| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
Tender Value
₹14.1 L
EMD Value
₹28,299
Closing Date
6 Jan 2023, 6:00 pmClosed
AGM (E-E)
S V Airport Raipur
Modification of existing BMS System at S V Airport, Raipur
2022_AAI_136659_1
AAI/RPR/ENGG (E)/CW/BMS/2022-23/E-NIT-01
Open Tender
Electrical Works
Item Rate
30 days
S V Airport Raipur
as per NIT document
6 documents required · 6 mandatory
₹1,120
₹28,299
19 Jul 2023
28 Nov 2022
9 Jan 2023
29 Nov 2022
6 Jan 2023
29 Nov 2022
29 Nov 2022 - 12 Dec 2022
Amount
Supply, Installation, Testing and commissioning of Necessary BMS Software & Network interface unit (UL Listed) for integration of automation stations to management level network (BACnet/ Ethernet / IP) routers with integrate this BMS, complete etc as required.
Supply, Installation, Testing and commissioning of DDC Controller for AHUs (Compact DDC with atleast 36 I/O per DDC for two AHU control and atleast 22 I/O for single AHU control which shall be UL listed / approved. The DDC controllers shall be provided with minimum 32 bit microprocessors to carry out required control and management functions which is Based on ANSI/ ASHRAE standerd 136-2001 (BACNetT), ENV13321-1 Operation standalone are as part of Lon Talk system network TP/ FT- 10, 78k Bits with Built in BACnet/ Lontalk interface of ETHERNET/ IP. Including lockable mounting cabinets duly powder coated with connector terminals and internal wiring and switching relays at I/O Ports , complete etc as required.
Supply, Installation, Testing and commissioning of Duct mounted combined Temperature and Humidity sensors having temperature ranges of (-35 Deg C to + 35 Deg C and 0 to 50 Deg C) and time constant of 20 second in moving air. The Humidity measurement range shall be 0 to 100% RH. Humidity measurement accuracy +/- 2% within 0-90% RH. IP 65 protaction, CE marked , complete etc as required.
Supply, Installation, Testing and commissioning of the Indoor Air Quality sensor. This shall be design for acquiring indoor air quality from rooms of air ducts with micro-processor based unit having slective photo acoustic CO2 sensor and VOC sensor having IP 54 protection and CE marking , complete etc as required.
Supply, Installation, Testing and commissioning of Differential Pressure switch. The switch shall be diapragm operated and have differential pressure range of 50 to 500 Pa along with 2 meter tubing for acquiring the differential pressure. The housing shall be IP54 rated. The pressure switches shall be available in minimum of 3 ranges suitable for applications like Airflow proving, dirty filter, etc. The set point shall be concealed type , complete etc as required.
Supply, Installation, Testing and commissioning of Wall Mounted commbined Outside Temperature and Humidity sensors having temperature range of (-35 Deg C to + 35 Deg C and 0 to +50 Deg C) and time constant of 20 seconds in moving air. The Humidity measurement range shall be 0 to 100% RH. Humidity measurement accuracy +/- 2% within 0-100% RH. IP 65 protection, CE marked , complete etc as required.
Supply, Installation, Testing and commissioning of temperature sensor shall be Ni 1000 type fitting with element having positive temperature coefficient. Temperature measuring range shall be - 50 Deg C to + 130 Deg C , complete etc as required.
BMS Desktop PC OS: Windows 10 Professional OS: Windows 10 Professional CPU: Intel i7 (4 core), RAM :16 GB (RAM) HDD: 1 x 600+ GB, Mouse, Monitor, Ethernet port, USB ports MS Office 365
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .