CWE AF NAGPUR
HQ CWE AF NAGPUR VAYUSENA NAGAR, NAGPUR 440007 MILITARY ENGINEER SERVICES
REPAIR MAINT OF HT DISTRIBUTION SYSTEM, VCB TRANSFORMER, HT PANEL AND CABLES AT AFS AMLA
2025_MES_733958_1
80708/E8
Open Tender
Civil Works
Item Rate
GE AF AMLA
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE AF AMLA
₹90,000
Yes
22 Dec 2025
6 Oct 2025
8 Nov 2025
6 Oct 2025
6 Nov 2025
30 Oct 2025
Amount
Material and Labour for on load filtration/dehydrating of transformer oil by means of ultra High vacuum double stage machine to remove impurities from oil such as moistures dirt air and other gases at site of installations by continuous circulation of transformer oil through mechanical filters (any type transformer 11KV / 433 volt and 33 KV/11 KV) at various location to achieve the desired dielectric strength of 40-60 KV for one minute at 2.5 mm gap including filtration of new transformer oil required for top up to oil conservator level complete all as specified. Note: (i) Oil samples are to be collected from top and bottom of oil tank and test results to be submitted by the contractor for each sample before and after filtration. (ii) New transformer oil required for top up will be measured & paid separately.
Supply and topping up new transformer oil as per IS-335 of dielectric strength 60 KV at 2.5 mm gap in transformers/CTs/PTs of various capacity installed in various sub stations. Note: (i) New transformer oil in the transformer shall be filled in the transformer only after filtration and dehydration of existing transformer oil. (ii) Transformer oil shall be supplied in sealed barrel with test result and test certificate to be submitted by the contractor.
Taking out old/ exhausted silica gel from transformer breather, cleaning of the breather assembly. Supply and filling new silica gel in the breather complete and re-fixing the breather assembly with the transformer complete all as specified and directed.
Supply & Fix in repairs breather assembly of the transformer of 1 KG capacity, any shape, any dia suitable to fit for existing transformer assembly complete all as specified and directed. Note: Shape/type should be as per existing transformer at site.
Supply and fix in replacement out door type HT 11 KV cable jointing feeder pillar (supplied by CPRI approved manufacturer) powder coated for inspection and meggering during faults, fabricated of CRCA sheet 3 mm thich duly painted as per standard normas totally enclosed and sealed with rubber packing and feeder pillar mounted on MS angle size 70 x 70 x 05 mm thick including two coat of black paint over one coata of red oxided primer, dust proof, vermin proof/ water proof both sides openable, having provision for termination of two No's 11 KV HT cable with AI bus bar PVc sleeve, air insulataed coloru coded of 200 Amp capacity, duly mounted on 11 KV epoxy insulators with two No's GI studs 10 mm thick for connection of GI earthing stip complete all as specified and as directed. Make & drawing to be approved by GE.
M&L for disconnecting 11/0.433 KV distribution transformer of follwing capacity by removing overhead conductor/ underground cables and earth strips etc. Installation of transformer after repairs, making all connections, testing and recommissioning to full satisfaction of Engr-in-charge. Taking out the transformer from any substation using suitable capacity crane or by any other method irrespective of type of approach available, loading in vehicle, transportation to workshop for repairs and unloading carefully. Reloading the tranformer after repairs, transportation to site and unloading including placing at given position complete all as specified and directed. Note : (i) All the T&P required for disconnection, connection, loading and unloading including necessary petty items like bolts, nuts etc will be arranged by the contractor and rates for the same deem to be included in the rates quoted. (ii) All test certificate to be produce by contractor to Engr-in-Charge. (iii) Any damge to the transformer during transporting or any damged during repair will be rectify by contractor without any extra cost.
Capacity 315 KVA to 1250 KVA
Capacity 50 KVA to 250 KVA
M&L for repair to transformer step down 11/0.433 KV indoor/outdoor type of following capacity, after dismantling the transformer carefully, opening the top cover of transformer for inspection /repair, draining out the transformer oil from the housing complete, taking out the core and winding by disconnecting the internal connections, removing the carbon/sludge deposit in transformer housing core, renewal/replacement of u/s rubber bushes and washers , replacement of tap changer and thimbles, replacement of silica gel, replacement of top cover gasket set including pasting with pasting material, replacement of worn out nut and bolts, replacement of unserviceable LT & HT bushes, cutting the burnt out winding and re-winding the same with suitable size of super enamelled copper wire as per existing guage, insulating the winding connection by using fire proof sleeve and fire proof tape, varnishing the coil, keeping the coils in electric oven chamber for 24 hrs to remove the moisture, Painting of complete transformer body from outside and inside, Marking of MES/SM Number etc, replacement of conservator tank glass, re-installing the core and winding inside properly, making the all connection with suitable copper lungs, refilling of dehydrated transformer oil including dehydration, reinstalling the top cover after cleaning and painting of housing, conservator tank, expulsion vent etc, Meggering the LT and HT side of the Transformer and testing complete all as specified and directed by Engr-in-Charge. Note : Winding wire including labour for making of coils and LT/HT bushes will be measured & paid seperately. Contractor should make necessary arrangement for factory visit before opening of the transformer for repairing work and testing of the transformer after carried out necessary repairs.
Capacity 315 KVA to 1250 KVA
Capacity 50 KVA to 250 KVA
All As per item no. 6 but for 33/11 KV Power transformer up to 2.0 MVA
All As per item no. 7 but for 33/11 KV Power transformer up to 2.0 MVA
Material & Labour for rewinding of any type and any size of transformer with super enamelled copper conductor wire of suitable gauge and size as per requirement and as per OEM specifications and relevant IS for rewinding the HV coil complete all as directed.
Material and Labour for rewinding of any type and any size transformer with super enamelled copper conductor wire of suitable gauge and size as per requirement and as per OEM specifications and relavent IS for rewinding the LV coil complete all as directed.
Supply and fix HT bush assembly made out of brass stud made out of heavy duty brass complete with brass spindle, rubber gasket, nuts, bolts & washers with bushing insulators all as per existing size shape & length suitable for HT 33 KV/11 KV 2000 KVA transformer complete with oil seal, gaskets, ring washer etc for transformers including taking out existing bushings and refilling the same, complete all as specified & directed.
Supply and fix LT bush assembly made out of brass stud made out of heavy duty brass complete with brass spindle, rubber gasket, nuts, bolts & washers with bushing insulators all as per existing size shape & length suitable for HT 33 KV/11 KV 2000 KVA transformer complete with oil seal, gaskets, ring washer etc for transformers including taking out existing bushings and refilling the same, complete all as specified & directed.
Supply & fix HT bushings with brass rod suitable size for following capacity of transformer, including cork sheet gaskets complete all as specified and directed:-
Capacity 315 KVA to 1250 KVA
Capacity 50 KVA to 250 KVA
Supply & Fix LT bushings with brass rod suitable size for following capacity of transformer, including cork sheet gaskets complete all as specified and directed:-
Capacity 315 KVA to 1250 KVA
Capacity 50 KVA to 250 KVA
Supply and fix Oil temprature indicator for distribution transformer up to 1250 KVA, including necessary control wiring and accessories as per site requirement complete all as specified and directed.
Supply and fix winding temprature indicator for distribution transformer 1250 KVA , including necessary control wiring and accessories as per site requirement complete all as specified and directed.
All as per item No. 16 but for power transformer up to 2000 KVA
All as per item No. 16 but for power transformer up to 2000 KVA
Material and labour for disconnecting and shifting of 11/0.433 KV distribution transformer/CSS of capacity up to 400 KVA by removing overhead conductor/ underground cables and earth strips etc from one location to other location within the Airforce station permisis and reinstallation of transformer making all connections to full satisfaction of Engr-in-charge from any substation using suitable capacity crane or by any other method irrespective of type of approach available, loading in vehicle, transportation to another substation and unloading carefully.complete all as specified and directed. Note : (i) All the T&P required for disconnection, connection, loading and unloading including necessary petty items like bolts, nuts etc will be arranged by the contractor and rates for the same deem to be included in the rates quoted. (ii) Any damge to the transformer during transporting or any damged during repair will be rectify by contractor without any extra cost.
Material and labour for preventive maintainance, overhauling, servicing & testing on on/off load of Vacuum Circuit Breaker (VCB) 630/800 Amps, 3 Phase, 50 Hz, AC supply system, indoor type of Make: Easun Reyrolle/Areva/ Megawin/CG by taking out trolley of vacuum circuit breaker 630/800 Amps 11 KV from the cabinet & opening top cover, cleaning & decarbonizing moving and fixed contacts, lubricating, inspecting the control wiring identifing the defect & their redressal alongwith microprocessor EF/OC relay, tripping coil electrical and checking for auto manual operation, caliberation of microprocessor E/F & O/C relay of VCB complete and caliberating with portable relay test kit to set time and fault level adjustment of setting with according to load & time with main grid for proper synchronising the the tripping so that individual VCB shall be tripped prior to main panel checking & inspecting the wiring, spring charging motor, tripping coil, closing coil, spring charging limit switch & testing for manual /auto tripping system, cleaning wiping of insulating component, incl primary & secondary current injection test, spouts, busbars, supports, CT, PT, cleaning contact tips, cover the expossed portion of busbar with HT tape & heat shrinkable sleeves, spout insulators for visible crack, tightness of fasterners holding moving contacts, check & correct the buffer gap adjustment & mechanism settings, meters. Testing and calibration of all relays fitted in control panels from authorized testing team of the OEM, such as earth fault relays, over current relays fitted in HT 33/11 KV panels for its corrections & setting with main control panel relays 33 KV VCB panels for its corrections & setting with main control panel relays so that individual VCB shall be tripped prior to main panel, contractor shall submit testing and calibration report showing all set parameters. Testing, cleaning & overhauling of complete operating mechanism for smooth functioning, checking of control panel wiring for operation & protection for tripping & closing & rectifying the defects all equipments including Deoxidizing of all electrical contacts /make & break contacts using water & heat resistant CRC aerosol lithium base white grease spray suitable for lubrication & rust removal of moving & fixed contacts of electric switchgears complete all as specified as directed by Engineer-In-Charge. Note: (i) Servicing shall be got carried out by the authorised rep of the VCB manufacturer and the service engineer will submit a service report for each VCB. (ii) The parts recommended by the service engineer will be replaced under subsequent items and shall be measured & paid seperately as supply only (iii) Any minor items not included above but required for successful operation of the panel will be provided by the contractor and same shall deemed to be included rate quoted.
Supply only HBC fuse links HT 12 KV AC 10 A/20A/25A
Supply only Heater unit, 230 volts, with thermostat complete with wiring suitable for 11 KV HT VCBs
CT for HT 11 KV of ratio 5/50/5/100 Amp as per existing size and shape all as specified and directed.
Supply only epoxy insulators HT 11 KV suitable for providing spacing between bus bar and panels of 11000 volt grade, shape as per existing at site complete.
Supply only digital voltmeter for VCB 11 KV complete.
Supply only digital Amp meter for VCB 11 KV complete.
Supply only shunt trip coil 30 V DC 11 KV VCB complete.
Supply only closing coil 30 V DC 11 KV VCB complete.
TNC switch suitable for auxillary supply 24V DC
Supply only vaccum interrupter 12 KV, 2000A, 20.3 KA rating. Make: Bharat Electronics Model - VS12014
Supply only spring charge motor 230 volt DC suitable for Make: Easun Reyrolle VCB type EVB 1225, rated voltage 11 KV, 400 Amp, 13.4 KA rating.
Supply only HT panel shutter/base plate made up of 2mm CRCA sheet as per existing size including neoprene gasket and screws as per existing bore in order to ensure complete packing HT panel.
Supply only 11 KV VCB panel spout in set of three including steel nuts, bolts and washers complete.
Supply and fix in repair PVC insulated and weather proof three core copper multi stranded conductor cable 4 Sqmm size as required length for replacing unserviceable cable for VCB conrol panel to circuit brekar all as specified & as directed . Make Polycab, Havells, KEI, Gloster etc
All as per item no 35, 6 core 4 sqmm all as specified & as directed . Make Polycab, Havells, KEI, Gloster etc
All as per item no 35, 12 core 4 sqmm all as specified & as directed. Make Polycab, Havells, KEI, Gloster etc
Material and labour for preventive maintainance, overhauling, servicing and testing of potential transformer (PT) 11 KV, ratio 11kv/110v, class 0.5, top mounting of incomer 11 KV VCB panel complete all as specified and directed. Note: Spares replaced shall be measured and paid under relevant items here-in-after as supply only.
Supply only 11 KV PT HRC Fuse 11000 Volts rating, 2 Amps complete.
Supply only push type contacts suitable for 11 KV PT complete.
Supply only spouts for 11 KV PT complete.
Supply only bushings for 11 KV PT complete.
Material and labour for preventive maintainance, overhauling, servicing & testing on on/off load of HT VCB 33 KV (Make: Areva/Crompton Greaves) breaking capacity 25 KA, 36 KV, 800/1250 Amp rating decarbonising complete contact points, meggering, all HT insulators including oiling/greasing to moveable parts and replacement of burnt/unserviceable parts including checking of control wiring all as specified and as directed. Note: Spares replaced shall be measured and paid under relevant items here-in-after as supply only
Supply only vaccum interruptor 33 KV, 800 Amps complete.
Supply only tripping coil 30V DC complete.
Supply only closing coil 30V DC complete
Supply only spring charging motor 230V AC
Material and labour for preventive maintainance, overhauling, servicing & testing on on/off load of HT 33 KV CTs/ PTs, single phase including top up of oil complete all as specified and directed. Note : (i) Spares replaced shall be measured and paid under relevant items here-in-after as supply only. (ii) Test reports of CTs & PTs shall be submitted by the contractor.
Supply only brass/copper stud size 30mm dia alongwith suitable nuts & washers.
Supply only pad connector (Aluminium alloy)
Material and labour for preventive maintainance, overhauling, servicing, relay setting & testing on on/off load of HT 33 KV control relay panel of Make: Schneider/ CG/ Areava, having 3 phase over current earth fault numeric relay MICOMP111, Make: Alstom auxillary relays, Make: Alstom master trip relay, testing primary current injection for tripping operation and checking of DC circuits simultation/calibration check of all auxillary relays for its trip/alarm signal complete all as specified and directed. Note: (i) Test Reports of control relay panel shall be submitted to by the contractor. (ii) Spares replaced shall be measured and paid under relevant items hereinafter as supply only. (iii) Repair and relay setting shall be undertaken through authorised OEM service engineer.
Supply only TNC switch suitable for auxillary voltage 30V DC.
Supply only auxillary relay 30V DC rating Model : VAA33ZG8344BCH
Taking out old unserviceable parts of air break isolating switches (GOD) rating 11 KV 200/400 Amps rating. S&F following parts complete all as specified and directed. Make: Jaipuria
Male contact/moving contact blade.
Female contact/fix contact jaw
MS Jumper carrier
Back connector plate
Supply, fixing, testing and commissioning in replacement air break isolating switch tripple pole mechanically operated with vertical isolation,12 nos. polymer type insulators mounted on steel frame with operating mechanism worked from ground level and including operating rod of 25 mm dia medium grade GI pipe and locking arrangement of capacity 200 Amps 11 KV with drop out fuse set including making all incoming/outgoing connection of HT cable and overhead conductor using new leads and nuts, bolts etc and painting of steel work with 2 coats of aluminium paint over a coat of red oxide primer complete all as specified and directed. Make: Jaipuria/Pactil/Alstom
All as per item No. 55 here-in-before but for capacity 400 Amps
Supply and fix isolator 33 KV horizontal type, rating 200 Amp, triple pole, outdoor type including steel frame with operating mechanism worked from ground level complete including taking down of old isolator all as specified and directed. Make: Jaipuria/Pactil/Alstom
Material and labour for servicing of isolator 33 KV horizontal type, triple pole outdoor type including cleaning contacts, removing carbon, adjusting the fixed and moving contacts, guides, applying petroleum jelly for easy operation all as specified and as directed. Note: Spares replaced shall be measured and paid under relevant items here-in-after as supply only.
Supply only pad connector (Aluminium alloy)
Supply only male contact rod with clamps & Nuts, bolts.
Supply only female fix contact jaw
Taking out old userviceable HT UG cable of size 120/95 Sqmm from trenches/ducts/pole complete all as specified and directed.
Supply and laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable, heavy duty with aluminium conductor 11000 volts grade (earthed) of following cross sectional area complete all as specified and directed :-
95 Sqmm 3 core
120 Sqmm 3 core
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable for following sizes :-
50 Sqmm to 95 Sqmm
120 Sqmm to 185 Sqmm
Supply and fix outdoor in repair cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable for following sizes :-
120 Sqmm to 185 Sqmm
50 Sqmm to 95 Sqmm
Supply and fix in repairs cross arms, bracing, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts, in any shape or size including two coat of aluminium paint over one coat of red oxide paint complete all as specified and as directed.
Dismantling old steel poles/struts, any size.
Supply and fix in repairs for steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11.0 metres long)
Supply and fix in repairs pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade.
Supply and fix in repair disc type insulator, porcelain, vitreous 145 mm high and 255 mm dia ball and socket type, white brown or green "Two-in-series" assembly for tension with tension clamps for conductors, working pressure 11000 volts.
Material and labour for lightening arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 33 KV. Make: Jaipuria/Pactil/Alstom
Supply and fixing RCC HT cable route/joint marker of size 300mmx120mm and 800 mm long with engraved letters "MES 11 KV HT CABLE" including painting with appropriate colour paint as directed by Engineer-in-charge complete all as specified and directed. Note : Earth work and PCC work shall be included in the quoted rate.
Material and labour for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for HT 25x20cm size all as specified and directed
Material and labour for earthing complete with galvanized iron or steel plate electrode 60cm x 60 cm x 6.00 mm thick buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 32 x 6 mm dia as earthing lead by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to machinery/ equipment all as shown in electrical plate No. 3 of SSR-2010 Part I and including necessary excavation and earth work in any type of soil, 20mm bore light grade GI pipe for watering, funnel, wire mesh, PCC (1:3:6) type C-1 chamber, PCC (1:2:4) type B-1 reinforced with 6 mm dia MS round bars @ 15 cm c/c both ways for cover 50 mm thick and MS frame of suitable size made of angle iron 50 x 50 x 60 mm, complete all as specified. Note: (i) The unit rate includes earth lead and protection pipe up to maximum 7.5 metre from earth plate to earth point/test point. (ii) Earth pit shall be constructed minimum 0.5 metre away from earth.
Servicing and preventive maintenance of out door type HT 11 KV cable jointing feeder pillar (supplied by CPRI approved manufacturer) tripple pole vertical isolation, 06 Nos, epoxy insulators mounted on steel frame, physical check of expoxy type insulator for any damage, repairing of locking arangement by means of welding or replacement of hindges as per requirement, chekcing of earthign strip connection and make sure it is connected to feeder pillar, cleaning the vegetation around the panel and kaing servicable capacity 200 Amps 11 KV grade.
M&L for earthing complete with copper earth plate electrode 60cmx 60x cm x 3.15 mm thick and burried directly in ground (earth pit not less than 2.5 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to copper earth plate with copper strip of size 20 x 03 mm as earthing lead by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 32 mm bore (light grade) connected to machinery/ equipment all as shown in electrical plate No. 3 of SSR-2010 Part I and including necessary excavation and earth work in any type of soil, 20mm bore light grade GI pipe for watering, funnel, wire mesh, PCC (1:3:6) type C-1 chamber, PCC (1:2:4) type B-1 reinforced with 6 mm dia MS round bars @ 15 cm c/c both ways for cover 50 mm thick and MS frame of suitable size made of angle iron 50 x 50 x 60 mm, complete all as specified. Note: (i) The unit rate includes earth lead and protection pipe up to maximum 7.5 metre from earth plate to earth point/test point. (ii) Earth pit shall be constructed minimum 0.5 metre away from earth..
Material and labour copper strip as earth continuity conductor or main earthing lead of size 20 x 3 mm
Supply & fix in replacement battery bank 240 Volt(12V x 20),26AH at 10Hrs discharge rate self contained,floor mounted two tier housing steel (CRCA) sheet cabinet for housing the battery floor mounted sheet with Battery charger unit 240V,10Amps maintenance free VRLA battery,initial charged complete with accessories suitable for DC supply of HT VCB 415V,3 phase ,50HZ,AC supply ,complete all as specified and as directed.
Supply and laying synthetic rubber insulated mat 2.50 mm thick for voltage upto 11 KV for electrical purpose as per IS-15652 of size 2 Mtr x 1 Mtr,complete all as specified and directed.
Excavation in trenches not exc. 1.5 Mtrs wide and not exc. 1.5 mtr deep and getting out in hard/dense soil all as directed and specified.
Excavation in trenches, not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3.0m in depth; for laying cables and getting out in hard/dense soil complete all as specified and directed.
Returning filling in including spreading levelling watering and well ramming in layers not exc 25 cm thick all as specified and directed.
Removing of surplus excavated materials to a distance not exceeding 50 mtr and deposting where directed at a level not exc. 1.5 mtr above the starting point all as specified and directed.
Material and labour for river sand, washed and screened dry for cushioning to under ground cable in trenches/ sub station cable ducts below and around under ground cable including spreading and levelling complete all as specified and directed.
Supplying and laying un-reinforced precast concrete cable cover, class EVP, type 1 with peak size 300mmx180mmx40mm over sand cushioning for protection of cable complete all as specified and directed.
Supply and fixing in repairs for GI tubing size 100 mm dia light grade laid in trenches/fixed to poles, walls etc as protection of cable all as specified and directed. Make: Tata/Jindal/Prakash Surya
Material and labour for cement concrete 1:3:6 type C2 using 40 mm graded as in foundation filling and mass concrete complete all as specified.
Material and labour for cement concrete type B1, 1:2:4 (using 20 mm graded stone aggregate) for coping including form work etc complete all as specified and directed.
Material and labour for plain cement concrete 1:4:8 type D2 using 40 mm graded stone aggregate as in foundations, filling and mass- concrete, complete all as specified & directed.
Material and labour for painting of poles of 2 pole structures at various locations as under with two coats of aluminium paint inlcuding preparation of surfaces all as specified and as directed.
All as per ser item No 90 above but of 4 Pole structure complete.
Material and labour for laying graded coarse aggregate of nominal size 40mm out of basalt/trap/granite stone spread in layers in sub stations/ transformer installations complete all as specified and directed.
Supply and fix in repair/replacement 11 KV feeder protection IDMT relay 3OC+1EF relay Model no CGI14N IN of CG or equivalent in ABB or Ashida with O/C+EF+High set 15/51RYBN numerical relay,lowest O/C-1s,Highest O/C-1hs,Lower D/F-0s,Highest E/F Ohs,including caliberation of relay with existing system so that can be arrested in indivisual panel,all as specified and directed.
Note : The amount against Schedule of Credit on Page No. 38 shall be deducted from the total amount quoted against Sch 'A' while deriving lum Sum for Acceptance.
Paragon Electrotechnics (BID ID -3468060)
nhsaluji and associates (BID ID -3469944)
Bidder Name
Paragon Electrotechnics
nhsaluji and associates
S S TRADERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.59 MB
BOQ_821828.xls
BOQ • 0.41 MB
ps.pdf
Tender Documents • 1.40 MB
corrigendum0180708.pdf
PDF • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .