GE NORTH PUNE
Garrison Engineer North General Cariappa Marg Camp Pune 411001
GE(N)P/T- 48OF21-22REP MAINTOF EXISTLT PANELDIST SYS LT UG CABLECONTRS AND CONN ITEMS IN SCSR GHORPADI VISHWAMITRA VICT NEHRU DMSA GOLF STP RSI APS SENIORWING 64 EME SLU POPE RDSAG SS SLMASBH MAPOFFICE COM EXTELECT OTHER ALLIEDOFAGEE/M(N)OFGE(N)PUNE
2021_MES_481716_2
GE (N) P/TOKEN- 48 OF 2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
GE NORTH PUNE
Refer tender documents.
8 documents required · 8 mandatory
₹500
GE NORTH PUNE
₹88,000
Yes
1 Feb 2022
6 Jan 2022
26 Jan 2022
6 Jan 2022
24 Jan 2022
11 Jan 2022
Amount
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI Approved, double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (100 x 10 mm ) 1000 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (NCC Line Ghorpadi)
Incoming
(a) ACB, 4 Pole, 415 Volts, 630 Amp, Manual Drawout type with microprocessor release with adjustable type with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (100 x 10 mm ) 1000 Amps Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 250 Amp, adjustable type Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos
(b) MCCB 3 pole, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 04 Nos
(c) MCCB 3 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu- 04 Nos
(d) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double CPRI Approved door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (50 x 10 mm ) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Ghorpadi Pump house No. 01)
Incoming
(a) MCCB, 4 Pole, 415 Volts, 250 Amp, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (50 x 10 mm) 500 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 100 Amp,adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos
(b) MCCB 3 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 04 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cables connections LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Glands, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI Approved double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar(60 x 10 mm ) 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Ghorpadi Pump house No. 02).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 400 Amp, adjustable type Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (60 x 10 mm ) 600 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 250 Amp, adjustable type Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos
(b) MCCB 3 pole, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos
(c) MCCB 3 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 04 Nos
(d)MCB DP 32 Amps - 02 Nos
(e) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI Approved double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 60 x 05 mm ) 300 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Near bldg No T7 Ghorpadi )
Incoming
(a) MCCB, 4 Pole, 415 Volts, 200 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar ( 60 x 05 mm) 300 Amp TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos
(e) MCB DP 32 Amps - 02 Nos
(b) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel CPRI Approved double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Bldg NP-09 Ghorpadi)
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar ( 50 x 10 mm) 500 Amps, TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3 pole, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 04 Nos
(b) MCB TP 63 Amp, 16 KA, 415 V AC - 02 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Bldg No. 148 Ghorpadi)
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu -02 No
(b) Alum bus bar ( 50 x 10 mm) 500 Amps, TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 04 Nos
(b) MCB TP 63 Amp, 16 KA, 415 V AC - 03 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Bldg No. E2 Ghorpadi).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 320 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu -02 No
(b) Alum bus bar ( 50 x 10 mm) 500 Amps, TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu- 05 Nos
(b) MCB TP 40 Amp, 16 KA, 415 V AC - 02 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (60 x 10 mm) 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Bldg No. 157 Ghorpadi).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 400 Amp, adjustable type Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (60 x 10 mm ) 600 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 250 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 01 Nos
(b) MCCB 3P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 04 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Bldg No.133 Ghorpadi).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 250 Amp, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (50 x 10 mm) 500 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 100 Amp, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 02 Nos
(b) MCB TPN 63 Amp, 16 KA, 415 V AC - 04 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 60 x 10 mm) 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Sub Station no. 01 Ghorpadi).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 400 Amp, adjustable type Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (60 x 10 mm ) 600 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 08 Nos
(b) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar (120 x 10 mm) 1200 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Ghorpadi Sub station No.01).
Incoming
(a) ACB, 4 Pole, 415 Volts, 800 Amp, Manual Drawout type with microprocessor release with adjustable type with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (120 x 10 mm ) 1200 Amps Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 160 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 03 Nos
(b) MCCB 3P, 250 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos
(c) MCCB 3P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 07 Nos
(d) MCB DP 40 Amp, 16 KA, 415 V AC - 02 Nos
(e) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 100 x 10 mm) 1000 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Ghorpadi Sub Station No. 03 & Vishwamitra Marg) .
Incoming
(a) ACB, 4 Pole, 415 Volts, 630 Amp, Manual Drawout type with microprocessor release with adjustable type with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (100 x 10 mm ) 1000 Amps Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 250 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 02 Nos
(b) MCCB 3P, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 03 Nos
(c) MCCB 3P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 04 Nos
(d) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 80 x 05 mm) 400 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Vishwamitra Marg).
Incoming
(a) ACB, 4 Pole, 415 Volts, 1400 Amp, with Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar ( 80 x 05 mm) 400 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 63 Amp, Rotary Handle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 16 Nos
(b) Provision for space to be kept blank for fixing of MCCB - 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Supply, fixing, testing and commissioning in replacement of LT feeder pillar panel single door floor mounted outdoor type, as per IP-65 grade, made out of MS sheet 3.00 mm thick of size 540x525x200mm with aluminium bus bar 250 Amps, 4 strip (3 phase) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking with 150 Amps 16 KA MCCB four pole for incomer cable, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands etc and providing fixing arrangements including earthing lead fixing arrangement, complete all as specified and directed. Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted.
Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 240 Sq mm. complete all as specified and as directed. Note : Provision of suitable double crimpped lugs and glands deemed to be included in quoted rates.
-ditto- all as per item No 14 here in above but 3.5 core 120 sqmm
-ditto- all as per item No 14 here in above but 3.5 core 95 sqmm
-ditto- all as per item No 14 here in above but 3.5 core 70 sqmm
-ditto- all as per item No 14 here in above but 3.5 core 50 sqmm
-ditto- all as per item No 14 here in above but 4 core 25 sqmm
-ditto- all as per item No 14 here in above but 4 core 16 sqmm
Supply & Fix in repairs Mild steel plates, chequered, 5mm thick or over in thickness in available sizes of Fe 410-W (Gde-E-250) quality-A for covering cable trenches complete all as specified and as directed.
M&L for painting of steel tubular pole including cable protection pipe and all iron parts of 9/11 mtr long pole complete with 2 coats of aluminium paint after cleaning all rust and dust and preparing surface with wire brush and including strips of white and red colour of synthetic enamel paint up to the height of 1.5 mtr from the bottm of the pole complete all as specified and as directed. Make : Nerolac/Asian paint
Supply and lay in trenches /under roads/ crossing or fixed to wall/ pole, GI tubing light grade of size 40mm bore for protection of UG cables complete all as specified and as directed.
All as per Item No. 23 above but 80 mm
Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified and as directed.
Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed.
Supply and laying 40mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 50mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 63mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 77mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
S&F MCCB 400 A ,4 pole ,36 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge (incoming).
S&F MCCB320 A ,3 pole ,36 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
S&F MCCB 250 A ,3 pole ,36 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
S&F MCCB 200 A ,3 pole ,36 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
S&F MCCB 100 A ,3 pole ,25 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as specified and as directed by the Engineer-in-Charge.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Vishwamithra Marg Bldg No. 198 & 200 ).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 250 Amp, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (50 x 10 mm) 500 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(b) MCCB 3P, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 04 Nos
(d) Provision for space to be kept blank for fixing of MCCB - 01 No
(e) Street light timer for controlling street light- 01 No
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 60 x 10 mm) 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Vishwamithra Marg Near Main Gate ).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 400 Amp, adjustable type Thermal Magnetic relay with breaking capacity 36 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar (60 x 10 mm ) 600 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 200 Amp, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 volts Ics=100% Icu - 03 Nos
(b) MCB TPN 63 Amp, 16 KA, 415 V AC - 02 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
(d) Automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps, 220 Volts, 50 Hz - 01 No.
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning of LT feeder pillar panel double door floor mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body of suitable size with aluminium bus bar ( 60 x 10 mm) 600 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (752 TPT Coy).
Incoming
(a) MCCB, 4 Pole, 415 Volts, 150 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu -01 No
(b) Alum bus bar ( 50 x 05 mm) 250 Amps TPN -01 Set
(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
Outgoing
(a) MCCB 3P, 100 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 01 Nos
(b) MCCB 3P, 63 Amp, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 volts Ics=100% Icu - 02 Nos
(c) Provision for space to be kept blank for fixing of MCCB - 01 No
(d) Automatic timer switch with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps, 220 Volts, 50 Hz - 01 No.
Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
Material and labour for PVC flat twin core 2.5 sq mm aluminium wire 1100 volt grade laid in 20 mm dia medium grade rigid PVC conduit (and fixing brackets on PCC pole) from Loop-in-loop out junction box to light fitting terminal complete all as specified and as directed. Note :- PVC conduit shall be clamped properly with suitable clamps and no extra payment will be done on this account.
S & F Junction Box for Street Lights of size 250 x 200 x 105 mm made out of SMC totally enclosed, dust, shock, rust and vermin proof, Rot proof and termite resistant, cable entry/out from bottom, 100 % weather proof, Locking door arrangement with gaskat, water tight IP 42 protection single leaf shutter in front having proper locking arrangements with suitable size of "connectwell" stud teriminal (provision for socket bolting)- 05 Nos suitable for 415 volts, 50 Hz, 3 phase 4 wire internal wiring system including MCB SP 06 amps- 01 No and mounted on security light pole with suitable bracket nuts, bolts including removal of exiting unsv all as specified and directed.
Dismantling cross-arms of MS channel or angle section of GOD, Lightening arresters, DO fuse etc complete all as specified and as directed.
Dismantling insulators any type, any size complete all as specified and as directed.
Dismantling earth wire complete all as specified and as directed.
Dismantling of ACSR or AAC conductors complete all as specified and as directed.
Supply and jointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 70 to 150 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Supply and jointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 240 to 300 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
Supply & Installation of Maintenance Free Earthing System consisting of a Copper bonded steel rod shall have 17.2 mm dia. & min. 10 feet length as per UL 467. The material shall have low carbon, high tensile steel molecularly bonded with 99.99% pure electrolytic grade copper thickness of minimum 250 microns with an exothermically welded Cu Busbar of (50X6X200mm) both tested by CPRI at 25 kA Fault Current carrying capacity. Copper Bonded Rod shall be UL listed. The manufacturer shall be RDSO approved to ensure the manufacturing capacity & capability along with the quality of the earthing rod. Along with a sealed bag of minimum 30 kg (10 kg Bag x 3) RoHS tested Earth Enhancement Compound tested by NABL accredited lab in compliance to IEC 62561-7 with a resistivity of less than 1.0 ohm-m. It shall be a carbon based material and shall be free from bentonite and other hazardous substances. It shall be a permanent, non-corrosive material and will not leach any chemicals into the ground. It shall retain moisture even in high soil resistivity areas. It shall lower an earth resistance value and shall offer a constant desirable performance. Including an Earth Pit cover shall be made of Poly plastic tested at 7.5 ton load for closing of earth.
Supply and fixing 415V 10KA 'B' curve miniature circuit breaker (MCB) TPN 63 Amps capacity of following poles and current carrying capacity in the DB complete with connection testing and commissioning
S&F Earth conitnuity Copper clad steel conductor or main earthing lead fixed to wall on batten or reccess or chases or burried in ground or drawn in conduit/pipe or fixed to pole or any other indicated situation for loop earthing etc as required 8 mm dia after taking down the old one any type.
Note : 1. Performance security:- Refer Condition 22 of Special Conditions. 2. Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site.
Rama Electricals
Mahindra Electric Stores
Vijay Construction and Company
T.H.ASSOCIATES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .