Sr. Executive Eng., RAC Section
RAC unit located in the Old building , IIT KGP
Supply, Installation, Testing and Commissioning of Air Handling Unit at Central Library Annexure Building of IIT Kharagpur
2026_IITKG_914833_1
IITKGP/RAC/ CENTRAL_LIBRARY_ANNEX./2026
Open Tender
Electrical Works
90 days
IIT Kharagpur Campus
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹64,300
RAC unit located in the Old building , IIT KGP
25 Jun 2026
25 Jun 2026
17 Jul 2026
25 Jun 2026
16 Jul 2026
25 Jun 2026
3 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supplying, Installation, Testing and commissioning of CKD(Knockdown condition) floor mounted chilled water double skin type horizontal/vertical air handling units in confirmation to IS 18794 : 2024 made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with TEFC drive motor of efficiency class IE5 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for varialbe frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification of CPWD and of following capacities. (Total static pressure considered is max. 50 mm wg). Make- Systemair/ VTS/ Citizen/ Flakwood/ Carrier | |||||
| 1.01 | 10,200 CMH | - | Nos | - | - |
| 2Volume control damper for duct damper Make-Systemair/ Airmaster/ Air flow | |||||
| 3Electrical panel for AHUs.: Panel shall be with suitable incomer MCB / MCCB, contractors, relays, push button (On/off/reset), indicating lamps for start, stop, trip for AHUs. Panel shall have neccessary relays & contractors for BMS application, auto manual switches with interlock. Make- Thitanix/ EAP/ Genpower | |||||
| 4Power and Control Cable:Copper Cables for power and control of AHU | |||||
| 5MS perforated cable tray Hot Dipped Galvanized 100 X 50 X 1.6 mm | |||||
| 6Flexible canvas connection | |||||
| 7Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. | |||||
| 7.01 | M.S. Pipe 65mm dia | - | RMT | - | - |
| 7.02 | M.S. Pipe 50mm dia | - | RMT | - | - |