| 1 | | Supply of 10KVA capacity, 1 Phase (Input and Output)Modular N+1 module type online UPS of onsite warranty of minimum 03 Years, with 30 minutes full load battery backup facility along with Normal,Battery,Bypass mode of operation and independent battery monitoring system of international standard,reputed brand, make shall be installed along with provision for source selection including Accessories (60 meter Power cable at least 10 sq. mm of 3 core each of Good quality as per ISI standard ), Battery banks with seperate racks, in-built display Units (with Control units and Event log), remote monitoring systems, with Input and Output SPD | 2 | Pieces | VAKP_CNS_AS | 45 |
| 2 | | Batteries (VRLA SMF Type) | 2 | Set | VAKP_CNS_AS | 45 |
| 3 | | Installation Testing commissioning Charges | 1 | Job | VAKP_CNS_AS | 45 |
| 4 | | Supply and Installation of Metalic Distribution Board for the distribution of UPS output, including 63 Amps 1 phase DP MCB as incomer and 32 amps 1pole MCB-02 Nos, 20 amps 1pole MCB-02 Nos and 10 amps 1pole MCB-04 Nos as outgoing, with all Internal and External wirings with suitable rating of Copper wires, Neutral Link, Earth Link, as required | 2 | Job | VAKP_CNS_AS | 45 |
| 5 | | Supply and Installation of Electrial plug point (5,16 Amps Switch socket Combined) along with metal Base to be fixed in wall, including supply and wiring of copper wire for providing Power supply between UPS Output distribution box to Plug point inside the work site, labour Charges, as required. | 14 | Job | VAKP_CNS_AS | 45 |
| 6 | | Supply of 5KVA capacity, 1 Phase (Input and Output)Coventional online UPS (IGBT-PWM based with inbuilt Isolation Transformer ) of onsite warranty of minimum 03 Years, with 30 minutes full load battery backup facility along with Normal,Battery,Bypass mode of operation and independent battery monitoring system of international standard,reputed brand, make shall be installed along with provision for source selection including Accessories(60 meter Power cable at least 6 sq. mm of 3 core each of Good quality as per ISI standard .), Battery banks with seperate racks, in-built display Units (with Control units and Event log), remote monitoring systems, with Input and Output SPD, . | 2 | Pieces | VAKP_CNS_AS | 45 |
| 7 | | Batteries (VRLA SMF Type) | 2 | Set | VAKP_CNS_AS | 45 |
| 8 | | Installation Testing commissioning Charges | 1 | Job | VAKP_CNS_AS | 45 |
| 9 | | Supply and Installation of Metalic Distribution Board for the distribution of UPS output, including 32 Amps 1 phase DP MCB as incomer and 20 amps 1pole MCB-02 Nos, 16 amps 1pole MCB-02 Nos and 10 amps 1pole MCB-04 Nos as outgoing, with all Internal and External wirings with suitable rating Copper wires, Neutral Link, Earth Link, as required. | 2 | Job | VAKP_CNS_AS | 45 |
| 10 | | Supply and Installation of Electrial plug point (5,16 Amps Switch socket Combined) along with metal Base to be fixed in wall, including supply and wiring of copper wire for providing Power supply between UPS Output distribution box to Plug point inside the work site, labour Charges, as required. | 12 | Job | VAKP_CNS_AS | 45 |