| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹44.4 LAccepted-Finance | L1 | Accepted-Finance Accepted being L1 | |
| 2 | L2₹48.2 L+₹3.7 L (8.40%)Rejected-Finance | L2 | Rejected-Finance Rejected being L2 | |
| 3 | L3₹50.6 L+₹6.2 L (13.9%)Rejected-Finance | L3 | Rejected-Finance Rejected being L3 | |
| 4 | L4₹50.7 L+₹6.2 L (14.0%)Rejected-Finance BUILDING NO FLAT NO 19 6TH CROSS ROAD SANJEEVINI NAGAR MUDALAPALYA BANGALORE 560072 | BANGALORE | BANGALORE | KARNATAKA | 560072 | L4 | Rejected-Finance Rejected being L4 | |
| 5 | L5₹51.7 L+₹7.3 L (16.4%)Rejected-Finance NO 422 CHURCH STREET NEW THIPPASANDRA BANGALORE 560075 | BANGALORE | BANGALORE | KARNATAKA | 560075 | L5 | Rejected-Finance Rejected being L5 |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
20 Mar 2023, 6:00 pmClosed
GE I RD East Bangalore
GE I RD East Bangalore 93
REPAIRS REPLACEMENT OF UNSERVICEABLE DISTRIBUTION BOARD MAIN SWITCHES SOCKETS LED LIGHT FITTINGS REWINDING OF EXHAUST CEILING WALL MOUNTING FAN FIRE SAFETY WORKS AND OTHER ALLIED WORKS AT ADE DEBEL UNDER GE I R D EAST BANGALORE
2023_MES_582952_1
8347
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE I RD East Bangalore
D b (i)
9 documents required · 9 mandatory
₹500
Yes
GE I R AND D East Bangalore
₹96,000
Yes
24 Mar 2023
25 Feb 2023
22 Mar 2023
25 Feb 2023
20 Mar 2023
11 Mar 2023
27 Feb 2023 - 6 Mar 2023
Amount
M & L for earthing complete with copper earth plate electrode 60cm x 60cm x 3.15mm thick buried directly in ground (earth pit not less than 3 mtr deep below ground level) with top edge of the plate not less than 2.10 mtr below normal ground level, connected to and including copper earth strip of 32x6 mm by means of rivetting and brazing and protected by GI pipe light grade of suitable size up to the test point i.e. up to 7.5 mtr, including providing alternate layers up to full volume of pit by charcoal dust and common salt, all around the plate 15 cm depth and width minimum including PCC pit chamber, watering pipe of 50mm dia medium grade GI pipe up to the top of the plate having funnel complete and RCC cover, connecting to the test point and testing on ground complete and including excavation and earth work in any type of strata and cleaning of site all as specified in MES SSR Part-I and directed by Engineer-in-Charge.
M & L for chemical earthing complete with copper earth plate electrode 90cm x 60cm x 5mm thick buried directly in ground (earth pit not less than 3 mtr deep below ground level) with top edge of the plate not less than 2.10 mtr below normal ground level, connected to and including copper earth strip of 32x6 mm by means of rivetting and brazing and protected by GI pipe light grade of suitable size up to the test point i.e. up to 7.5 mtr, including providing alternate layers up to full volume of pit by charcoal dust and common salt, magnesium sulphate & vegetable soil all around the plate 15 cm depth and width minimum including PCC pit chamber, watering pipe of 50mm dia medium grade GI pipe up to the top of the plate having funnel complete and RCC cover, connecting to the test point and testing on ground complete and including excavation and earth work in any type of strata and cleaning of site all as specified in MES SSR Part-I and directed by Engineer-in-Charge.
M & L for copper earth continuity main earthing Strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit of size 20 x 3 mm all as specified and directed.
M & L for sub main wiring with four single core PVC insulated unsheathed , 1100 Volts grade, copper cable 4x10.0 sq. mm stranded conductor and drawing through and including rigid PVC non metalic surface conduit of suitable size with conduit accessories such as junction boxes, bends, tees etc. including continus earth wire PVC insulated unsheathed 1100 volts grade, one run of cable 10 sqmm copper conductor and connected to common earth dolly complete as directed including taking down old submain wiring Note :-(i) One run of PVC conduit, 5 runs of cable shall be measured and paid as one unit.
All as pr item No- 04 but 4 x 6.0 Sqmm + 01 x 6 Sqmm wire as earth wire all as specified and directed
All as per item No-04 but 4 x 2.5 Sqmm + 01 x 2.5 Sqmm as earth wire all as specified and directed
All as per item No-04 but 4 x4 Sqmm + 01 x4 Sqmm as earth wire all as specified and directed
All as per item No-04 but 2 x10 Sqmm + 01 x 10 Sqmm as earth wire all as specified and directed. Note :-(i) One run of PVC conduit, 3 runs of cable and one run of earth wire shall be measured and paid as one unit.
All as per item No-08 but 2 x6 Sqmm + 01 x 6 Sqmm as earth wire all as specified and directed. Note :-(i) One run of PVC conduit, 3 runs of cable and one run of earth wire shall be measured and paid as one unit.
All as per item No-08 but 2 x4 Sqmm + 01 x 4 Sqmm as earth wire all as specified and directed. Note :-(i) One run of PVC conduit, 3 runs of cable and one run of earth wire shall be measured and paid as one unit.
All as per item No-08 but 2 x2.5 Sqmm + 01 x 2.5 Sqmm as earth wire all as specified and directed. Note :-(i) One run of PVC conduit, 3 runs of cable and one run of earth wire shall be measured and paid as one unit.
S & fix in Replacement of Distribution Board, SPN 12 way, 240V, double door type including making all connection as per existing.
S & fix in Replacement of Distribution Board, SPN 8 way, 240V, double door type including making all connection as per existing.
S & fix in Replacement of Distribution Board, SPN 4 way, 240V, double door type including making all connection as per existing.
S & fix in Replacement of Distribution Board, TPN 4 way, 415 V, type. Double door type including making all connection as per existing.
S & fix in Replacement of Distribution Board, TPN 6 way, 415V, type. Double door type including making all connection as per existing.
S & fix in Replacement of Distribution Board, TPN 8 way, 415V, type. Double door type including making all connection as per existing.
S & fix in Replacement of Distribution Board, TPN 12 way, 415V, type. Double door type including making all connection as per existing.
Supply and fixing of MCB, SP, 240V, upto 6 to 32 Amp 10KA rupturing capacity, 230 Volts
Supply and fixing of MCB, SPN, 240V, upto 32 Amps 10KA rupturing capacity, 230 Volts
Supply and fixing of MCB, SPN, 240V, upto 40 TO 63 AMP Amps 10KA rupturing capacity, 230 Volts
Supply and fixing of MCB, TPN, 415V, upto 16 TO 32 Amps 10KA rupturing capacity 415 Volts
Supply and fixing of MCB, TPN, 415V, upto 40 to 100 Amps 10KA rupturing capacity, 415 Volts
Dismantalling of existing RCC/steel pole by breaking/ removing, Supply and fixing of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts screws and washers as specified type of 410 SP - 31 (9.00 meters long)
M&L for Cement concrete 1:4:8, type D-2 ( using 40mm graded stone aggregate) as in foundations, filling and mass concrete for PCC pole complete all as specified and directed.
M&L for Cement concrete 1:3:6, type C-2 ( using 20mm graded stone aggregate) as in coping,/suface foundation filling and mass concrete for PCC pole complete all as specified and directed.
Supply and fixing DLP U-PVC Cable trunking systems and acessories snap on trunking 80 x 50 mm supplied without cover, Legrand Cat no : 010412 80mmx50mm PVC Trunking
Supply and fixing of Flexible cover only, full cover size width 65 mm suitable for 80mmx50mm PVC Trunking Make : Legrand Cat no. : 010521
Removing the existing unserviceable PVC junction boxes supply and fix PVC enclosure (140 mm x 140mm x 95mm) weather, dust and, rain guarded, cable entry and exit arrangement of suitable size of housing of with 01 No MCB SP 10 Amps including nuts, bolts clamps for fixing to pole, including end termination of cables of size 25 / 35 sqmm 2 Nos in each box complete all as directed. Make : Sintex, model GSJB-1414
Supply and Fixing in repairs Street light fitting, LED street light fitting made of pressure die casting cast aluminium housing with heat resistant toughened glass and IP66 protection of 60 watts capacity including LEDs including all necessary fitting accessories and prewired complete all as specified and as directed.
All as per item No -30 but of cap 70 W
All as per item No 30 but building security light of cap 35 W
All as per item No -30 but of cap 90 W
Supply & Fixing in repairs LED Bollard light fitting, IP65, 9 Watts
Supply and fix circular led highbay light with tapered design and excellent thermal management alongwith IP 66 protection suitable for hanger/technical building of cap 120 watt of 130 Lm/Watt
Dismantling the ceiling fan complete of any type and size , cleaning, servicing, greasing to bearings checking of nuts bolts , safety split pin, bushes , capacitor and complete spray painting as directed by Engr-in- charge testing all as directed. Note :- Expendable stores like cotton waste/cleaning materials, grease, lubricants, machine screws, safety split pin, bots/nuts and transportation to and from site to work place are deemed to be included in rate quoted.
Dismantling all components of ceiling fan 1200mm sweep, cutting and removing burnt out copper winding from the rotor assy and rewinding with super enamelled copper winding wire of suitable gauge and turns with necessary insulation materials , varnishing, reassembling , greasing to bearing , replacing bushes, replacment of capacitor and complete testing all as directed. Note:- (a) The spares like ball bearing, capacitor and GM bush required for repair the ceiling fan will be measured and paid separately under respective item. (b) Expendable stores like cotton waste /cleaning materials, grease, lubricants, machine screws, safety split pin, bolts, nuts and transportation to and fro from site to work place are deemed to be included in rate quoted.
All as per item No 37 herein before but for 1400mm sweep ceiling fan
All as per item No 37 herein before but for upto 300mm sweep exhaust fan
All as per item No 37 herein before but for 300 mm to 450mm sweep exhaust fan
Supply and replace worn out fan bearings suitable for ceiling fan /exhaust fan of the existing size of superior quality complete all as specified and directed
Supply and replace capacitor 2.5mfd suitable for 1200/1400 mm sweep ceiling fan complete all as specified and directed
Supply and replace capacitor 4.0mfd suitable for exhaust fan complete all as specified and directed
S & Replacement of GI bracket for street lights made out of light grade GI pipe 50mm dia, 3.0 mtr long bend to shape as directed, fixed on poles with MS clamp flat iron suitable for RCC rectangular/steel tubular pole with nuts, bolts and washers and all as specified and directed.
Perodical checking & testing, normal and routine maintenance including cleaning of all parts and carry out corrective maintenance, attending to complaints on call repair and replacement of spares for fire alarm system of make and model for the following areas at ADE and all as specified and directed and specified( Periodical will be checked by quaterly in a year) (i) SANCHAR Building, USD Bldg, Simulation bld, & Falcon Bldg , : Fire alarm panel servicing and clearing faults, checking cable continuity, troubled sensor servicibility of parts Sensor's/MCP's/Hooter's/ RI's batteries etc. Note : Spares required to maintain the fire alaram system will be measured and paid seperately.
All as per item No 45 above, but in debel new bldg /old bldg all as specified and directed.
Supply and fixing in repairs Conventional Smoke Detector with Baselow profile design,Low current draw, Wide opening voltage 8 to 30 V DC, Bi - colour LED detectorstatus indicator, tested and approved to EN54. Make : System Sensor, 2351E
Supply and fixing in Repairs Conventional manual call point,Break glass unit, Alaram status is indicated by Red Colour LED, 24 DC.
Supply and fixing in Repairs Conventional Hooter, Wall mount, 24 v dc, operating current 40mA, Piezo Electric Type.
Supply and fixing in Repairs Battery 12V, 7AH MAKE : EXIDE
Supply and fixing in Repairs Conventional Response Indicators 24 V DC all as per specified and directed
Supply and fixing 2 Core x 1.50 Sq. mm sheathed cable with PVC insulated with multi strand heavy duty copper conductor cable.
Supply and fixing 19mm PVC conduit with accessories.
Supply and fixing in repairs Electric/Zone /Module unit cards as per exisitng all as specifie and directed
Supply, Test, Install and Commissioning of Repeater Control Panel as per existing all as specified and directed
M & L for Repairs to the Fire Alarm system by Servicing/ Caliberation all as specified and directed.
Supply and fix in replacement of Manual Call Point : Checking the wiring circuits, glass LED etc all as specified and directed.
Caliberation and functioning of the Smoke detectors / Hooters by cleaning the Sensing chamber and LED fuses and wiring circuits Etc.
Supply and fixing LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complet
Supply and fixing of sheet metal enclosure powder coated, Distribution boards VTPN MCCB 250 Amp DB, double door, Provision of TPN MCCB 125 Amps, 16 ka as Incomer, 12 way, 415V, Double door type IP 43 protection, shrouded Neutral Bar & Pan assembly with flexible link Cement spill protector, Door earthing, complete
Supply and fixing of MCCB of capacity 160 Amp,415V,36 KA,TPN,
Taking down in trenches, fixed on walls, passing through pipes, jointing and testing of electric LT cables, PVC insulated, PVC sheathed, galvanised steel strip or wire armoured electric power cables with stranded aluminium conductors 1100 Volts grade for the following.
2/4 Core 16 Sqmm to 50 Sqmm
Supply and laying in trenches XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area of following size into trenches all as specified and directed.
4 Core 16 Sqmm
4 core 25 Sqmm
4 core 35 Sqmm
3.5 core 50 Sqmm
M&L for sand filling for cable duly filtered the earth cushioning inducing spreading and levelling as directed Note - punned thickness only will be measured and paid
Excavation in trenches n. exc. 1.5m wide and n exc. 1.5m in depth for taking out/laying cables in Hard/dense soil all as directed.
Returning filling in, including, spreading, leveling, watering and well ramming in layers n exc. 25 cm all as directed..
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5m above the starting point all as directed.
Supply and laying of Fire bricks for cable protections of size 230 x 113 x 75 mm.
M&L for steel tubing GI light grade of size 50mm for cable protection, passing under road/floor or for fixing to poles/walls all as specified and directed
Fixing only of LED light fitting / street light fittingsof different type and different rating as per site requirement including provision of flexible copper wire from celing rose to fitting. NOTE : LED light fitting and assesories will be issued from deparmanent (Schedule B) for free for fixing only
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .