Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹13.3 LAccepted-AOC | 1 | Accepted-AOC Lowest | |
| 2 | 2₹14.9 L+₹31,100 (2.14%)Rejected-AOC | 2 | Rejected-AOC 2nd | |
| 3 | 3₹15.6 L+₹1.1 L (7.31%)Rejected-AOC | 3 | Rejected-AOC 3rd | |
| 4 | 4₹15.8 L+₹1.3 L (8.59%)Rejected-AOC | 4 | Rejected-AOC 4th | |
| 5 | 5₹17.1 L+₹2.6 L (17.7%)Rejected-AOC A 93 SECTOR 36 GREATER NOIDA GAUTAM BUDDHA NAGAR UTTAR PRADESH 201308 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201308 | 5 | Rejected-AOC 5th |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
28 Aug 2021, 6:00 pmClosed
GE AF TUGHLAKABAD
GE AF TUGHLAKABAD SANGAM VIHAR PO NEW DELHI 110080
Repair / Maint of STP and sewage installation at 7 BRD under GE(AF) Tughlakabad
2021_MES_464531_1
GE/TKD/TOKEN-27/2021-22
Open Tender
Civil Works - Others
Item Rate
270 days
GE AF TUGHLAKABAD
MES contractor enlisted as Class E or above category aii and bi having deposited Standing Security of Rs. 50000 with dept. Contractors not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category
8 documents required · 8 mandatory
₹500
GE AF TUGHLAKABAD
₹50,000
Yes
8 Apr 2022
2 Aug 2021
30 Aug 2021
12 Aug 2021
28 Aug 2021
12 Aug 2021
Amount
Periodical cleaning of equalizing tank/grit chamber/oil grease chamber/stiling chamber of Sewage water and removing by scrapping with wire brush or any other means from walls and bottom of tank and removing the sludge/silt/fungus deposited inside the sumps and tank with buckets and depositing where directed including removing media of settled down and making good the disturbed surfaces of walls internally or externally in cement mortar 1:3 as required and followed by cleaning with bleaching water solution and fresh water and finnaly applying one coat of snowcem on internal and external surfaces including writing the date of cleaning and due date of cleaning in white colour on black background on external walls complete all as specified and directed by Engr-in-charge. (Location: 7BRD STP and capacity 250/300 KLD.) Note: The rate quoted by the tenderer is deemed to be included in the unit rate for the following aspects:- (a) Diesel driven pump set of appropriate caqpacity with operators including necessary POL required at site for de-watering of sewage septic water including PVC heavy duty flexible hose pipe for suction and delivery purpose.
Contd srl item No 1.00: (b) Lorry or tractor mounted storage tank of appropriate capacity not less than 3 KL should be used for disposing off the same to the location where apporoved by the MCD. (c) Necessary oxygen mask, gloves, gum boot and all other safety aspects to be observed including necessary Phawda, Steel Bucket, Manila rope etc required at site shall be arranged by the contractor.
-Ditto- all as per sl item No 1 but for cleaning of MBBR-1 and MBBR-2 of sewage treatment plant.
-Ditto- all as per sl item No 1 but for cleaning of tube settler /lamella clarifier of sewage treatment plant.
-Ditto- all as per sl item No 1 but for cleaning of treated water tank with chemical contact tank of sewage treatment plant.
M&L for cleaning and desilting the sewage well of capacity and dewatering the well of 100 to 125 cubic metre removing all the deposited sludge, soil and other material from the well including bailing/pumping out muddy water from the well by manually or by providing suitable pump sets from bottom level of well, scrapping out the scales/deposits from inner surface of the well thoroghly, washing with bleaching powder and soda ash, cleaning/bailing out settled materials completely by any means and removing sludge to a distance upto 3 KM outside of defence land limit and dispose off in low lying area including dewatering as required complete all as specified and directed by Engr-in-Charge. Note: (i) Contractor is to arrange own diesel pump, T&P for cleaning purpose and minor spares and consumables like small screws, washers, cleaning agents consumables and safety measures taken while working in lift well shall be deemed to be included in the cquoted rate. (ii) The accumulated or deposited sludge after drying shall be disposed off outside the defence land to a distance exceeding 1.5 KM and not exceeding 5 KM form the lift well and cost of which shall be deemed to be inclusive in the quoted rate. (iii) Before commencement of work necessary arrangement for disposal of sewage/sludge be made and work to be carried out in fast pace by depolying more man power at lift well in order to complete the work at the earliest.
Supply only AQUAFIT-CHLORINE, 65%-70% (Calcium based granular disinfectant for water treatment, more stable than chlorine gas and stronger than bleaching powder and sodium hypochlorite) in 45 kg drum complete all as specified and directed by Engr-in-charge. Make: Sree Rayalaseema/HI-Strength HYPO Ltd
M&L for replacement of unserviceable MBBR media from the tank and supply of filling fresh media of MBBR media in the main reactor as specified of existing and suitable make with the following specifications complete all as specified and as directed by Engr-in-Charge:- (a) Effective surface area of media approx: 400 Sqm/Cum (b) Media hieght approx: 15/10 mm (c) Media dia appros: 22 mm (d) Weight per unit surface area approx: 22 mm (e) Voidage: > 93 grams per cubic centimetre (f) Media fill range: 25-55% of volume.
M&L in replacement of Hybrid Bio-Cultured (Synthetic Bacteria) suitable for STP of capacity 250/300 Cum/day complete all as specified and directed by Engr-in-Charge.
M&L for in replacement of activated carbon IV 1000 complete all as specified and directed by Engr-in-Charge.
Supply and mixing of dewatering poly electrolyte of 100% purity complete all as specified and directed by Engr-in-Charge.
Supply and mixing of calcium hydro-oxide (Lime, 80-85%) in powder form as pH booster for STP water, packing in 40 Kg packs complete all as specified and directed by Engr-in-Charge.
Supply and mixing of ortho tolidin solution for testing of dissolved chlorine in water complete all as specified and directed by Engr-in-Charge.
Supply and mixing of chlorination testing glass test tube kit complete all as specified and directed by Engr-in-Charge.
Supply and mixing of alum ferric of grade-4 best quality as per sample, for purification of water containing lead (as PB) 30 ppm max and arsenic 6 ppm max, confirming to IS-299/2012 (revised) as amended upto date complete all as specified and directed by Engr-in-Charge. Note: The alumino ferric sulhate shall be supplied in superior quality bricks or slabs as per IS specifications. Manufactureres name and trade mark shall be engraved on each brick or slab in addition to marking of relavant clause of IS spcifications.
Supply and mixing of bacteria culture areobic in 30 Kg of drum complete all as specified and directed by Engineer-in-Charge.
Supply and mixing of DAP fertiliser for day to day use in sewage treatment plant complete all as specified and directed by Engr-in-Charge.
Supply and mixing of molasses for day to day use in sewage treatment plant complete all as specified and directed by Engr-in-Charge.
Supply and mixing of PAC (Poly Aluminium Chloride) AC 1005 in organic soluble polymer powder packed in 25 Kg poly bag complete all as specified and directed by Engr-in-Charge.
Carrying samples for testing of treated water of STP and submission of detailed test report to the office of the Engr-in-charge for the following aspects:- (a) Carrying out minimum essential testing of water as per IS-3025 & IS-1622 mandatory for chemical, colour, odour, PH value, TSS, BOD, COD, Total residual chlorine, total nitrogen, sulphate, oil and grease, anmmonical nitrogen (NH3-N) and bacteriological total coliform organism per 100 ml (MPN) and ecoli in 100 ml. Contd......
(b) Treated sewage water shall confirm to the following characteristics:- (i) TSS < 10 mg/litre (ii) BOD < 10 mg/litre (iii) COD < 150 mg/litre (iv) Ph: 6.5 to 8.5 (v) Total coliform < 100 MPN/100ml (desired nil) (vi) Residual CI > 1 mg/litre Rest of the characteristics of the treated water shall be as per IS-3025 & IS-1622 Note: Cost of sterlized bottle and to and fro transportation charges for collection of samples shall be included in the quoted rates.
Carrying samples for testing of sewage water as per relevant IS of STP and submission of detailed test report to the office of the Engr-in-charge for the following aspects:- (a) Carrying out minimum essential testing of sewge water as per relevant IS mandatory for chemical, odour, ph value, TSS, BOD, COD, total nitrogen, sulphate, oil and grease, ammonical nitrogen (NH3-N) and bacteriological total colliform organism and other characteristics as per relevant IS of sewage water:- Note: Cost of sterlized bottle and to and fro transportation charges for collection of samples shall be included in the quoted rates.
M&L for painting of all the pipe lines, plant plastered surfaces complete with two coats of synthetic enamel paint with two coats of apex anamel paint complete all as specified and as approved by Engr-in-Charge.
M&L for cleaning, scrapping outside of vessel properly including painting with one coat of zinc chrome primer and two coats of best quality synthetic enamel paint complete all as specified and as approved by Engr-in-Charge.
M&L and testing for coverhauling and repairing of multigrade pressure sand filter incuding replacement of filter media as per existing including other connected assessories as required at site of STP capacity 250/300 KLD complete all as specified and as approved by Engr-in-Charge.
S&F in replacement MCCB of capacity, 400 Amps, 04 pole, 415 Volt, 36 KA Breaking capacity, with adjustable thermal & adjustable magnetic setting complete all as specified and as approved by Engr-in-Charge. Make: Cat No IHLLSEBF0400# of Havells/Cat No 830176 of Indoasian/Cat No CM98404OORO of L&T
M&L in replacement MCCB of capacity, 250 Amps, 04 pole, 415 V, 36 KA Breaking capacity, with adjustable thermal & adjustable magnetic setting complete all as specified and as approved by Engr-in-Charge. Make: Cat No IHLFNF0250# of Havells/Cat No 830117 of Indoasian/Cat No CM98065OOPO of L&T
M&L in replacement MCCB 200 A, 4 Pole, 415 V, 36 KA Breaking capacity, with fixed thermal magnetic release complete all as specified and as approved by Engr-in-Charge. Make: Cat No IHLFNF0200# of Havells/Cat No 830116 of Indoasian/Cat No CM98065OONO of L&T
M&L in replacement MCCB 100 A, 4 Pole, 415 V, 25 KA Breaking capacity, with fixed thermal magnetic release complete all as specified and as approved by Engr-in-Charge. Make: Cat No IHLGNT0100# of Havells/Cat No 830008 of Indoasian/Cat No CM90517OOKO of L&T
M&L in replacement MCCB 63 A, 4 Pole, 415 V, 16 KA Breaking capacity, with fixed thermal magnetic release complete all as specified and as approved by Engr-in-Charge. Make: Cat No IHLGNT0063# of Havells/Cat No 830006 of Indoasian/Cat No CM90517OOHO of L&T
Dismantling the unserviceable part of 250/300 KLD capacity sewage treatment compressor blower and replace with new one including testing after completion all as specified and directed by Engr-in-charge.
S&F in Replacement Suction filter suitable for sewage treatment 250/300 KLD compressor blower complete all as specified and as approved by Engr-in-Charge. Make: Everest or equivalent ISI marked.
S&F in Replacement bearing of size 6306 for sewage treatment 250/300 KLD compressor blower complete all as specified and as approved by Engr-in-Charge. Make: Everest or equivalent ISI marked.
S&F in Replacement gears of size 125mm dia with Hub complete with hardware suitable for sewage treatment 250/ 300 KLD compressor blower complete all as specified and as approved by Engr-in-Charge. Make: Everest or equivalent ISI marked.
S&F in Replacement V- Belt of size 50 suitable for sewage treatment 250/300 KLD compressor blower complete all as specified and as approved by Engr-in-Charge. Make: Everest or equivalent ISI marked.
S&F in Replacement gear oil No-90 suitable for sewage treatment compressor blower complete all as specified and as approved by Engr-in-Charge. Make: Castrol or equivalent ISI marked.
S&F in Replacement oil seal and gasket set suitable for sewage treatment compressor blower for 250 KLD capacity complete all as specified and as approved by Engr-in-Charge. Make: Everest or equivalent ISI marked.
S&F in Replacement Set of rotor with shaft for sewage treatment compressor blower for 250 KLD capacity complete all as specified and as approved by Engr-in-Charge. Make: Everest or equivalent ISI marked.
S&F in replacement of blower of capacity 300 cubic metre per Hour, pressure 0.5 kg per square cm, 1770 RPM, 415 Volts complete all as specified and directed by Engr-in-Charge. Make: Everest or equivalent as approved by GE.
S&F in replacement of silencer suitable for Everest blower complete all as specified and directed by Engr-in-Charge. Make: Everest or equivalent as approved by GE.
Disconnecting of the Electric connection of Decrin Dosing pumps and removing of the Decrin Dosing pumps from the existing location and Transporting to work shop and replacement of the following unserviceable parts and re-fixing the same testing and commissioning for 250 KLD capacity complete all as specified and directed by Engr-in-charge.
S&F in replacement of coil 250 volt 50 Hz complete all as specified and as approved by Engr-in-Charge. Make: Declibac or equivalent ISI marked.
S&F in replacement of Weighted suction line strainer 3/8 complete all as specified and as approved by Engr-in-Charge. Make: Declibac or equivalent ISI marked.
S&F in replacement of Jet mixer nozzles of size 25 mm for equilizer tank of STP complete all as specified and as approved by Engr-in-Charge. Make: Everest or equivalent ISI marked.
M&L in replacement electrical works such as submersible flat flexible copper conductor 3 core 4 Sqmm complete all as specified and as approved by Engr-in-Charge. Make: Havells Cat part No WHPNDSKG34X0 or equivalent in Plaza or Finolex.
M&L in replacement of cable PVC insulated and sheathed flexible single core of size 25 Sqmm with multistranded copper conductor complete all as specified and as approved by Engr-in-Charge.
S&F in replacement cast iron impeller suitable for Non clogging centrifugal pump 40 HP complete all as specified and as approved by Engr-in-Charge. Make- Kirloskar
-Ditto- All as per sl item No 42 but for 20 HP.
Disconnecting the electric and water pipe connections for taking out burnt non clogging submersible pumping set of capacity 1 to 12.5 HP by using tripod & chain pulley arrangement from sewage sump at a depth of approx 18 feet by dismantling column pipe flanged joint for carrying out necessary repair including transportation of pumping set to civil work shop for repair and return to site after repair including testing complete all as specified and as approved by Engr-in-Charge.
M&L for taking out the Non clogging submersible pump 12.5 HP from the motor and rewinding of motor with super enameled copper wire including removing burnt winding cleaning of slots separation of rotor and starter making insulation to all joint including replacement of following items:- (a) Replacement of both side ends cover and machining to size of ball bearing. (b) Replacement of driving and nondrying end ball bearing. (c) Balancing of rotor including straightening of strips. (d) Assembling of motor including replacement of copper lead.
-Ditto- All as per sl item No 44 but for 5 HP.
-Ditto- All as per sl item No 44 but for 3 HP.
Opening of Non-clogging Submersible pump 12.5 HP for repair and replacement of following unserviceable parts including re-fixing of all the same and testing and commissioning complete all as specified and directed by Engr-in-charge. (a) Replacement of gun metal impeller. (b) Replacement of bearing plate. (c) Replacement of gun metal bush. (d) Replacement of oil seal. (e) Replacement of glay oil
-Ditto- All as per sl item No 45 but for 5 HP.
-Ditto- All as per sl item No 45 but for 3 HP.
S&F of Cast iron sluice valve of size 150 mm dia Stainless steel stem PN- 1.6 ( Flanged) conforming to IS 14846 hand wheel operated including taking down old one complete all as specified and as approved by Engr-in-Charge.
-Ditto- All as per sl item No 46 but for 100 mm.
Earthing complete with GI earth plate 600 x 600 x 6 mm thick buried directly in ground (earth pit not less that 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mr below normal ground level connected to galvanised iron strip of size 25x4 mm by means GI welding after tighten by bolts, nuts, check nuts and washers from earth pit to test point with protection GI pipe of size 40mm dia light grade and providing masonry enclosure and watering pipe of dia 40mm including wiremesh steel funnel, including watering arrangement 200 ltrs for each earth pit complete as specified and directed by Engr-in-charge. Note: GI strip of 7.5 mtr shall be included in the quoted rate from earth pit to test point
S&F cast iron NRV flanged end of size 100 mm dia with all fitting and accessories including taking down old one complete all as specified and directed by Engr-in-Charge.
S&F cast iron NRV flanged end of size 80 mm dia with all fitting and accessories including taking down old one complete all as specified and directed by Engr-in-Charge.
S&F cast iron Butterfly valve 50 mm dia with lever operated CI Disc Nitrile/EPDM Rubber Lining test pressure PN-1.6 and MS nut bolt and washers and pair of rubber/fibers including taking down old one complete all as specified and as approved by Engr-in-Charge. Note: Pair of rubber/fibers required for the work shall be supplied by contractor for fixing in position.
-Ditto- All as per sl item No 49 but for 80 mm.
-Ditto- All as per sl item No 49 but for 100 mm.
S&F gun metal ball valve with iron wheel/handle screwed both ends for iron pipe and fixed of size 50 mm bore including taking down old one complete all as specified and as approved by Engr-in-Charge.
Taking out compressor from 12.5 HP motor and rewinding of motor same gauge with super enameled copper wire including removing burnt winding cleaning of slots separation of rotor and starter making insulation to all joint and replacement of the following items complete all as specified and directed by Engr-in- charge. (a) Replacement of ball bearing 02 Nos . (b) Replacement of cooling fan - 01 Nos.
Taking out the 40 HP centrifugal pump from the motor and rewinding of motor of same gauge with super enameled copper wire including removing burnt winding and cleaning of slots, separation of rotor and starter making insulation to all joint and replacement of the following items all as specified and directed by Engr-in-charge. (a) Replacement of ball bearing 02 Nos. (b) Replacement of cooling fan 01 No.
-Ditto- All as per sl item No 52 but for 12.5 HP.
-Ditto- All as per sl item No 52 but for 5 HP.
-Ditto- All as per sl item No 52 but for 2 to 3 HP.
Opening of pump centrifugal 40 HP for repair and replacement of following unserviceable parts including re-fixing the same, testing and commissioning complete all as directed by Engr-in-charge:- (a) Replacement of gun metal impeller - 01 No (b) Replacement of gun metal bush - 02 Nos (c) Replacement of ball bearing - 01 No (d) Replacement of oil seal - 01 No. (e) Replacement of gland - 01 Job
-Ditto- All as per sl item No 53 but for 12.5 HP.
-Ditto- All as per sl item No 53 but for 5 HP.
-Ditto- All as per sl item No 53 but for 2 to 3 HP.
S&F in replacement Direct on line submersible pump starter of capacity 7.5 HP (5.5 KW) current rating 18 Amp, overload relay range 10-16 Amp complete all as specified and as approved by Engr-in-Charge. Make- Havells cat part No IHSDOANB*A or equivalent in L&T or BCH
Supply and lay or fixing or passing through pipe cable XLPE insulated PVC sheathing (heavy duty) armoured cable with aluminium conductor for 1100 volts of size 6 Sqmm with aluminium 3 Core complete all as specified and as approved by Engr-in-Charge.
Supply and laying in replacement of galvanised steel water tubing medium grade in trenches / wall floor with all GI fittings like tee, socket, reducer, elbows connections as required at site of size 15 mm bore complete all as specified and as approved by Engr-in-Charge.
-Ditto- All as per sl item No 56 but Bore of pipe 20 mm.
-Ditto- All as per sl item No 56 but Bore of pipe 25 mm.
-Ditto- All as per sl item No 56 but Bore of pipe 50 mm.
-Ditto- All as per sl item No 56 but Bore of pipe 80 mm.
S&F in replacement of UPVC pipe manufactured as per ASTM-D-1785 as per IS-559, Schedule-40, pressure rating 10 kgf/Sq cm with all types of fittings, laid in trenches or wall in required length inner bore size 25mm dia complete all as specified and as approved by Engr-in-Charge.
Supply and Laying in replacement of heavy duty class 'C' MS pipe including fittings as required for 80 mm dia pipe laid in trenches or laying on floor for connecting to various STP accessories and to connect outgoing water main including taking down the unserviceable pipe and depositing to MES store yard complete all as specified and as approved by Engr-in-Charge. Note: MS flange and flange joint with jointing materials shall be deemed to be included in the quoted rate.
S&F in replacement of dosing pump of capacity 3 LPH @ 2.5 per square cm or equivalent specifications complete all as specified and as approved by Engr-in-Charge. Make: Eureka Forbes/Milton Roy/Ramco.
Excavation in trenches in soft/loose soil, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deep and getting out in soft/ loose soil for laying of cable/foundation of pole and stay etc in complete all as specified and as approved by Engr-in-Charge.
Removing the excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above ground level from starting point complete all as specified and as approved by Engr-in-Charge.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as specified and as approved by Engr-in-Charge.
Supply and laying HDPE pipe 100 mm dia for cable protection complete all as specified and as approved by Engr-in-Charge.
M&L for boring holes for laying of pipe of 200 mm dia without distrurbing roads/top surface of ground by trenchless method and getting out and disposal of spoil to a distance of not exceeding 50 m complete all as specified and as approved by Engr-in-Charge.
M&L for removal of lamella clarifier fiber settling plates of lamella clarifier suitable for 250 KLD STP complete all as specified and directed by Engr-in-Charge.
S&F in replacement of foot valve of size 100 mm dia of plastic body with necessary fixing arrangement like nut, bolts, washer, packing sheet inlcuding taking out existing unserviceable foot valve complete all as specified and directed by Engr-in-Charge.
-Ditto- All as per sl item No 66 but for 80 mm.
-Ditto- All as per sl item No 66 but for 50 mm.
M&L in replacement for electronic type timer ST 100 type, 110/240 Volt, 50 Hz for 3-30 seconds complete all as specified and directed by Engr-in-Charge. Make: Cat Part No ST80328OOOO or equivalent in Havells
M&L in replacement for single phase preventer for 415 V, 50 Hz complete all as specified and directed by Engr-in-Charge.
M&L for Power contactor 3 Pole, Type CN5, 50 AC, rating 50 A complete all as specified and as approved by Engr-in-Charge. Make- Havells Cat Part No- IHPAA050511, L&T, Siemens
M&L for Power contactor 3 Pole, Type MNX 32 AC 3, rating 32 A complete all as specified and as approved by Engr-in-Charge. Make- L&T Cat Part No- CS94111, Havells, Siemens
M&L for Power contactor 3 Pole, Type MNX 18/22/25, 415 Volt complete all as specified and as approved by Engr-in-Charge. Make- L&T Cat Part No- CS94110, Havells, Siemens
S&F electronic overload relay, manual reset type, range 24-40 Amp suitable for direct mounting complete all as specified and directed as by Engr-in-Charge. Make- L&T cat Part No SS9597900G0 or Havells, Siemens
S&F electronic overload relay, manual reset type, range 9-16 Amp suitable for direct mounting complete all as specified and directed as by Engr-in-Charge. Make- L&T cat Part No SS9597900A0 or Havells, Siemens
S&F electronic overload relay, manual reset type, range 45-75 Amp suitable for direct mounting complete all as specified and directed as by Engr-in-Charge. Make- L&T, Havells, Siemens
Note: The amount of Rs 1,25,274.00 against schedule of credit given on Tender Serial Page Nos 44 & 45 shall be deducted from the total amount quoted by the contractor against BOQ while deriving the contract sum for acceptance.
M/S Delhi Engineering Co.
Deep Contractor
M/s Hemakshi Enterprises
Deepak Electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .