5 L (31.6%)Rejected-Finance | L4 | Rejected-Finance Rejected Being not L1 | |
| 5 | L5₹38.3 L+₹11.3 L (41.9%)Rejected-Finance | L5 | Rejected-Finance Rejected Being not L1 |
Tender Value
Refer Docs
EMD Value
₹85,240
Closing Date
27 Jun 2024, 6:00 pmClosed
GE (U) Meerut Cantt
Roorkee road Meerut Cantt
PROVN OF APFC PANEL AT NORTH AREA AND PROVN OF 03 PHASE SERVO STABILIZER (360V 480V RANGE) FOR SURGICAL SPLIT (SMALL CLINIC) AT 32 MVH CL-1 AND ALLIED WORK UNDER GE(U) MEERUT CANTT
2024_MES_656841_1
8596/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Meerut
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
Yes
₹85,240
Yes
30 Oct 2024
30 May 2024
4 Jul 2024
30 May 2024
27 Jun 2024
13 Jun 2024
Amount
Supply, installation, testing & commissioning POWER FACTOR IMPROVEMENT panel for indvidaul motor of capacity 75 HP motor floor mounted panel, indoor type of size 850X750X500mm, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system,dust and vermin proof, made out of CRCA sheet outer box thickness 2.0 mm front hinged door with proper locking arrangement,rubber gasket on front side , powder coated with two coat of super enamel paint over a coat of red oxide primer having aluminium busbar 4 pole of capacity 300 Amps , colour coading , complete including Axial fan 225 mm swep single phase 230 volt heavy duty with temprature control devices internal wiring with minimum size: 1.5 sqmm of copper cable complete with cable connection from main panel to APFC panel of suitable size of aluminium lugs / thimble including cable gland (brass) fixing / grouting to floor with PCC (1:2:4) type B1 works, the panel should be of suitable size to accomodate the following:-
Note :- (a) PCC work required for fixing of panel shall be deemed to included in quoted rate. (b) Drawing of panel shall be approved by GE before placing the order. (c ) All type test certificate and design verification with switch gear (MCB/MCCB) as per confirming to IS/EIC-61439/2011 Part-I & Part-II with short circuit test at 65 KA should be submitted by the contractor before executing the job.
INCOMING:-
(a) MCCB, 160 Amps 4 pole 16 KA with spreader link - 01 No.
(b) Electronic Volt Meter 3 phase 415 V- 01 No
(c) Electronic Amps Meter 3 phase 0-100 Amps - 1 No including CT of ratio 63 / 5
(d) Electronic Power Factor Meter- 01 No.
(e) RYB phase Indicating Lamp LED type 240 V AC - 01 Set of three.
(f) APFC Relay 4 Steps,CT INPUT - 1 No.
(g) MCB,Single pole 230 volt 10 KA , 6A- 04 No.
OUTGOINGS:-
(a) Capacitor MPP Type, 480 V,of capacity 20 KVAR ( 10 KVAR- 1 No.+ 5 KVAR -1 No + 3KVAR-1 +2 KVAR-1No)
(b) Capacitive duty connector of capacity 20 KVAR ( 10 KVAR- 1 No.+ 5 KVAR -1 No + 3KVAR-1 +2 KVAR-1No)
(c ) MCB - C' curve 3 pole 16 to 32 amps, 10 KA -4Nos
(d) MCB 6 A, SP, C' Series, 10KA -4Nos
(e) Rotary Auto / Mannual switch, 6 Amps -1No
(f) On - Off push button with accessories-0 8 Nos
(g) On line indicator LED type - 4 Nos
Supply, installation, testing & commissioning POWER FACTOR IMPROVEMENT panel for indvidaul motor of capacity 40 / 50 HP motor floor mounted panel, indoor type size 850X750X500mm, suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system,dust and vermin proof, made out of CRCA sheet outer box thickness 2.0 mm front hinged door with proper locking arrangement,rubber gasket on front side , powder coated with two coat of super enamel paint over a coat of red oxide primer having aluminium busbar 4 pole of capacity 300 Amps , colour coading including Axial fan 225 mm swep single phase 230 volt heavy duty with temprature control devices, control wiring with minimum size: 1.5 sqmm of copper cable complete with cable connection from main panel to APFC panel of suitable size of aluminium lugs / thimble including cable gland (brass) fixing / grouting to floor with PCC (1:2:4) type B1 works, the panel should be of suitable size to accomodate the following:- Note :- (a) PCC work required for fixing of panel shall be deemed to included in quoted rate. (b) Drawing of panel shall be approved by GE before placing the order. (c ) All type test certificate and design verification with switch gear (MCB/MCCB) as per confirming to IS/EIC-61439/2011 Part-I & Part-II with short circuit test at 65 KA should be submitted by the contractor before executing the job.
INCOMING:-
(a) MCCB, 160 Amps 4 pole 16 KA with spreader link - 01 No.
(b) Electronic Volt Meter 3 phase 415 V- 01 No
(c) Electronic Amps Meter 3 phase 0-100 Amps - 1 No including CT of ratio 63 / 5
(d) Electronic Power Factor Meter- 01 No.
(e) RYB phase Indicating Lamp LED type 240 V AC - 01 Set of three.
(f) APFC Relay 4 Steps, 1 CT INPUT- 1No.
(g) MCB,Single pole 230 volt 10 KA , 6A- 04 No.
OUTGOINGS:-
(a) Capacitor MPP Type, 480 V,of capacity 15 KVAR ( 5 KVAR - 02 Nos + 3KVAR-1 +2 KVAR-1No)
(b) Capacitive duty connector of capacity 15 KVAR ( 5 KVAR -2 No + 3KVAR-1 + 2 KVAR-1No)
(c ) MCB - C' curve 3 pole 16 to 32 amps, 10 KA -4Nos
(d) MCB 6 A, SP, C' Series, 10KA -4Nos
(e) Rotary Auto / Mannual switch, 6 Amps -1No
(f) On - Off push button with accessories-0 8 Nos
(g) On line indicator LED type - 4 Nos
Note : (a) PCC work required for fixing of panel shall be deemed to included in quoted rate. (b) Drawing of panel shall be approved by GE before placing the order.
Supplying ,laying and testing XLPE Insulated, screened, bedded galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 Sq mm 3.5 core , laid in trenches/ducts or passed through pipes/roads or fixed to walls/poles complete connection with suitable size of aluminium lugs , nuts and bolts all as specified and directed.
Supplying ,laying and testing XLPE Insulated, screened, bedded galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 volts grade with stranded aluminium conductor of size 70 Sq mm 3.5 core , laid in trenches/ducts or passed through pipes/roads or fixed to walls/poles complete connection with suitable size of aluminium lugs , nuts and bolts all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 60cm x 60 cm x 6 mm thick buried directly in ground earth pit not less than 2.25 mtr deep below ground level with top edge of the plate not less than 1.5 mtr below ground level connected to Aluminium earth strip 25x4 mm by means of bolts, nuts, check nuts and washers of GI or steel surrounded with adequate quality of charcoal dust mixed with salt on all side of earth plate including complete earthwork PCC 1:2:4 chamber and RCC 1:2:4 cover all as shown in electrical plate No 5 and all as specified and directed by EIC Note:- If desired earth resitance not found, earthing shall be redone by the copntractor at no extra cost to the department
Supply, installing, testing and commissioning of 125 KVA Voltage servo stabilizer for un balanced load automatic operation, three phase naturally oil cooled indoor type & designed for input variation between 340 V to 460 V with output voltage stabilized at 415 with accuracy ± 2.5% and speed of correction 8 Volts per second and with control switches including area leveling with PCC Foundation near ground level to 20 cm height complete all as specified and as directed by Engr-in-Charge
M&L for shed of size 3mx3m, hieght 3m from GI covered with prepainted galvolume aluminium zinc coat GI based corrugated sheet 0.5 mm thick having tensile straingth of 550 mpa,4 No posts made of MS angle 65mmX65mmX6mm and roof frame with 3 Nos ms angle both side of size 50mmX50mmX5mm including 230 mm thick brick work wall upto 900 mm hieght (three side of shed) using fly ash bricks with cm 1:6, plastering of exposed surface of brick work with cm 1:4, 3 coat of white wash on plastered surface. Earth work for posts grouting of posts with PCC 1:3:6 type C1 and sub base PCC 1:4:8 (100mm thick) over mix including 100 mm thick hard core with brocken bricks and finish the floor with 50 mm thick PCC 1:2:4 type B0 including painting of steel surface with two coat of synthetic enamel paint over and including one coat of zinc oxide primer complete all as specified and directed by Engg-in-Charge.
M&L for plate earthing for sub station equipments complete with galvanised mild steel plate electrode 60 cm x 60 cm x 6.3 mm thick buried directly in ground vertically (in earth pit not less than 3.5 m below normal ground level) with the top edge of the earth plate at a depth not less than 2.75 m below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl GI earth strip 32 x 6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate at one end and connected to metallic bodies of HT/LT equipments etc at the other, earth strip encased in and including 40mm bore GI light grade pipe with all fittings from top of electrode to body of equipment fixed with and including 25 x 3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B-O using 12 mm graded crushed stone aggregate excavation & earth work and RCC cover complete all specified and shown in electrical plate No 5 of SSR Pt-I.
Supply, laying, jointing, testing and commissioning LT underground cables, 120 Sqmm 3.5 core 1100 volts grade, XLPE insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-7098 (marked, laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe complete all as specified and directed. (Note;- Rate quotted includes terminal Lugs / road cutting/ wall cutting/ floor cutting and making good damged portion matching with existing surface with all existing finishes.)
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in soft/ loose soil including trimming sides and bottom of trenches complete all as specified in the following type of soils:
Returning, filling-in, including spreading, watering and well ramming in layers not exceeding 25 cm thick each, in soft /loose soil complete all as specified in the following type of soils
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables complete all as specified.
M & L Bricks for protection cover to under ground cable (with standard size fly ash bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10mm as directed.
Jain Traders (BID ID -3032264)
EX SOLDIERS MECHANICAL WORKS (BID ID -3034391)
NITHYA INFRATECH (BID ID -3034987)
Ramesh Traders Govt Contractors & General OrderSuppliers (BID ID -3034585)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .