Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹69.0 LAccepted-AOC | L1 | Accepted-AOC Acceptance Letter issued. | |
| 2 | L2₹77.7 L+₹5.1 L (7.04%)Rejected-Finance | L2 | Rejected-Finance Financial Bid Rejected | |
| 3 | L3₹1.1 Cr+₹36.4 L (50.1%)Rejected-Finance | L3 | Rejected-Finance Financial Bid Rejected | |
| 4 | L4₹1.1 Cr+₹36.4 L (50.1%)Rejected-Finance | L4 | Rejected-Finance Financial Bid Rejected |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
5 Feb 2020, 5:00 pmClosed
Jt Director of Industries Pune Region Pune
Office of the Joint Director of Industries,Pune Region, Agriculture College Campus, Shivajinagar, Pune - 411 005
SUPPLY, ERRECTION, COMMISSIONING AND PERMISSION OF TRANSFORMER ELECTRIFICATION WORK ALONG WITH TURNKEY JOB
2020_DIMUM_537309_1
JDI/PUNE/MSECDP/MAEC/2019-20/2
Open Tender
Electrical Works
Item Rate
547 days
FIVE STAR MIDC KAGAL DIST KOLHAPUR
Please refer Tender Document
2 documents required · 2 mandatory
₹3,000
Online Payment
₹50,000
Yes
Office of the Joint Director of Industries,Pune Re
28 Feb 2020
23 Jan 2020
7 Feb 2020
23 Jan 2020
5 Feb 2020
28 Jan 2020
23 Jan 2020 - 27 Jan 2020
27 Jan 2020
Amount
SUPPLY, ERRECTION, COMMISSIONING & PERMISSION OF TRANSFORMER ELECTRIFICATION WORK (ALONG WITH TURNKEY JOB) [•Total cost in CIF premises at Microaxis Auto & Engineering Centre, Plot No. H-2 at Kagal Hatkanangale Five Star Industrial Area, MIDC, Dist. Kolhapur, State-Maharashtra, India, including GST, All applicable taxes, Clearing, Transportation, Insurance , Unloading, Installation & Commissioning, agency commission, packing, forwarding, On-site technological training, training for mechanical and electrical maintenance for 4 persons for 2 weeks, Internal Electrical Cable
SUPPLY OF MSEB CONNECTION, TRANSFORMER CENTRE
RSJ 116 x 100, 11 m long
RSJ 116 x 100, 10 m long
11 kV Pin Insulators with G.I. Pins
Disc Insulator 11 KV 7000 KG.
G.I Wire
Garding channel
Top Fitting
AAAC Dog Condector
H.T. Stay Set
G.I. Barbad Wier
Panting For All Poles & structure
Concreting For All Poles & structure
HT Earthing set
Including Power Supply & Layering of sand Bricks to cover All Cable. Length . Exaction & Back filling worked
CU point set
Installation of termination kit for above cable
Supply & fixing of 100mm die GI Pipe
Supply & fixing DP Structure with GOD.DO& LA set RSJ pole 11mtrs long MS channel Supports GOD.DO& LA set etc as required to completed job
Installation 200KV. 11KV. Outdoor type onan cooled transformer
Supply and making Chain link fencing including civil work
Earthing pits for DP structure-supply and providing 2X2 filis long GI Plates with 2 no. Bag Back fill compound fixing of copper bolt nut Etc Complete as required
Earthing pits (Supply and providing 2X2 feets long GI Plates I with 2No. Bag Back fill compound excavation of earth pit in any type soil work .sp[reading a back fill compound fixing of copper bold nut etc complaintetly as required )
supply a& fixing of GI strip 32X5mm including necessary material require to completed Job
Load deposit of 125 HP & 10/40A meter capcitor
electrical inspecator for factory insepcator approval layout letter drawing approval & permition work
Transportation of all material
sundries
main meter wiring (40/200) main board to machine panel supply Xlpe armod cabel laying machine supply (MCCCB-DP) all machine earthing
1PH Multy stand wire in PVC pipe industrial wiring. Tube set fitting, LED fitting, Power plug
Shed for Metering kiosk
CUBICAL PANEL BOARDS :- Installation , testing & commissioning of M.S. Cubical Panel Boards as per specific conditions . ( Note- Panels will be supplied by Owner at Site)
MAIN PANEL No.-1 NEAR TRANSFORMER AT GROUND FL.
SWITCHGEARS :- Supply & erection of following Switches / MCCBs in sheet steel enclosure at various places as directed. The cost includes necessary M.S. Channels frame required etc. complete.
32 A TP MCCB
63 A TP MCCB
125 A TP MCCB
200 A TP MCCB
250 A TP MCCB
16 A. S.M.D.P. with rewirable fuses.
32 A. S.M.D.P. with rewirable fuses.
63 A. S.M.T.P. with rewirable fuses.
M.C.B. DISTRIBUTION BOARDS :-upplying, erecting ,connecting & commissioning of following MCB Distribution Boards with IP 43 protection at various places in a concealed manner with necessary openings in the wall & repairing it as original, painting, M.S./T.W. wireway box below DB as directed & etc. complete. Note-1) Breaking Capacity - MCCB- 25 kA, MCB - 10 KA, 2) The outgoing MCBs may vary as per actual requirements , 3) DB Circuit Numbering to be done for each MCB in Ecah DB after completion of work ) Vertical TPN Distribution Boards ( VDB)- (NOTE :- The outgoing SP / TP MCB configuration may change as per actual load requirements.)
4 way vertical TPN Distribution Board with Metallic double door, busbar etc. complete similar to Legrand Cat No. 507740 with cable end box suitable to accommodate meters, indicating lamps etc. complete. ( Main VDB- 11, VDB-16, VDB-22, VDB-26 ) Incoming – i) 63 A TP MCCB Outgoing – i) 3 Nos. 6-20 A. SP MCB. ii) 2 Nos. 20-32 A. TP MCB. iii) 1 No. 40-63 A. TP MCB.
SPN Distribution Boards ( SDB)-
8 Way Single Phase & Neutral Distribution Board with Metallic Double Door, busbar etc. complete similar to Legrand Cat. No.507611 with 6 Nos. 6-32 A. SP MCB as per circuit load fitted in Box as directed.
12 Way SPN Distribution Board with Metallic Double Door, busbar etc. complete similar to Legrand Cat. No. 507612 with 8 Nos. 6-20 Amp. SP MCBs as per circuit load fitted in Box as directed.
ETPN Distribution Boards( LDB/ PDB/ADB/ PLDB )-
4 Way Three Phase & Neutral Distribution Board with Metallic Double Door, busbar etc. complete similar to Legrand Cat. No. 507670 with 12 Nos. 6-20 Amp. SP MCBs as per circuit load fitted in Box as directed.
6 Way TPN Distribution Board with Metallic Double Door, busbar etc. complete similar to Legrand Cat. No. 507671 with 18 Nos. 6-20 Amp. SP MCBs as per circuit load fitted in Box as directed.
8 Way TPN Distribution Board with Metallic Double Door, busbar etc. complete similar to Legrand Cat. No. 507672 with 24 Nos. 6-20 Amp. SP MCBs as per circuit load fitted in Box as directed.
Flexi Distribution Boards ( RDB)
4 Row 14 Modules Distribution Board with Metallic Double Door, busbar etc. complete similar to Legrand Cat. No. 507707 with 4 Nos. 32 Amp. DP RCBOs as incomer & R-Y-B Indicating Lamps & 32 Nos. 6-32 A SP MCBs as per circuit load fitted in Box as directed.
Supplying, erection, connection of following accessories in above existing Distribution Board as directed by Consultant etc. complete.
As Incomer :
i) 32 A/40 A. DP Isolator.
ii) 25 A/32 A (100 mA) DP RCBO/ Hpi RCCB
iii) 25 A. (300 mA) FP RCBO.
iv) 40 A. (300 mA) FP RCBO.
v) 40 A. FP Isolator.
vi) 40 A. (100 mA) FP RCBO.
vii) 63 A. FP Isolator.
viii) 63 A. (100 mA) FP RCBO.
Voltage surge Protector 2 Pole for Imax-40 kA,UP-1.4 kV.
Supplying & erecting following accessories in MS / PVC enclosure as directed etc. complete.
6-32 A. DP MCB
32 A. FP MCB
40-63 A. FP MCB
Supplying & erecting metal plug socket ( 2P + E) with 10 A SP MCB as per Legrand Cat. No. 507810 . The cost includes necessary interconnection with provided wiring as directed etc. complete.
Supplying & erecting metal plug socket with 32 A FP MCB as per Legrand Cat. No. 507822 . The cost includes necessary interconnection with provided wiring as directed etc. complete.
EARTHING & CHAMBERS :-
Providing & installation of Pipe in Pipe Type GI electrode of size 80 mm dia. with copper terminal strip , 3 Meter in length with 75 Kg. of Excel Grounding Mineral compound (Earth Grip) etc. complete as per IS 3043. ( Note- The earth pit numbers to be painted in yellow/ black oil paint & Earth Test Report to be submitted alongwith it. )
Supplying & erecting watering chamber / cable chamber of size 450 x 450 x 600 mm. deep with 230 mm. burnt bricks in cement morter (1:6) with 300 x 300 x 300 x 80 mm. thick precast RCC removable cover plate etc. complete.
Supplying , laying & connecting following earthing strips with Heat shrinkable sleeves / PVC flexible copper wires for various panels / machines / alongwith cables on cable trays. The cost includes necessary connection with brass nut bolts with main earthing etc. complete. The cost includes brazing for copper strips as directed.
50 x 6 mm. GI strip .
30 x 5 mm. GI strip
25 x 5 mm. Copper strip with PVC sleeve
No. 14 to 8 SWG Copper wire
10 sqmm PVC flexible Copper wire in suitable size PVC Conduit
16 sqmm PVC flexible Copper wire in suitable size PVC Conduit
SUB-MAIN WIRING :-
Providing & drawing following PVC FRLS single core 1100 V. PVC insulated, copper conductor wire in FRLS PVC 2 mm. thick pipe ( MMS Type) mentioned below with necessary M.S. junction / wireway boxes, in a concealed manner, including providing & laying the pipe on slab, cutting the wall embedding the pipe etc. complete as directed.
2 x 1.5 sq. mm. in existing conduit for Inverter wiring.
2 x 1.5 sq. mm. + 1 x 1 sq. mm. PVC wire in 25 mm. dia. conduit.
2 x 2.5 sq. mm. + 1 x 1 sq. mm. PVC wire in 25 mm. dia. conduit.
2 x 4 sq. mm. + 1 x 2.5 sq. mm. PVC wire in 25 mm. dia. conduit.
2 x 6 sq. mm. + 1 x 2.5 sq. mm. PVC wire in 25 mm. dia. conduit.
3 x 6 sq. mm. + 1 x 2.5 sq. mm. PVC wire in 25 mm. dia. conduit.
4 x 6 sq. mm. + 1 x 2.5 sq. mm. PVC wire in 32 mm. dia. conduit.
5 x 6 sq. mm. + 1 x 2.5 sq. mm. PVC wire in 32 mm. dia. conduit.
4 x 10 sq. mm. + 2 x 4 sq. mm. PVC wire in 32 mm. dia. conduit.
5 x 10 sq. mm. + 2 x 4 sq. mm. PVC wire in 32 mm. dia. conduit.
4 x 16 sq. mm. + 2 x 6 sq. mm. PVC wire in 32 mm. dia. conduit.
FEEDER CABLES :- ( Note-1) The cable will be supplied by owner, 2) The contractor must finalize the route of the cable at site & accordingly exact lengths to be given,. 3) The cables must have aluminium tags with its size at both ends) Laying following LT PVC / XLPE armoured copper / aluminium cable 1100 V Grade with ISI mark Standard / solid aluminium with 6 mm. thick 25 mm. width M.S. spacers & G.I. saddles screwed, with continuous 12 / 8 SWG G.I. earth wire complete on wall/ ceiling /lift well or on cable tray with 25 x 3 mm. M. S. clamps / in provided pipe in an approved manner.
COPPER CABLES :-
3 core 2.5 sq.mm. 2XWY / 2XFY cable.
4 core 2.5 sq.mm. 2XWY / 2XFY cable.
4 core 4 sq.mm. 2XWY / 2XFY cable.
4 core 6 sq.mm. 2XWY / 2XFY cable
4 core 10 sq.mm. 2XWY / 2XFY cable.
4 core 16 sq.mm. 2XWY / 2XFY cable.
4 core 50 sq.mm. 2XWY / 2XFY cable.
ALLUMINIUM CABLES :-
4 core x 16 sq.mm. A2XFY cable
4 core x 25 sq.mm. A2XFY cable
3.5 core x 35 sq.mm. A2XFY cable
3.5 core x 70 sq.mm. A2XFY cable
3.5 core x 95 sq.mm. A2XFY cable.
3.5 core x 185 sq.mm. A2XFY cable .
3.5 core x 240/300 sq.mm. A2XFY cable .
END TERMINATION WORK & CABLE TRAYS
Providing end termination work for following 1100 V grade copper aluminium armoured PVC cables with double compression type brass glands & crimping bimetallic lugs as per standard method etc. complete.
COPPER CABLES :-
3 core 2.5 sq.mm. YWY/YFY cable.
4 core 2.5 sq.mm. YWY/YFY cable.
4 core 4 sq.mm. YWY/YFY cable.
4 core 6 sq.mm. YWY/YFY cable
4 core 10 sq.mm. YWY/YFY cable.
4 core 16 sq.mm. 2XWY / 2XFY cable.
4 core 50 sq.mm. YWY/YFY cable.
ALLUMINIUM CABLES :-
4 core x 16 sq.mm. A2XFY cable
4 core x 25 sq.mm. A2XFY cable
3.5 core x 35 sq.mm. A2XFY cable
3.5 core x 70 sq.mm. A2XFY cable
3.5 core x 95 sq.mm. A2XFY cable.
3.5 core x 185 sq.mm. A2XFY cable .
3.5 core x 240/300 sq.mm. A2XFY cable .
Supplying & erecting of readymade type hot dipped GI Ladder type cable trays of various sizes including necessary coupler plates & nut bolts for earth termination at every 10 meters & accessories. The cost includes necessary fixing arrangement with 50 x 50 x 6 mm. / 75 x 75x 6 mm. Angles/ 75 mm. channel/ Anchor fastners with G.I. hangers to ceiling / wall /steel column etc. complete as directed (Note- The cable tray length includes all above fixing arrangements unless mentioned).
300 x 75 mm. Size & 14 SWG Thickness.
600 x 100 mm. Size & 12 SWG Thickness
Supply & erection of readymade 'C' type hot dipped Galvanised Perforated cable trays without Cover of various sizes vertically / horizontally mounted including necessary coupler plates & nut bolts for earth termination at every 10 meters & accessories . The cost includes necessary fixing arrangement with 50 x 50 x 6 mm. / 75 x 75x 6 mm. Angles/ 75 mm. channel/ Anchor fastners with G.I. hangers to ceiling / wall /steel column etc. complete as directed ( Note - The cable tray length includes all above fixing arrangements unless mentioned).
50 x 50 mm. Size & 16 SWG Thickness.
100 x 50 mm. Size & 16 SWG Thickness.
200 x 50 mm. Size & 16 SWG Thickness.
Supplying of MS Chequred plate on cable trench wherever necessary made with 6 mm. thick MS plate & 50 x 50 x 6 mm. angle fixed at the bottom including painting with 2 coats of red oxide primer & 2 coats of black synthetic enamel paint etc. complete.
Providing trench of size 450 mm. x 600 mm. deep including excavation in soft strata laying the various cables / pipes, refilling, cleaning the site etc. complete.The cost includes necessary sand & bricks to cover the cable as per standard practice etc. complete.
Supplying & erecting, lowering, laying 150 mm. dia. NP2 class tested R.C.C. Hume pipe with suitable alignment grade, fixing with collers in cement mortar (1:1). The cost includes necessary excavation, back filling, compaction testing etc. complete.
POINT WIRING :- CONCEALED TYPE WIRING IN PVCCONDUITS :- ( FRLS wire with Modular switches in FRLS Conduits ) ( Important Notes :- 1) Use white switches/ sockets for Raw Power points & Black switches/ sockets for UPS power points 2) If the wall chasing done after final plastering of wall ; the necessary rework cost will be reimbursed from Electrical Contractor ).
Providing wiring for a Light / Exhaust Fan Point with 1 sq. mm. 'FRLS' PVC insulated, copper conductor wire of 1100 V. grade in FRLS Conduit of 25 mm. dia. 2 mm. thick in concealed manner/ above false ceiling including providing & laying FRLS PVC pipe( MMS Type) on the slab with deep M.S. junction boxes, cutting the wall & providing the chase in the wall . Providing necessary M.S. / wireway boxes / conduit accessories flush type wiring accessories erected in a concealed type M.S. box covered with Modular front plate with 6 A. one way modular switch, ceiling rose/ angle holder & 18 gauge powder coated enamel painted MS round plate for covering ceiling outlet etc. complete ( Light Points - 1027, Ex. Fan Points - 43) ( Avergare Point Length= 7.5 Mtr)
Ditto-ditto but extra long point ditto-ditto etc. complete (Point upto 20 mtr. Avg. length)
Ditto-ditto but for a two way light point / bell point ditto-ditto etc. complete
Ditto-ditto but for a ceiling fan point with steplace to accommodate stepped fan regulator on switchboard ditto-ditto etc. complete.
Ditto-ditto but for a 6 Amp. two in one plug socket & 6 A. switch at isolated position & wiring with 1.5 sqmm PVC copper FRLS wire & 1 sq.mm wire as running earth ditto-ditto etc. complete.
1 plug socket & 1 switch.
2 plug sockets & 2 switches.
Ditto-ditto but for a 6 Amp. two in one plug socket & 6 A. switch at isolated position & wiring with 2.5 sqmm PVC copper FRLS wire & 1 sq.mm wire as running earth ditto-ditto etc. complete.
3 plug sockets & 3 switches.
4 plug sockets & 4 switches.
Ditto-ditto but for a 6 A. plug point with two in one plug socket (5 pin) & switch on the same lighting board position, etc. complete.
Ditto-ditto but wiring for 16 A ( combined 6/16 A) power plug point with 2.5 sq. mm. FRLS PVC copper wire & 1 sq. mm. PVC FRLS copper wire as running earth ditto-ditto etc. complete. The cost to include 16 A plug socket & switch & circuit wiring from DB etc. complete.
1 No. 16 A plug socket & 16 A Switch.
2 Nos. 16 A plug sockets & 2 Nos.16 A Switches.
Providing wiring for a Geyser (Boiler) point with 4 sq.mm. FRLS PVC insulated copper conductor wire & 2.5 sq. mm. wire as Running Earth etc. complete. The Cost includes 16 A Plug socket & 20 A D.P. switch with Indicator etc. complete.
Providing wiring for a A/c point with 4 Sq. mm. FRLS PVC copper wire & 1.5 Sq. mm. FR PVC copper wire as running earth & 16/32 A SP MCB/ Modular starter/ 20 A DP SWitch with Indicator & 20 A Industrial Plug socket / 16 A Plug socket etc. complete ( Note - The Cost of the wiring includes wiring from DB to point & from point to Control station near Entry door ) ( Avg. point length = 20 Mtr. )
Providing & erecting following switches / MCBs etc. complete as directed. 6 A./ 10 A. SP MCB in PVC box / 32 A. DP switch with Red Indicator fixed on concealed MS box as a Master OFF outside the room. The cost includes necessary interconnection with existing wiring etc. complete.
Providing & fixing Red Indicator on existing lighting switchboard as directed.
Providing cross holes across beam / walls & repairing it as original as directed.
Supplying & erecting following 6 A /16 A two in one plug socket & 6 A/ 16 A. switch at various positions with cover plates on wall with MS co-Box as directed & the cost include interconnection with provided UPS wiring of size 1.5 sqmm / 2.5 sq.mm / 4 sq.mm PVC copper FRLS wire & 1 sq.mm wire/2.5 sqmm as running earth ditto-ditto etc. complete. (NOTE :-UPS plug socket & Switches to be of Black in colour)
1 No. 6 A plug sockets & 1 No. 6 A switch.
2 Nos.6 A plug sockets & 2 Nos.6 A switches.
3 Nos. 6 A plug sockets & 3 Nos. 6 A switches.
1 No. 6/16 A plug socket & 1 No. 6/16 A switch.
2 No. 6/16 A plug socket & 2 No. 6/16 A switch.
5 No. 6/16 A plug socket & 5 No. 6/16 A switch.
Supplying & erecting Watertight IP 55 Plexo Boxe & adaptor as per Legrand Cat. No. 680613 with 6 A plug & 6 A socket etc. complete. The cost includes necessary termination with provided wire / cable.
SURFACE TYPE CONDUIT / CASING WIRING :- (with Modular type switches) : ( AT- BASEMENT)
Providing wiring for a light point / Exhaust fan point / isolated plug point with 3 x 1 sq. mm. FRLS PVC copper conductor, 1100 V. grade wire in 2 mm. thick 25 mm. wide PVC casing capping / 20 mm. dia. PVC conduit with flush type wiring accessories such as ceiling rose / batten holder / 6 A. Modular switch erected on surface mounted box/ formica facing double T.W. block. etc. complete as directed.
Ditto-ditto but ceiling fan point with step regulator etc. comp.
LOW VOLTAGE WIRING :- ( DATA/ VOICE / CCTV / SPEAKER WIRING )
Supplying & laying of UTP CAT–6 , 4 pair solid cable in provided PVC conduit etc. complete as directed.( Note- Separate colour wire to be used for LAN, Telephone, CCTV & Nurse Call Bell system)
Supplying & laying of 75 Ohm., RG-6 Air space Co-axial cable for Cable TV in concealed manner in provided PVC conduit etc. complete as directed.
Supplying & laying of 40 / 0.0076 extra thick flexible 2 core unarmoured copper wire/cable for speaker points in suitable size PVC MMS FRLS conduit / 25 mm wide casing capping etc. complete as directed. ( The cost includes conduit / casing -capping)
Supplying & laying of 14 / 0.0036 shielded cable for interconnection for Microphone & Amplifier ditto-ditto etc. complete as directed. ( The cost includes conduit / casing -capping)
Supplying & laying following I.T.D. approved 0.5 mm. size unarmoured Telephone cable in provided concealed PVC conduit
2 pair cable.
5 pair cable.
10 pair cable.
Supplying & laying I.T.D. approved copper conductor armoured 100 pair jelly filled cable.B192
Supply & erection of telephone junction box. The TJB shall be made as per Krone type eboxy powder coated MS box with SS frame & lock. Disconnection type modules for 10 pair each mounted on SS frame
10 pair Strip Box.
20 pair Strip Box.
100 pair Strip Box.
Supplying & erecting following in a concealed MS box with Modular front plate as directed. The cost includes necessary end termination with provided wiring etc. complete as directed.
RJ-11 Telephone jack for Intercom & Telephone points.
RJ-45 computer socket / single port CAT-6 information outlet
Microphone / Speaker socket
Volume controller / off switch for speaker
INSTALLATION OF BED HEAD PANELS - (NOTE :-Bed Head Panels with Switch & sockets will be provided by owner.)
Installation, testing & commissioning following type Bed Head Panels supplied by Owner. The cost includes necessary end termination with provided wiring etc. complete as directed.
INSTALLATION OF LIGHT FIXTURES & FANS :- (NOTE-Light Fixtures & Fans will be supplied by Owner)
Erecting, connecting & commissioning LED / incandescent fittings & fixtures with 3 core x 1 sqmm unarmoured flexible copper white cable on appropriate size painted T.W. block / PVC block etc. complete as directed.
LED fittings directly to ceiling/wall/column.
LED downlighter / ceiling speaker in false ceiling.
2' x 2' LED Panels in false ceiling.
Ceiling fans/ railway type ceiling mounted fan
Exhaust fan with M.S. bracket/ wall mounted ceiling fan
Supplying & erecting following sundry materials etc. complete as directed.
19 mm. dia. HGBE screwed painted conduit M.S. pipe with necessary cutting, threading, painting etc. complete for a fixtures as directed.
Chain for suspension of fittings with necessary hook.
Fastener / fan hook for the ceiling fan / chandelier & making the good the ceiling as original.
Supplying & erecting Bell / Buzzer / Ding-Dong bell / Bell Indicators with double coil suitable for 230 V. complete erected on Formica block etc. complete.
LIGHTENING ARRESTOR PROTECTION :-
Supplying & erecting ‘Trishul’ type Lightening Arrestor with Gunmetal bowl, copper spikes & brass rod 3 mtr. long & it on the roof with necessary material etc. complete.
Supplying & erecting following GI tape as down & roof conductor with necessary copper GI saddles & spacers from test link to Lightening Arrestor etc. complete.
25 x 3 mm. GI tape.
40 x 6 mm. GI tape.
NANDA ENTERPRISES
Shri Laxmi Electrical
Prashant Enterprise
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .