Supply, installation and commissioning of UPS Systems
2025_DTEDM_1153421_1
COEP Tech./EWC/UPS/2024-25/33
Open Tender
Electrical Goods/Equipment
Item Wise
30 days
Electrical Engineering Department, COEP Technologi
As per Tender document
2 documents required · 2 mandatory
₹21,240
₹1.8 L
Electrical Engineering Department, COEP Technologi
20 Mar 2025
22 Feb 2025
17 Mar 2025
22 Feb 2025
15 Mar 2025
22 Feb 2025
27 Feb 2025
UPS and Battery backup Note: Please note that each UPS and its Batteries will be evaluated togather
20 kVA without isolation transformer UPS and Battery backup Supply installation and commissioning of UPS 3phase input and 3 phase output rating 20 kVA without isolation transformer 2Level IGBT switching high frequency PWM technology,) IGBT Based rectifier and inverter with double conversion UPS System, with input voltage 320~480VL-L @ full Load & 260 – 480 @ < 50% Load and out put voltage 400 Vac +/-1% 3-Phase + N + E Unity power factor CommunicationPorts RS232,Modbus and inbuilt Ups efficiency should be Min 94% SNMP Card system to monitor operation- System With inbuilt phase sequence corrector inbuilt , Transient surge voltage surge suppressor include parallel operation up to 6 units , Ups base frame is required for proper wiring support and to avoid direct floor contact ,this system shall include Parallel kit To operate this system inparallel redundancy mode with battery temperature sensor inbuilt in the system, ups should include Emergency power off kit to shut down ups in Emergency condition , protection- IP 20
Battery backup - Battery should be provided or consider at 0.8 load pf on 100% full load 15 min backup - with Min Guranteed VAh - 9980 VAh -Battery should be SMF VRLA 12 volt - make -Exide /Quanta - battery should be use of 26 Ah Accesories - With battery rack made of metal channel to place support respective batteries for corriosion resistance asethetically pupose battery rack should be Powder coated , Dc isolator OR Suitable SFu links shuold be reuired , Ups to battery Standard DC cable should be required , battery interlinks should be at contractor scope - UPS warranty - 3 Years / Battery Warranty - 3 years
30 kVA without isolation transformer UPS and Battery backup Supply installation and commissioning of UPS 3phase input and 3 phase output rating 30 kVA without isolation transformer 2Level IGBT switching high frequency PWM technology,) IGBT Based rectifier and inverter with double conversion UPS System, with input voltage 320~480VL-L @ full Load & 260 – 480 @ < 50% Load and out put voltage 400 Vac +/-1% 3-Phase + N + E Unity power factor CommunicationPorts RS232,Modbus and inbuilt Ups efficiency should be Min 94% SNMP Card system to monitor operation- System With inbuilt phase sequence corrector inbuilt , Transient surge voltage surge suppressor include parallel operation up to 6 units , Ups base frame is required for proper wiring support and to avoid direct floor contact ,this system shall include Parallel kit To operate this system inparallel redundancy mode with battery temperature sensor inbuilt in the system, ups should include Emergency power off kit to shut down ups in Emergency condition , protection- IP 20
Battery backup - Battery should be provided or consider at 0.8 load pf on 100% full load 15 min backup - with Min Guranteed VAh - 17120 VAh -Battery should be SMF VRLA 12 volt - make -Exide /Quanta - battery should be use of 42 Ah Accesories - With battery rack made of metal channel to place supportr respective batteries for corriosion resistance asethetically pupose battery rack should be Powder coated , Dc isolator OR Suitable SFu links shuold be reuired , Ups to battery Standard DC cable should be required , battery interlinks should be at contractor scope - UPS warranty - 3 Years / Battery Warranty - 3 years
30 kVA with Inbuilt isolation transformer UPS and Battery backup Supply installation and commissioning of UPS 3phase input and 3 phase output rating 30 kVA with Inbuilt isolation transformer As per given deatail specification 2Level IGBT switching high frequency PWM technology,) IGBT Based rectifier and inverter with double conversion UPS System, with input voltage 320~480VL-L @ full Load & 260 – 480 @ < 50% Load and out put voltage 400 Vac +/-1% 3-Phase + N + E Unity power factor CommunicationPorts RS232,Modbus and inbuilt Ups efficiency should be Min 94% SNMP Card system to monitor operation- System With inbuilt phase sequence corrector inbuilt , Transient surge voltage surge suppressor include parallel operation up to 6 units , Ups base frame is required for proper wiring support and to avoid direct floor contact ,this system shall include Parallel kit To operate this system inparallel redundancy mode , ups should include Emergency power off kit to shut down ups in Emergency condition , protection- IP 20
Battery backup - Battery should be provided or consider at 0.8 load pf on 100% full load 60 min backup - with Min Guranteed VAh - 45600 VAh -Battery should be SMF VRLA 12 volt - make -Exide /Quanta - battery should be use of 100 Ah Accesories - With battery rack made of metal channel to place support respective batteries for corriosion resistance asethetically pupose battery rack should be Powder coated , Dc isolator OR Suitable SFu links shuold be reuired , Ups to battery Standard DC cable should be required , battery interlinks should be at contractor scope - UPS warranty - 3 Years / Battery Warranty - 3 years
40 kVA with Inbuilt isolation transformer UPS and Battery backup Supply installation and commissioning of UPS 3phase input and 3 phase output rating 40 kVA with Inbuilt isolation transformer As per given deatail specification 2Level IGBT switching high frequency PWM technology,) IGBT Based rectifier and inverter with double conversion UPS System, with input voltage 320~480VL-L @ full Load & 260 – 480 @ < 50% Load and out put voltage 400 Vac +/-1% 3-Phase + N + E Unity power factor CommunicationPorts RS232,Modbus and inbuilt Ups efficiency should be Min 94% SNMP Card system to monitor operation- System With inbuilt phase sequence corrector inbuilt , Transient surge voltage surge suppressor include parallel operation up to 6 units , Ups base frame is required for proper wiring support and to avoid direct floor contact ,this system shall include Parallel kit To operate this system inparallel redundancy mode, ups should include Emergency power off kit to shut down ups in Emergency condition , protection- IP 20
Battery backup - Battery should be provided or consider at 0.9 load pf on 100% full load 60 min backup - with Min Guranteed VAh - 76800 VAh -Battery should be SMF VRLA 12 volt - make -Exide /Quanta - battery should be use of 100 Ah Accesories - With battery rack made of metal channel to place support respective batteries for corriosion resistance asethetically pupose battery rack should be Powder coated , Dc isolator OR Suitable SFu links shuold be reuired , Ups to battery Standard DC cable should be required , battery interlinks should be at contractor scope - UPS warranty - 3 Years / Battery Warranty - 3 years
40 kVA without isolation transformer UPS and Battery backup Supply installation and commissioning of UPS 3phase input and 3 phase output rating 40 kVA without isolation transformer 2Level IGBT switching high frequency PWM technology,) IGBT Based rectifier and inverter with double conversion UPS System, with input voltage 320~480VL-L @ full Load & 260 – 480 @ < 50% Load and out put voltage 400 Vac +/-1% 3-Phase + N + E Unity power factor CommunicationPorts RS232,Modbus and inbuilt Ups efficiency should be Min 94% SNMP Card system to monitor operation- System With inbuilt phase sequence corrector inbuilt , Transient surge voltage surge suppressor include parallel operation up to 6 units , Ups base frame is required for proper wiring support and to avoid direct floor contact ,this system shall include Parallel kit To operate this system inparallel redundancy mode, ups should include Emergency power off kit to shut down ups in Emergency condition , protection- IP 20
Battery backup - Battery should be provided or consider at 0.8 load pf on 100% full load 15 min backup - with Min Guranteed VAh - 20160 VAh -Battery should be SMF VRLA 12 volt - make -Exide /Quanta - battery should be use of 42 Ah Accesories - With battery rack made of metal channel to place support respective batteries for corriosion resistance asethetically pupose battery rack should be Powder coated , Dc isolator OR Suitable SFu links shuold be reuired , Ups to battery Standard DC cable should be required , battery interlinks should be at contractor scope - UPS warranty - 3 Years / Battery Warranty - 3 years
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .