CWE (AF) Jaisalmer
HQ CWE (AF) Jaisalmer
WORK SERVICES FOR PROVISION OF MAFI POWER REVERTING TO BACK FEED CONFIGURATION AT AF STNUTARLAI
2026_MES_758054_4
80385
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
GE (AF) Utarlai
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) Utarlai
₹71,154
1 Sept 2026
1 Sept 2026
24 Sept 2026
1 Sept 2026
22 Sept 2026
15 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Material, Laying , connection, testing and commissioning for Automation system for sequencial monitoring and controlling 06 Nos VCBs, RMU for operating of HT 11 KV VCB in Auto mode by electric supply availability, fault current sensing , operating of incomer VCB in Auto mode. The system shall consist the following items complete all as specified and directed by Engr-in-Charge:-
1) panel Box with made out of 2mm thick CRCA sheet stand made out of angle iron including programming for automatic ON/OFF operation of VCB and provision of operation in manual mode.
2) PLC type 32DI/24DO repairs-1Set
3)HMI display7" - 1 Nos.
4) Communication Module RS 485 serial communication- 1 No.
5) Energy meter with RS 485 indicating all Electrical Parametres including PVC flexible copper conductor cable PLC of type - 7 Nos.
6) Main Switch 32 A - 1No.
7) Control MCB 6A - 21 Nos.
8) Relay Module including all accessories - 3 Nos.
9) Power Supply Module 24 VDC 5A - 1 No.
10) Fan 4"- 1 No. | 1 | Each | - | - |
| 1.01 | 11) Ventilation Fan Filter 4" - 2 Nos.
12) Cable tray as per requirement.
13) Din Rail - as per requirement
14) Control Wire 1.5 Sqmm 2 core as required.
15) Power Cable 2.5 Sqmm as required
16) Power Trminals as required.
17) Control Terminals as required including internal controll limits.
18) Programming of PLC as per site requirement for automatic/ manual mode operation of VCB for ensuring power supply change over based on supply availability all as directed at site.
19) Field wiring 1Sq.mm 2 core cable with glands, lugs, connectors, conduit as per requirement of suitable lugs for connection with existing VCB & ACB
20) Power Cable of multi core copper conductor with glands, lugs, connectors, conduit as per requirement of suitable lugs for connection with existing VCB & ACB (21) all safety precaution and connection should be as per IE rules. (22) All connection & operational sequention and time lag for switching should be as per user reqmt accordingly CAT II mode of operation (23) Integration of ACBs/VCBsyo suit emergency power feed to MAFI PS-II includng selection and supply with conformity to interlock suitability for normal and CAT-II modes of operation for specific direction of power feeds. | - | - | - | - |
| 2 | Supply, install, commission and test Ring Main Unit (RMU) HT 11 KV Outdoor Extensible type, cubical 3 Way (2 I/C VCB + 1 O/G VCB) gas (SF6) insulated comprising with incomer - 2 Nos. X VCB and outgoing - 01 NOs X VCB of rating of each 630 Amp 3 phase 50 cycle 12 KV, 20 KA/3 sec ambeint temprature (-5 degree celsius to +55 degree celsius ) . Manual operated SF6 breaker having copper bus bar 600 Amp rating cast resin tank with , LV current transformer compatible with self powered relay & 11 KV resin cast PTs (one set of 3 Nos.) with seprate metering chamber complete make- SIEMENS model 8 DJH ST/ euivalent in makes specified in Appendix "B" Makes of Particular Specifications..
Each Circuit breaker will have the following-
(i) Manually operated SF6 VCB 3 phase 630 A, 12 KV rating circuit breaker having resin cast tank and earthing switch with full making capacity with position ON-OFF - Earth
(ii) Manual line disconnector with three position switches ON-OFF -Earth
(iii) Anti reflex operating handle
(iv) Auxiliary switches 3 No. +3 NC with wiring | 1 | Each | - | - |
| 2.01 | (v) Shunt trip coil (230 V AC) for external trip signal
(vi) Self powered O/C + E/F relay protection 3 phase definite time over current and short circuit protection with selectable inverse time characteristics and definite time short circuit currrent element ( ANSI 50/51) , definite Make- WIB Woodward AVK SEG/ equivalent (vii) Live cable indicating LEDs energised through capacitive voltage dividers
(viii) cable box suitable for cable termination of 1 No , 3 CX 120 Sqmm XLPE cable | - | - | - | - |
| 2.02 | Accessories with each RMU includes-
(i) Operating handle -01 Nos
(ii) Right angled cable boots make- Siemens/equivalent - 03 Sets
(iii) Capacitive voltage indicator type HR-ST-Make Hortsmann - 03 Nos separate metering chamber having -
(i) 3 phase 3 limb drawout type bus connected epoxy potential transformer ratio 11 kv/root3/110V/root 3 AC accuracy 1.0 burdon 50 VA-01
9ii) Digital type voltmeter -01 Nos.
(iii) RYB indicator- Sets
NOTE-
(i) RMU shall be outdoor plinth mounted
(ii) Erection commissioning and civil work (plinth protection) for RMU is deemed to be included with unit rates. The plinth protection details as per the manufacturer instruction after approval of drawing from GE.(i) Cable terminals cable bushing situated not beyond 300 mm or as per OEM tested design from cable cover to allow ease for installation/testing /*replacement purposr) with door arrangement for enhanced safety (IP 54+IP3X) interlocke to prevent access up to 11 KV, 185 Sqmm 3 core alongwith XLPE AL cable termination each set of 03 | - | - | - | - |
| 2.03 | (iii) Right angle boots (push on type) each set of 3
(iv) 3O/C +1 E/F self powered numerical protection relay with low and high set for overcurrent and earth fault. relay should have facilities to display maximium loaded phase current also. relay shall record minimum 5 fault records with time stamping . Relay shall be communicable with RS 485 port on MODBUS protocol-01 No. /per VCB
(v) Relay for OTI/WTI/B - relay protection-01 No.
(vi) Associated ring core cast -resin insulated CTs 50/1 Amps 2.5 VA 10 P 10 protection - each set of 3
(vii) Arc proof cable cover having cable entry from bottom , front with interlocking mechanism including earth switch -01 No.
(viii) Capacitive voltage indication fixed type system as per IEC 6123 with LED -01 set
(ix) ON OFF Earth mechanical indication on the front mimic of the panel - 01 No.
(x) Emergency trip push button -01 Nos. | - | - | - | - |
| 2.04 | 01 No bus connected fixed- type auxilary transformer with floor mounted compartment of matching height and depth positioned alongside RMU to provide required aux supply for spring charging motor and metering consisting of following accessories.
(i) 3 ph ( 11 KV/root 3) ; 230 volt AC 500 VA auxilary transformer -01 No. alongwith trivector meter
2X12 Volt DC battery -01 Set
(iii) Battery charger with power pack -01 No. with indication of status of functioning
(iv) HRC fuses links for primary side isolation and AC/DC supply availability -01 Set
(vi) anti condensation space-heater -01No.
(vii) LED lamp for illumination and 3 pin socket with switch-01 No.
(viii) Enclosure- powder coated camouflage
(ix) Complete RMU must be scada compatible
(x) Separat cable entry box must be mounted with RMU system(D) Standard mano meter -01 for each tank operating handle -2 , cable clamping provision (standard) -01 / for every cable entry operation and maintenance manual-01, installation and commissioning manual-01, Foundation as per OEM recommendation (earth work and PCC works) for placing RMU on plinth is deemed to be included in the cost quoted . Height of plinth should not be less than 0.60 mtrs from ground level. | - | - | - | - |
| 3 | Supply, lay, test, joint and commission XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured electric powercable heavy duty with aluminium conductor of size cross sectional area 120 sqmm 3 core, 11000 Volts grade (11 KV earthed system); laid in trenches/under floor/through ducts, on Hill / fixed on pole complete all as specified and directed.
Note : Excavation & Earth work, sand cushioning, cable protection cover, pipe and joint shall be measured and paid separately under respective items . | 70 | RM | - | - |
| 4 | S&F for Cable End Termination Jointing Kit, HT 11 KV grade, heat shrinkable, indoor type complete with jointing materials and accessories suitable for HT XLPE cable 3 core 11 KV grade of size 70 Sqmm to 120 Sqmm x 3 core armoured alumuinium conductor cable complete all as specified and directed.
Note- Unit rate quoted by the contractor shall be deemed to inclusive of jointing material like long sleeve form RMU connection and other connected items, T&P and labour etc. | 4 | Each | - | - |
| 5 | Supply, lay, test, joint and commission XLPE insulated , galvanised steel strip or wire armoured electric powercable heavy duty with aluminium conductor of size cross sectional area 300 sqmm 3.5 core, 1100 Volts grade laid in trenches/under floor/through ducts, on Hill / fixed on pole complete all as specified and directed.
Note : Excavation & Earth work, sand cushioning, cable protection cover, pipe and joint shall be measured and paid separately under respective items . | 60 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.61 MB
Tender.pdf
Tender Documents • 1.24 MB
BOQ_882230.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .