| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.8 LAccepted-AOC 840 1B MADHUR VIHAR COLONY CIVIL LINES JHANSI UP 284 001 | JHANSI | JHANSI | UTTAR PRADESH | 284001 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹37.2 L+₹2.5 L (7.11%)Rejected-Finance CHATAI SHEEP WARD NO 07 NEW MARKET ROAD AHIWARA DURG CHHATTISGARH 490036 | DURG | CHHATTISGARH | 490036 | L2 | Rejected-Finance Not become lowest bidddr | |
| 3 | Rejected-Technical | - | Rejected-Technical Not enlisted in appropriate category |
Tender Value
Refer Docs
EMD Value
₹66,000
Closing Date
1 Feb 2021, 6:00 pmClosed
Major Deepak Kumar
Garrison Engineer Jhansi
REPAIR MAINT TO TRANSFORMERS HT LT OH LINE UG CABLE HT LT PANEL INCLUDING VARIOUS STREET GARDEN GATE LIGHT AND CERTAIN CI DI GI PIPE LINES PUMP MOTOR AND OH RESERVOIRS AT MILITARY STATION NOWGONG (BKD) UNDER AGE EM AT GE JHANSI
2020_MES_398969_2
GE/JHA/TOK/56 OF 2020-21
Open Tender
Civil Works
Item Rate
180 days
GE Jhansi
Please refer tender documents
6 documents required · 6 mandatory
₹500
Yes
GE Jhansi
₹66,000
Yes
19 Feb 2021
16 Jan 2021
3 Feb 2021
16 Jan 2021
1 Feb 2021
19 Jan 2021
Amount
Disconnecting and removing old jumpers, substation clamps and connectors of any description from 33 KV MRS switch yard at Jhansi Cantt and Material and labour for 33 KV jumpers using new ACSR conductor of code name DOG up to 3.0m (Three meters) length and connecting both ends with suitable type and size of 33 KV or above grade substation clamps and connectors such as PG Clamp, T Connector, C wedge connector, Bi-metallic transformer clamp, Compression Clamp, Isolator Clamp, Post Clamp, LA Clamp etc with stainless steel hardware complete as per site requirement and as directed by Engineer-in-Charge. (Note: ACSR Conductor (Dog) up to 3.0 meters length and both end substation clamps and connectors shall be measured as each jumper)
Supply and fix in replacement of Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, colour of glaze brown, three disc in series assembly for tension with tension clamps for conductors, working pressure 33 Kilo Volts complete all as specified and directed by Engineer-in-Charge. Make: BHEL/ Bengal Potteries/ Jayshree/ Pactil / WS Insulators/ Jaipuria/ Southern Insulators/ MEI/ Modern Insulators / Rashtriya
Supply and fix in replacement of 33 KV Post Insulator, porcelain, vitreous, brown insulator complete with GI fixing hardware and all as specified and directed by Engineer-in-Charge. Make: BHEL/ Bengal Potteries/ Jayshree/ Pactil / WS Insulators/ Jaipuria/ Southern Insulators/ MEI/ Modern Insulators / Rashtriya
Supply and fix in replacement of Lightning arresters expulsion type complete with all fittings, station class, discharge capacity 10 kilo amp suitable for 33 Kilo Volts complete all as specified and directed by Engineer-in-Charge. Make : Oblum /Atlas / BHEL / Rashtriya / Elpro / Crompton Greaves / Jaipuria
Supply and install in replacement of HT 33KV outdoor, triple pole, Gang Operated Switch, Double Break, Rotating type, Horizontal mounting consisting of hot dip galvanized channel iron base, having 2 Nos. Post type Insulators in stack & 3 stacks per phase, copper alloy high pressure heavily tinned contact plated m.s.arcing horns capable of breaking the magnetizing current complete with down rod levers, couplings & operating handle with pad locking arrangements manufactured as per IS 9921of rating up to 200 Amps complete all as specified and directed. Make : Pactil / MEI / Jaipuria Brothers / Southern Switchgear / HEI / BHEL / ELPRO / Atlas / Rashtriya
Supply and fix in replacement of 33000 volts grade, expulsion type drop out fuse set mounted on insulators and steel frame of current rating up to 200 Amps complete all as specified and directed by Engineer-in-Charge. Make : Pactil / MEI / Jaipuria Brothers / Southern Switchgear / HEI / BHEL / ELPRO / Atlas / Rashtriya
Supply, laying, testing & commissioning in replacement of XLPE insulated, insulation screening with extruded semi conducting compound in combination with copper tape, cores laid up, PVC inner sheath, galvanized steel strip armoured and overall PVC sheathed electric power cables(heavy duty) with stranded aluminum conductor of cross sectional area 300 sqmm, 3 core, 33000 volts grade(Earthed) cable confirming to IS 7098 complete all as specified and directed. Make: Havells / Universal / Gloster / Polycab / Finolex
M&L for Cable jointing kit for 33 KV (Earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 sqmm complete all as specified and directed by Engineer-in-Charge. Make: Raychem / Denson / 3M
Dehydration / Filtration of transformer oil of power / distribution transformer indoor/out door type of any capacity installed at various locations with mobile type centrifuge dehydration / filtration machine/plant to achieve di-electric strength of 40 KV or above for 1 minute at 2.5 mm gap as per relevant IS/IEC including testing and recording the values of dielectric strength of oil before and after filtration at site with transformer oil testing machine complete all as directed by Engineer-in-Charge. (Note: Record of Di-electric strength before and after dehydration / filtration duly signed by Contractor, JE E/M and Engineer-in-Charge shall be submitted by contractor to the department before claiming payment through RAR / FB)
Re-filling / Topping up of new transformer oil into the body / conservator tank of transformer to the desired level complete all as specified and directed by Engineer-in-Charge. Make: Power Oil / Electrol / Transol / Sero ELectra. Note: The dielectric strength of oil should not be less than 40 KV.
Isolating the defective transformer by carefully disconnecting the primary (HV), secondary (LV) and earth connections, drawing out the oil from transformer to required level and storing in cleaned containers, opening the top cover and conservator tank from transformer, identifying and rectifying the defects and re-fixing back the same duly replacing with new rubberized cork sheet gasket for transformer top cover and new GI bolts, nuts & washers of suitable size and reconnecting all primary (HV), secondary (LV) and earth connections as per the original, re-filling the transformer oil to required level and testing on completion for satisfactory performance complete all as specified and directed by Engineer-in-Charge for the following capacity of transformers:- (Note : Re-winding and replacement of HT / LT bushings shall be measured and paid separately. However, the cost of rectification of minor defects such tightening of loose connections, replacement / connecting of copper strips to bushings, provn of nuts, bots, washers etc. is deemed to be included in quoted rates.)
Power transformer 500 KVA, 33 KV / 11 KV
Power / distribution transformer 500 KVA, 33 KV / 0.433 KV
Distribution transformer 500 KVA, 11/0.433 KV
Distribution transformer 160 KVA, 11/0.433 KV
Lifting the transformer from its plinth / pole structure inside the fence area with the help of suitable crane and transporting to workshop for carrying out necessary repairs and bringing back and re-installing in its original place complete all as specified and directed by Engineer-in-Charge for the following capacity of transformers:- (Note : Repairs required shall be measured and paid separately under relevant items of BOQ)
Power transformer 500 KVA, 33 KV / 11 KV
Power / distribution transformer 500 KVA, 33 KV / 0.433 KV
Distribution transformer 500 KVA, 11/0.433 KV
Distribution transformer 160 KVA, 11/0.433 KV
Taking out complete core from transformer, cutting and removing burnt out winding [primary (HV) and secondary (LV)] and re-winding the same with super enameled copper conductor of existing gauge together with insulation materials, applying varnish, pre-heating in heating chamber, re-assembling the transformer as per the original and testing on completion complete all as specified and directed by Engineer-in-Charge for distribution transformer of capacity up to 500 KVA of any make and Power Transformer of capacity 500 KVA of any make.
Supply and fix in replacement of HV side porcelain transformer bushing with brass stud, nuts, bolts & washers including oil seal and gaskets suitable for following rating of step down transformers complete all as specified and directed by Engineer-in-Charge.
Power transformer 500 KVA, 33 KV / 11 KV
Power / distribution transformer 500 KVA, 33 KV / 0.433 KV
Distribution transformer 500 KVA, 11/0.433 KV
Distribution transformer 160 KVA, 11/0.433 KV
Supply and fix in replacement of LV side porcelain transformer bushing with brass stud, nuts, bolts & washers including oil seal and gaskets suitable for following rating of step down transformers complete all as specified and directed by Engineer-in-Charge.
Power transformer 500 KVA, 33 KV / 11 KV
Power / distribution transformer 500 KVA, 33 KV / 0.433 KV
Distribution transformer 500 KVA, 11/0.433 KV
Distribution transformer 160 KVA, 11/0.433 KV
Opening the LV side cable box and disconnecting the LT cables and Supply and fix in replacement of oil seal and gasket suitable for LV side bushing of 11KV/433V transformer of rating up to 500 KVA complete all as specified and directed by Engineer-in-Charge.
M&L for preparation of old painted surfaces of outdoor/indoor type power / distribution transformers and painting with synthetic enamel paint of approved colour using spray painting machine / spay gun through out externally and writing machine number in white colour on black background complete all as specified and directed by Engineer-in-Charge for following rating of transformers:-
Power transformer 500 KVA, 33 KV / 11 KV
Power / distribution transformer 500 KVA, 33 KV / 0.433 KV
Distribution transformer 500 KVA, 11/0.433 KV
Distribution transformer 160 KVA, 11/0.433 KV
Supply and replace silica gel into the breathers of power / distribution transformers of any capacity and make complete all as specified and directed by Engineer-in-Charge.
Supply, laying, testing & commissioning in replacement of XLPE insulated, insulation screening with extruded semi conducting compound in combination with copper tape, cores laid up, PVC inner sheath, galvanized steel strip armoured and overall PVC sheathed electric power cables(heavy duty) with stranded aluminum conductor of cross sectional area 95 sqmm, 3 core, 11000 volts grade(Earthed) cable confirming to IS 7098 complete all as specified and directed. Make: Havells / Universal / Gloster / Polycab / Finolex
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95/120 sqmm complete all as specified and directed by Engineer-in-Charge. Make: Raychem / Denson / 3M
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95/120 Sqmm complete all as specified and as directed by Engineer-in-Charge. Make: Raychem / Denson / 3M
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for straight through termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120 Sqmm complete all as specified and as directed by Engineer-in-Charge. Make: Raychem / Denson / 3M
Supply and fix in replacement of Switch Air Break, gang operated, Triple pole, mechanically operated, vertical mounted on 09 insulators and steel frame, with operating mechanism worked from ground level, for current rating up to 200 amps suitable for 11000 volts grade complete all as specified and directed by Engineer-in-Charge. Make : Pactil / MEI / Jaipuria Brothers / Southern Switchgear / HEI / BHEL / ELPRO / Atlas /Rashtriya
Supply and fix in replacement of 11000 volts grade, expulsion type drop out fuse set mounted on 06 insulators and steel frame of current rating up to 50 Amps complete all as specified and directed by Engineer-in-Charge. Make : Pactil / MEI / Jaipuria Brothers / Southern Switchgear / HEI / BHEL / ELPRO / Atlas /Rashtriya
Supply and fix in replacement of Lightning arresters expulsion type complete with all fittings, distribution class of discharge capacity 10 kilo amp suitable for 11 Kilo Volts complete all as specified and directed by Engineer-in-Charge. Make : Oblum /Atlas / BHEL / Rashtriya / Elpro / Crompton Greaves / Jaipuria / Rashtriya
Supply and fix in replacement of Pin type, porcelain, vitreous, brown insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 150mm height, 150mm dia for 11000 volts grade complete all as specified and directed by Engineer-in-Charge. Make: BHEL/ Bengal Potteries/ Jayshree/ Pactil / WS Insulators/ Jaipuria/ Southern Insulators/ MEI/ Modern Insulators / Rashtriya
Supply and fix in replacement of Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, brown, single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts complete all as specified and directed by Engineer-in-Charge. Make: BHEL/ Bengal Potteries/ Jayshree/ Pactil / WS Insulators/ Jaipuria/ Southern Insulators/ MEI/ Modern Insulators / Rashtriya
Supply and fix in replacement of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as specified and directed by Engineer-in-Charge.
Supply and erection in replacement of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.0 meters long) including painting of poles with two coats of aluminium paint over a coat of red oxide primer on all exposed surfaces and black bituminous paint on embedded portion and Zebra marking on pole with black paint up to one meter height above PCC coping including pasting of radium reflector band / strips (Make: 3M or equivalent) of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from coping of pole and writing the pole number in black colour on yellow background at a suitable place on the pole complete all as specified and directed by Engineer-in-Charge. (Note: Excavation and concrete shall be measured and paid separately under relevant items of this BOQ). Make : India Electric Poles / Bombay Tubes / National Tubing Company / Bharat Conduit and Steel / Kalinga Tubes /Quality Steel Products
All as per item No. 29.00 here-in-before but of size 410 SP-31 (9.00 metres long).
M&L for PCC 1:3:6 type C2 using 40mm graded stone aggregate as in foundations of pole/ stay assembly complete all as specified and directed by Engineer-in-Charge.
M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate as in coping of pole including necessary form work complete all as specified and directed by Engineer-in-Charge.
M&L for pruning of tree branches up to 2.0 meter clearance all around HT/LT overhead lines and depositing where directed at a distance not less than 50m complete all as specified directed by Engineer-in-Charge. Note: The item will be measured in span length between poles. The approx span length is 50m.
Unbinding the existing HT/LT overhead lines of any configuration and size of conductor by opening the binding wire from insulators and Re-stringing to the required tension and sag and binding with new aluminium binding wire of suitable gauge complete all as directed by Engineer-in-Charge.
Supply and fix replacement of Shackle Type, Porcelain, vitreous, white, brown or green insulator including galvanized mild steel straps, washers, insulator bolts, washers and nuts for working pressure 1100 volts of size 75mm height and 90mm dia complete all as specified and directed by Engineer-in-Charge. Make: BHEL/ Bengal Potteries/ Jayshree/ Pactil / WS Insulators/ Jaipuria/ Southern Insulators/ MEI/ Modern Insulators / Rashtriya
Supply and fix replacement of Pin type, porcelain, vitreous, white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 100mm height, 65mm dia for 1100 volts grade complete all as specified and directed by Engineer-in-Charge. Make: BHEL/ Bengal Potteries/ Jayshree/ Pactil / WS Insulators/ Jaipuria/ Southern Insulators/ MEI/ Modern Insulators / Rashtriya
Supply and fix in replacement of ACSR conductor for HT/LT overhead line and proper stringing to required tension and sag including binding with new aluminium binding wire of suitable size complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of Stay assembly with 16mm dia stay rod and all accessories as shown in electrical plate No. 1 complete all as specified and directed by Engineer-in-Charge. Note: Loop type insulator, stay clamps, stay wire, excavation and concrete measured separately)
Supply and fix in replacement of Galvanized stay strand, 7/3.15mm including proper tightening to required tension complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of Loop type insulator, vitreous porcelain, white, brown or green Small size, with overall dimensions 65 x 90mm, clearance of hole 16mm complete all as specified and directed by Engineer-in-Charge.
Supply, Installation, connecting, testing and commissioning of 30 Volts Battery Backup Bank comprising of 15 Nos of 2 Volts, 40 AH batteries duly initial filling and charging including necessary inter battery connectors with suitable copper conductor cable, connecting hardware etc along with suitable 30 Volt battery charger unit for working on 230 Volts, 50 Hz, AC input power supply complete all as specified and directed by Engineer-in-Charge. Make: Exide/ Amaron / Okaya / Luminous
Servicing and overhauling of 11 KV Vacuum Circuit Breaker of any rating and any make by carefully drawing out the breaker from panel, degreasing and cleaning all moving parts, checking the condition of vacuum interrupters, male & female contacts, flexible connection, spring charging motor, gear assembly, tripping coil, timer, control wiring, operations of breaker both electrically and mechanically, inspecting all bolts, nuts, pins and collar pins etc and replacing the defective parts if any, applying grease to all moving parts, gears and trolley and petroleum jelly to male & female contacts and re-assembling, refixing and testing for smooth functioning of breaker complete all as specified and directed by Engineer-in-Charge. Note: The spare parts required shall be measured and paid separately as "Supply Only" and the labour part shall deemed to be included in the quoted rate.
Supply only in replacement of Vacuum Interrupter suitable for existing make and model of 11 KV Vacuum Circuit Breaker (VCB).
Supply only in replacement of female contact suitable for existing make and model of 11 KV Vacuum Circuit Breaker (VCB).
Supply only in replacement of flexible copper strip connection suitable for existing make and model of 11 KV Vacuum Circuit Breaker (VCB).
Supply only in replacement of spring charging motor suitable for existing make and model of 11 KV Vacuum Circuit Breaker (VCB).
Supply only in replacement of gear assembly (big & small both) suitable for existing make and model of 11 KV Vacuum Circuit Breaker (VCB).
Supply only in replacement of tripping coil suitable for existing make and model of 11 KV Vacuum Circuit Breaker (VCB) for 24 V DC control voltage.
Supply only in replacement of auxiliary switch suitable for existing make and model of 11 KV Vacuum Circuit Breaker (VCB) for 24 V DC control voltage.
Supply only in replacement of timer suitable for existing make and model of 11 KV Vacuum Circuit Breaker (VCB) for 24 V DC control voltage.
Supply only in replacement of push to trip / push to close buttons with spring suitable for existing make and model of 11 KV Vacuum Circuit Breaker (VCB) for 24 V DC control voltage.
Supply only in replacement of T-N-C switch suitable for existing make and model of 11 KV Vacuum Circuit Breaker (VCB).
Supply only in replacement of LED indication lamps of any colour as per site requirement suitable 11 KV Vacuum Circuit Breaker (VCB) Panel.
M&L for earthing complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 50mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion including taking out of unserviceable earthing set complete all as specified and directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II
Material & Labour for Power Cables, Aluminum Stranded Conductor 185 sqmm, 3.5 core, XLPE Insulated, Cores laid up, PVC Inner sheathed, Armoured with galvanized wire or galvanized steel strip, overall PVC Sheathed, 1100V Grade as per IS 7098(Part 1) 1988 complete laid in trenches / floors / fixed to poles / walls / drawn through pipes etc including provn of lugs, glands, nuts, bolts & washers etc for connecting in LT feeder pillar box / transformer bushings / connecting overhead lines with suitable binding wire and testing on completion including taking down existing unserviceable cable of any description complete all as specified and directed by Engineer-in-Charge. Make: Finolex / Havells / Polycab / Universal / Gloster / KEI. (Note: Excavation, earth work and provn of cable covers / protection pipe etc shall be measured and paid separately under relevant items of BOQ.)
All as per item No. 55.00 here-in-before but of size 120 sqmm, 3.5 core.
All as per item No. 55.00 here-in-before but of size 95 sqmm, 3.5 core.
All as per item No. 55.00 here-in-before but of size 50 sqmm, 3.5 core.
All as per item No. 55.00 here-in-before but of size 25 sqmm, 4 core.
All as per item No. 55.00 here-in-before but of size 16 sqmm, 4 core.
All as per item No. 55.00 here-in-before but of size 10 sqmm, 2 core.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting in hard / dense soil for laying of cables complete all as specified and directed by Engineer-in-Charge.
All as per item No. 62.00 above but exc 1.5m depth and n.exc 3.0m
Supply and spread M-sand in trenches for cushioning of cable complete all as specified and directed by Engineer-in-Charge. (Note: Punned down thickness only shall be measured for the purpose of payment)
Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed by Engineer-in-Charge.
Removing surplus excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by Engineer-in-Charge.
Supplying and laying in replacement of un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm for cable protection in trenches complete all as specified and directed by Engineer-in-Charge.
Supply and lay in trenches, un-reinforced precast concrete cable cover, Class LV, Type I, flat, size 250 mm x 150mm x 40mm for cable protection in trenches complete all as specified and directed by Engineer-in-Charge.
Material & Labour for cutting of existing road / hard standing up to 15 cm depth for laying of pipe lines / cables and making good the disturbed surfaces by providing PCC 1:2:4 type B-1 (using 20mm graded aggregate) after laying of pipes lines and returning filling of soil, complete all as specified and directed. Note:- Excavation and earth work below hard standing will be measured and paid under relevant items.
Supply and fix in replacement of 150mm dia bore tubes, 'light grade' galvanized, with all fitting and fixed complete to walls/ poles or laid in trenches/ floors for cable protection complete all as specified and directed by Engineer-in-Charge. Make : Jindal / Tata / Zenith / Prakash Surya / Swasthik
All as per item No. 70.00 here-in-before but of size 100mm dia bore.
All as per item No. 70.00 here-in-before but of size 80mm dia bore.
All as per item No. 70.00 here-in-before but of size 50mm dia bore.
Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts complete all as specified and directed by Engineer-in-Charge. Make: Finolex / Kisan / Prince / Tirupati /Supreme / Jain Irrigation Sys
Design, fabricate, supply, installation, testing and commissioning of outdoor type dust proof & vermin proof cubicle panel board compartmentalized with separate bus and cable alley chambers suitable for 3 phase, 4 wire, 415 Volts, 50 Hz, AC supply system as per latest IS / IEC standards & regulations, factory fabricated in an approved factory (Manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad-locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02 Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1500mm x 1500mm x 800mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexible cables and lugs of suitable grade/capacity complete all as specified and directed including taking down existing unserviceable LT panel of any description:- Note: (i) The Contractor shall submit set of all drawings of the L.T. Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing. However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations. Make of Panel builder: Universal Switchgear Control, New Delhi / United Engineering Services, Kanpur / Mclayers, Bhopal / BAFNA Electric Panel / SaB Engineers & Consultants, Kanpur
Supply and connect in replacement of PVC insulated and PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volts grade, conforming to IS 694, three core, 1.5 sqmm for connecting from junction box to street light fitting including taking down existing unserviceable cable of any description complete all as specified and directed by Engineer-in-Charge. Make: Finolex / Havells / Polycab / Universal / Gloster / KEI
Supply and fix in replacement of MCCB, 250 A, 4 Pole, 36 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. Make : L&T / Havells / C&S / Indo Asian
Supply and fix in replacement of MCCB, 200 A, 4 Pole, 36 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. Make : L&T / Havells / C&S / Indo Asian
Supply and fix in replacement of MCCB, 160 A, 3 Pole, 25 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal magnetic release along with busbar spreader terminal plates including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. Make : L&T / Havells / C&S / Indo Asian
Supply and erection of Hot dip galvanized tapered octagonal pole of height 7.0 meters in single or double section having top dia 70mm and bottom dia 130mm made up of 3mm thick sheet and welded with a base plate of size 200mm x 200mm x 12mm thick and provided with 1000mm long single arm bracket with 15 degree of angle for mounting street light fitting complete with provision of 04 Nos of ‘J’ type foundation bolts of size not less than 20mm dia, 600mm long embedded in PCC foundation concrete as per manufacturer’s recommendation including necessary earth work, RFR etc complete. A door should be provided at a height of 500mm from the base plate for accommodating and including provision of TPN aluminium bus bar system suitable for connecting up to 2 core, 16 sqmm aluminium cable and 01 No. of 6A SP MCB for street light protection inside the pole shaft including provision of 3 core, 1.50 sqmm PVC insulated PVC sheathed copper conductor cable 1100 volts grade conforming to IS:694 from pole junction box to street light fitting drawn through inside of pole . Radium reflector band / strips of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from base plate. Numbering of pole shall be done in black colour on yellow background at suitable place on the pole including taking down of existing broken / corroded pole any description complete all as directed by Engineer-in-Charge. Note: (i) Excavation, Earth Work, RFR etc and RCC shallow foundation as per manufacturer's design shall deemed to be included in quoted rate and nothing extra shall be paid on this account. (ii) Complete detailed drawing of pole and its foundation drawing as per manufacturer's recommendations shall be submitted and got approved from GE before procurement. Make : Bajaj / Philips / Utkarsh
Supply and fix in replacement of MCCB 100A, 16KA, 4 Pole with fixed thermal magnetic release mounted in MCCB sheet steel enclosure including taking down existing unserviceable MCCB of any description complete all as specified and directed by Engineer-in-Charge. Make : C&S / Indo Asian / L&T / Havells
Design, Fabricate, supply, installation and testing of outdoor type cubicle panel board bus bar box with MCCB suitable for 3 phase 4 wire, 50 Hz supply system factory fabricated made out of CRCA sheet steel of 3mm thick for outer shell and 2mm thick for inner shell with front openable door with locking arrangement complete with powder coat painting and suitable packing material for IP-54 degree of protection and including provision of 40mmx40mmx5mm angle iron base frame of suitable size for mounting the panel board at a height of 450mm above GL and grouted in PCC foundation. The size of panel board shall not be less than 500mm x 500mm x 300mm (outer dimensions) for accommodating and including provision of following switchgears complete:- Make of Panel builder: Universal Switchgear Control, New Delhi / United Engineering Services, Kanpur / Mclayers, Bhopal / BAFNA Electric Panel / SaB Engineers & Consultants, Kanpur (i) TPN Aluminium bus bar of 40 x 5 mm provided with heat shrinkable coloured PVC sleeve insulation mounted on insulators suitable for connecting 2 or 3 outgoing cables including provision suitable glands. (ii) MCCB, 100 A, 4 Pole, 25 KA (Ics=100%Icu), 415 V, 50 Hz, with adjustable thermal - magnetic release - 01 No (Make : L&T / Havells / C&S / Indo Asian)
Taking down the defective LED Flood light fitting/ / street light fitting/ security light fitting of various wattage from 70 Watts to 200 Watts from 9m/11m pole /Building walls etc from any position / height and identifying the fault and replacing the defective LED driver/ replacing the burnt wiring and re-assembling the fittings and re-fixing in its original position and testing for proper functioning complete all as directed by Engineer-in-Charge. Note: Supply only of LED driver and Supply and replacement of cable shall be measured and paid separately under relevant items of BOQ.
Supply only of LED driver as per sample suitable for existing make & model of 150 Watt LED flood light fitting. Make : Pyrotech / Surya / Halonix / Havells / Bajaj / Wipro
Supply only of LED driver as per sample suitable for existing make & model of 120 Watt LED street light fitting. Make : Pyrotech / Surya / Halonix / Havells / Bajaj / Wipro
Supply only of LED driver as per sample suitable for existing make & model of 90 Watt LED street light fitting. Make : Pyrotech / Surya / Halonix / Havells / Bajaj / Wipro
Supply only of LED driver as per sample suitable for existing make & model of 70 Watt LED street light fitting. Make : Pyrotech / Surya / Halonix / Havells / Bajaj / Wipro
Material and labour for overhauling of existing 16 meters height high mast lighting system by degreasing and cleaning of double drum winch, gear box, wire rope, clamp, bobbin arrangement, power tool motor, mechanical torque limiter, lowering the mast head assembly, degreasing and cleaning the pulley, docking arm etc and applying new grease / lubricating oil for all mechanical moving / rotating parts, checking all the electrical parts such as timer panel, all cable connections in control panel, motor, junction box, flood light fittings & aviation obstruction light fitting etc, rectifying the defects, renewing the defective components etc including testing for proper functioning complete all as specified and directed by Engineer-in-Charge. Note: Replacement of flood light fittings, aviation obstruction light, control cable, steel wire rope , timer panel components & rewinding of motor if required at site shall be measured and paid separately. However, the cost of minor spare parts & lubrication is deemed to be included in the quoted rate.
Supply and fix in replacement of 150 Watt LED flood light fitting made up of Pressure die-cast aluminium alloy housing with toughened glass, IP65 protection and impact resistance of IK07 and individual high power LEDs with secondary optics having system lumen efficacy ≥100 lm/W, Inbuilt potted electronic LED driver with APFC (SMPS based constant current supply), lower THD, Open Circuit protection, Over Voltage protection, Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec 13 and BIS complying including surface mounting using adjustable MS cradle of thickness 5 mm provided with the fixture including taking down existing unserviceable flood light fitting of any description complete all as specified and directed by Engineer-in-Charge. Make: Havells / Philips / Wipro / Bajaj
Supply and fix in replacement of Integral LED aviation light fitting comprising of aluminium housing with polycarbonate enclosure including taking down existing unserviceable aviation light of any description complete all as specified and directed by Engineer-in-Charge. Make : Havells / Philips / Wipro / Bajaj
Supply and connecting in replacement of PVC insulated and PVC Round Sheathed, Copper Conductor (flexible) industrial cable 5 core x 4 sqmm, 1100 Volt, conforming to IS 694 including taking down of existing unserviceable copper control cable of any description complete all as specified and directed by Engineer-in-Charge. Make: Havells / Polycab / Finolex / KEI / Gloster / Universal
Supply and fixing in replacement of round strand galvanized steel wire rope conforming to IS:2266/02 of size 8mm dia, 6/36 SW construction including taking down existing unserviceable wire rope of any description complete all as specified and directed.
Supply and fixing in replacement of analog time switch, 3 module size suitable for automatic switching ON & OFF of street lights through 3 pole power contactor including taking down existing unserviceable time switch of any description complete all as specified and directed by Engineer-in-Charge. Make: L&T / C&S / Havells
Supply and fix in replacement of reversing starter with Forward, OFF and Reverse switch 25A suitable for three phase power tool motor of high mast lighting system including taking down existing unserviceable reversing starter of any description complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of three pole AC power contactor, 32 Amps, 415 volts suitable for street light timer panel including taking down existing unserviceable power contactor of any description complete all as specified and directed by Engineer-in-Charge. Make: L&T / Havells / C&S / BCH
Supply and fix in replacement MCB, TPN, 40 Amps, 10 KA, 415 V, 50 Hz, AC including taking down existing unserviceable MCB of any description complete all as specified and directed by Engineer-in-Charge. Make: Havells / C&S / L&T
Supply and fix in replacement Auto/ Manual with centre off switch suitable for street light timer panel including taking down existing auto / manual switch of any description complete all as specified and directed by Engineer-in-Charge.
Cutting and removing of burnt out winding from electric motor of any make and rewinding with super enameled copper winding wire of existing gauge and number of turns including varnishing, heating etc and testing for satisfactory performance for capacity up to 3.0 HP, 3 Ph, 415 Volts, 50Hz, AC motor complete all as directed by Engineer-in-Charge.
Supply, fixing, installation & testing of All-in-one integrated solar street light with built in 15 Watt LED light, Mono Crystalline SPV Panel, Lithium Ferro Phosphate (LiFeP04) battery, MPPT charge Controller and PIR sensor with colour temperature 6000-6500K including taking down existing unserviceable solar street light fitting of any description complete all as specified and directed by Engineer-in-Charge. Make: Havells / Philips / Wipro / Bajaj
Supply and fix in replacement of 100 Watt LED street light fitting made up of Pressure die-cast aluminium alloy housing with toughened glass, IP66 protection and impact resistance of IK07 and individual high power LEDs with secondary optics having system lumen efficacy ≥100 lm/W, Inbuilt potted electronic LED driver with APFC (SMPS based constant current supply), lower THD, Open Circuit protection, Over Voltage protection, Surge Voltage protection & other safety test as per IS 15885 Part-2/Sec 13 and BIS complying including taking down of existing unserviceable street light fitting of any description complete all as specified and directed by Engineer-in-Charge. Make: Havells / Philips / Wipro / Bajaj
All as per item No. 101.00 here-in-before but of 60 Watt LED street light fitting. Make: Havells / Philips / Wipro / Bajaj
All as per item No. 101.00 here-in-before but of 45 Watt LED street light fitting. Make: Havells / Philips / Wipro / Bajaj
Supply and fix in replacement of LED Post top light fitting 45 Watt / 50 Watt, made in die-cast aluminum housing with decorative clear opal acrylic diffuser, IP 65 protection, spun aluminum powder coated canopy, low power Warm White (WW) LEDs connected in series and parallel combination with better heat dissipation arrangement with LED color temperature- 3000K ±300K, Highly efficient constant current electronic driver having operating voltage range from 140-280 Volt AC, provided with high voltage, open and short circuit protection, Voltage surge protection 5KV complete suitable for up to 60mm OD pipe entry with fixing bolts including taking down existing unserviceable post top light of any description complete all as specified and directed by Engineer-in-Charge. Make: Havells / Philips / Wipro / Bajaj
Supply and fix in replacement of GI pipe bracket made out of 40mm dia medium grade GI pipe of 1.50mtr long bent to required shape and fixed to steel tubular / PCC pole with clamps made out of 40mm x 5 mm MS flat fixed with suitable nuts, bolts and washers etc including taking down existing unserviceable bracket of any description complete all as specified and directed by Engineer-in-Charge.
Supply and connect in replacement of PVC insulated and PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volts grade, conforming to IS 694, three core, 2.5 sqmm for connecting from junction box to street light fitting complete all as specified and directed by Engineer-in-Charge. Make: Finolex / Havells / Polycab / RPG / KEI / Universal / Gloster
Supply and connect in replacement of PVC insulated and PVC sheathed aluminium conductor, unarmoured cable 4 sqmm, 3 core, 1100V grade complete connecting on overhead line and street light fitting as per site requirement and testing on completion. Make: Finolex / Havells / Polycab / RPG / KEI / Universal / Gloster
Material and labour for preparation of old painted surfaces of HT / LT steel poles and painting with one coat of aluminium paint on all steel surfaces such as poles, channels, angles, clamps, nuts, bolts and washers of any description and Zebra marking on pole with black paint up to one meter height above PCC coping including pasting of radium reflector band / strips (Make: 3M or equivalent) of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from coping of pole and writing the pole number in black colour on yellow background at a suitable place on the pole including applying one coat of snow cem on PCC coping of pole complete all as specified and directed by Engineer-in-Charge.
Material and labour for Chemical Earthing complete with copper earth plate electrode of size 900mm x 600mm x 5 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to copper earth strip of size 50mm x 6mm as earthing lead by means of copper bolts, nuts, check nuts and washers and earth strip protected by 80mm dia GI pipe medium grade and connected to power transformer / HT panels /earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II
Material and labour for earthing complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI wire 4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 15mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed. Note :- The unit rate quoted shall also include for excavation, earth work in any type of soil, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix type B1 cover reinforced with 8mm dia TMT bras @ 150mm C/C both ways, GI funnel with watering pipe, wire mesh, protection pipe, earth strip up to 7.50m long complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub heading earthing, specified in SSR Part II
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required with 6mm dia galvanized iron wire complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of Post top lantern Black ABS plastic spigot, spun aluminium canopy, with clear acrylic diffuser and accessories along with LED lamp 9 Watt with B22 base lamp holder including taking down existing unserviceable post top lantern fitting of any description complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of thermoplastic cable junction boxes of size 130 x 130 x 77, IP 65/66 with metric knockouts for cable entry including cable terminal connector and fixing on posts / poles with suitable clamps, nuts & bolts etc complete all as specified and directed by Engineer-in-Charge. Make : Hensel / Sintex / Gewiss
Cleaning the internal portion of RCC overhead reservoir of capacity 1,00,000 Liters having staging height up to 20 meters by applying wire brush on walls and bottom of tank and removing the silt/sand/ fungus etc deposited inside the tank by opening wash out valve, followed by cleaning with bleaching water solution and fresh water and finally applying one coat of white wash on internal surfaces including writing the date of cleaning and due date of cleaning in white colour on black background on external wall complete all as directed.
Cleaning the internal portion of RCC underground / semi underground sump of capacity 50,000 Liters by applying wire brush on walls and bottom of tank and removing the silt/sand/ fungus etc deposited inside the sump with buckets and depositing where directed, followed by cleaning with bleaching water solution and fresh water and finally applying one coat of white wash on internal surfaces including writing the date of cleaning and due date of cleaning in white colour on black background on external wall complete all as directed.
Supply and fix in replacement of PVC Insulated and PVC Sheathed Industrial 3 Core Flat Submersible Cable with Bare Bunched Copper Conductor 6.0 sqmm for Submersible Pump Motors with Voltage Grade 1100 Volts as per IS:694/2010 including taking out of existing unserviceable submersible cable of any description complete all as specified and directed. Make : Havells / Polycab / Universal / Gloster / Finolex / L&T / KEI
Taking up or down steel tubing and connections, including cleaning for refixing or taking credit complete all as directed for the following pipe sizes:-
15mm dia size
20mm dia size
25mm dia size
40mm dia size
50mm dia size
80mm dia size
100mm dia size
Material and labour for GI water tubing, medium grade, ISI marked, with and including all fittings such as bend, tee, elbow, reducer, union, nipple etc as per site requirement laid in trenches, complete as specified and directed for the following pipe sizes:- Make : Tata / Jindal / Prakash Surya / Zenith / Swastik Note : (i) The excavation & earthwork shall be measured & paid for separately. (ii) The cost of all type of GI fittings such as bend, tee, elbow, reducer, union, nipple etc is deemed to be included in quoted rates.
25mm dia size
40mm dia size
50mm dia size
80mm dia size
100mm dia size
Material and labour for GI water tubing, medium grade, ISI marked, with and including all fittings such as bend, tee, elbow, reducer, union, nipple etc, fixed to wall / ceiling, complete as specified and directed for the following pipe sizes:- Make : Tata / Jindal / Prakash Surya / Zenith / Swastik Note : The cost of all type of GI fittings such as bend, tee, elbow, reducer, union, nipple etc is deemed to be included in quoted rates.
15mm dia size
20mm dia size
25mm dia size
Supply and fixing of MS clamp made out of 75mm x 5mm flat with 20mm dia hole for taking branch connection with and including fixing of 25mm dia GI socket duly welded complete including fixing of clamp on existing GI pipe line of size 80mm/100mm dia with suitable rubber gasket packing to ensure leak proof joint and suitable nuts, bolts and washers etc complete all as specified and directed by Engr-in-charge.
M&L for in replacement of Straight plain brass ferrules screwed both ends for taking of branch connection of 20mm bore from CI/DI main pipe line and fixed complete all as specified and directed.
Cutting existing steel tubing of size 40 or 50mm dia and Screwing for alterations or additions (or lengthening screw on pipe to form connector) done in position without taking down complete all as specified and directed.
S&F Gun-metal gate valves, with iron wheel head, screwed both ends for iron pipe including taking down existing unserviceable gate valve of any description complete all as directed for the following sizes:- Make : Leader / Zoloto / Gem / Seiko/ Sant
50mm dia NB
40mm dia NB
25mm dia NB
20mm dia NB
15mm dia NB
Construction of Valve Chamber of Size 1000mm X 1000mm X 1200mm (Inner Dimension) with 150 mm thick PCC foundation 1:4:8 type D2, brick wall 230 mm thick built in CM 1:4, 10 mm thick internal plaster in CM 1:4, MS Sheet Cover 3mm thick including 50x50x5mm MS Angle iron frame fixed in 50mm thick PCC Coping of 1:2:4 type B1 with locking arrangement and the steel surfaces shall be painted with one coat of red oxide primer and two coats of synthetic enamel black paint and the valve chamber shall be painted with two coats of cement base paint complete including necessary excavation in any type of strata and removal of surplus soil etc complete all as specified and directed. Note : (i) Bottom PCC floor of the pit should be minimum 30 cms below the bottom surface of sluice valve flange to provide sufficient working space. (ii) The sluice valve should positioned in center of the pit.
M&L for Run lead joints to cast iron spigot and socket pipe (water main) and fittings including burning and taking out of old lead joint for 80 mm bore pipe complete all as specified and directed. Note : Excavation and Earth work will be measured and paid separately under respective items.
All as per srl item No 126.00 here-in-before but suitable for 100 mm bore pipe.
Supply and fix in replacement of Cast Iron sluice valve of size 150mm dia bore, having pressure rating PN 1.0, double flanged, non-rising stainless steel spindle with iron wheel conforming to IS:14846-2000 with jointing material i.e. new rubber gasket, nuts & bolts, washer etc of suitable size including taking down existing old unserviceable sluice valve complete all as specified and directed. Make: Venus / BIR / Kalpana Note : Material will be accepted and allowed to incorporate in the work only after production of proper purchase voucher from authorized dealer and test certificate from the manufacturer.
All as per item No. 128.00 here-in-before but of size 100mm dia bore
All as per item No. 128.00 here-in-before but of size 80mm dia bore
Overhauling of pump set of any make by opening the pump and motor, replacing the worn out/defective spare parts, making good of shaft and shaft sleeve, cleaning internally, lubricating the rotating parts, reassembling the pump and motor duly replacing the all the packing material, worn out bolts, nuts, washers etc and testing for satisfactory performance complete all as directed for the submersible pump set of capacity up to 12.5 HP. Note: (i) Quoted rate shall deemed to be inclusive of necessary packing material, nuts, bolts & washers etc. (ii) Spare parts replaced shall be measured and paid separately under relevant items of Sch 'A' as supply only.
Disconnecting the electric cable and water mains, lifting the submersible pump set of capacity up to 12.5 HP along with column pipe and submersible cable from bore well having depth up to 150 meters for carrying out repairs / rewinding / replacement of defective submersible cable / replacement of rusted column pipe / flushing of bore well etc and re-installing and reconnecting the water mains and electric connections and testing for satisfactory performance complete all as directed. Note: Repairs, rewinding, submersible cable, flushing of bore well, shifting of submersible pump to civil work shop etc shall be measured and paid separately under relevant items of Sch 'A'.
Shifting of pump set with motor of any type and any capacity from any pump house / open well / bore well to civil workshop for repair / rewinding and bringing back with suitable mode of transport complete all as directed.
Cutting and removing burnt out winding from submersible electric motor of any make of capacity up to 12.5 HP and rewinding with water proof poly wrapped copper winding wires of existing gauge and number of turns and testing for satisfactory performance complete all as directed by Engineer-in-Charge.
Supply only the following spare parts suitable for submersible / open well submersible pump sets and motors :-
Ball bearing suitable for up to 12.5 HP pump set
Impeller suitable for submersible pump up to 12.5 HP
Strainer suitable for submersible pump up to 12.5 HP
Coupling assembly suitable for submersible pump up to 12.5 HP
Sand guard suitable for submersible motor up to 12.5 HP
Oil seal suitable for submersible motor up to 12.5 HP
Thrust bearing suitable for submersible motor up to 12.5 HP
Taking out carefully the existing submersible pump set of any capacity / type from the bore hole up to 150 meter depth and 8" dia along with Column pipes and Elect cable from the bore well by disconnecting all in-coming and out going water and elect connections of approx depth 150 meter, flushing out the bore hole by using high pressure compressor air / back washing for a period of 2 hours or up to the time all sludge is flushed out till clear water is obtained, conducting yield test and Re - installation of submersible pumps sets along with column pipe with fittings and Elect cables etc in the bore well all as directed by Engineer in Charge. (Note : 1. The quoted rates shall be deemed to include the cost of any machinery / materials / man powers required for the complete flushing out of bore well. 2. The contractor must cater for all safety arrangement i. e. safety belts/ helmet / safety harness, shoes etc for working man power and inspecting staff and no extra cost will be paid in this effect.
M/S SANTOSH CONSTRUCTION CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .