Tender Value
₹1.4 Cr
EMD Value
₹2.8 L
Closing Date
11 Dec 2024, 1:00 pmClosed
SE,KHEC,PWD
Kolkata Health Electrical Circle, P.W.Dte KIT Annex Building, 5th Floor KOLKATA-700 073
Construction of proposed new building (BG9) opposite to Centenary Building within the campus of NRS Medical College Hospital, Kolkata.(Electrical Works) ..... Supply Installation Testing and commissioning of UPS system.
2024_WBPWD_769142_1
WBPWD/SEKHEC/CKHED/eNIT17/ 24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
60 days
NRS Medical College Hospital
Please refer Tender documents.
7 documents required · 7 mandatory
₹2.8 L
Office of the SE,KHEC,PWD
20 May 2025
14 Nov 2024
13 Dec 2024
14 Nov 2024
11 Dec 2024
25 Nov 2024
21 Nov 2024
Amount
SITC OF True Modular UPS with Hot Swapable Units of different ratings having following specifications as mentioned below,
30 KVA (3 Ph input & 3 Ph output)
20 KVA (3 Ph input & 1 Ph output)
10 KVA (3 Ph input & 1 Ph output)
INPUT:-
Input voltage 415V, 3 phases, 3 or 4 wires
Input voltage tolerance 305 to 480Vac at 100% load
Input frequency 50 Hz
Input frequency tolerance 50HZ +/-10Hz(40hz to 60Hz)
Current THD <3%
Control Fully Digital, DSP PWM technology
Event Log The Event Log shall store up to 2000 in the front display panel
Topology Level 3 or better
Self-Capacity test Full load Capacity test of the UPS at site without connecting any external load.
Inbuilt or external Isolation Transformer and supply through UPS OEM only
OUTPUT:
Nominal Module full load rating KVA/KW A) 30KVA=27KW or better A) 20KVA=18KW or better C) 10KVA= 9KW or better
Rated voltage 400V 3Ph/230v 1Ph
Output power factor range 0.9 lagging to unity without any KVA derating
Output voltage harmonics THDV 1.5% for liner load and 4.5% for non-liner load
Crest Factor 03:01
Overload rating 105% for 60 minutes 125% for 10 minutes 150% for 60 seconds
Successive Overloads sustainability: UPS System can withstand any number of repetitive/ multiple overloads occurring in quick succession of few seconds.
Inbuilt Manual by pass switch Required
Inbuilt Static by pass switch Required
Emergency Stop Emergency Stop Button on its Front panel.
Acoustic Noise (At 1 meter from UPS) Max 60 dbA(from 1 M)
DC CHARACTERISTICS
Nominal DC bus voltage Min 360V
Charge Current (Min.) Built-in min 12A (for 30/40KVA) 25A (60/80KVA) or better external charger is not acceptable
Battery Make EXIDE/AMARARAJA make
Type 12V SMF
Compatibility Compatible with SMF, Tubular, Ni-Cd, Li-Ion Battery
Battery block per string Maximum 50nos. Variable DC bus it can support at least variation of 10 nos of battery
Battery backup time 30min
Battery capacity
For 30 KVA Min VAH Capacity 31200, [reqired no of 12 V 65 AH (mimimum) batteries]
For 20 KVA Min VAH Capacity 20160, [reqired no of 12 V 42 AH (mimimum) batteries]
For 10 KVA Min VAH Capacity 10080, [reqired no of 12 V 26 AH (mimimum) batteries]
Battery isolation Battery circuit breaker
Automatic Battery testing Automatic battery testing from front display
Battery cables and rack UPS to Battery bank, should be connected with suitably rated copper cables and suitable size of metal rack should be provided
SNMP/MODBUS communication facility Required
CONTROLS
Charger input Isolator
Battery circuit breaker (mounted separately in its own enclosure)
Inverter output Isolator
Bypass line Isolator
Maintenance Bypass Isolator
Alarm acknowledge / Reset button
Inverter On-Off Push button for Manual switching On/Off of the Inverter
Emergency off push button
MEASURING INSTRUMENTS
LCD panel for Measuring Output voltages, Output currents and Frequency, Battery Voltage and Charging / Discharging current.
LCD panel displays status of the Battery charge status (in %).
Display- Digital LCD HMI type touch screen
PROTECTIONS
RC surge suppressor
Sustained under voltage on input side
Phase loss on input side.
Negative sequence on input side & bypass
Semiconductor fuses in the lines for rectifier thyristors
Snubber circuit for device dv/dt protection
Charger input current limit
Battery current limit
DC over voltage
Low battery
Overload
Over temperature for the inverter
HRC fuses in the control circuit
INDICATIONS (ALARMS & Warnings)
Inverter Failure
Overload (if load exceeds 100%)
Overload shutdown
Emergency shutdown
Equipment over temperature
Maintenance Bypass ON
DC over voltage
Low battery
Battery circuit breaker open
Battery on load
Mains failure
Rectifier Failed or Off
Inverter Unsynchronized
Load on bypass
Output voltage error
Environmental Conditions:
Panel type Floor mounted front access only
Operating temperature 0 – 45 deg.C continuous
Relative humidity < 90 % ( 20 deg. C.) non-condensing type
Altitude 1500 m from MSL without derating
Storage temp. From 0 to + 70 deg. C.
Product Brochures Original product brochure of the UPS battery should be submitted along with offer. Proto type system is not acceptable.
Certification ISO 9001,ISO 14001,ISO 45001 certified
UPS make:- Numeric/ Vertiv/ Switching AVO/Delta/ Fuji Electric/ Power One
Terms and Condition:
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
(Rates should be Quoted inclusive of all taxes & duities and L.W.C. @ 1% as applicable)
THE INDIAN OVERSEAS TRADING COMPANY (BID ID -5839630)
POWER ONE MICRO SYSTEMS P LTD (BID ID -5821448)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .