Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.2 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹26.2 L+₹7.7 L (41.8%)Rejected-AOC KTA ROAD LAMBA LINE JUNGLIGHAT PO PORT BLAIR 744103 | PORT BLAIR | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744103 | L2 | Rejected-AOC L2 | |
| 3 | L3₹26.8 L+₹8.3 L (44.7%)Rejected-AOC | L3 | Rejected-AOC L3 |
Tender Value
₹19.1 L
EMD Value
₹38,200
Closing Date
28 May 2020, 6:00 pmClosed
GE(I) CAMPBELL BAY
Garrison Engineer (I), Military Engineer Services, Army Land, Great Nicobar Islands, Campbell Bay, Pin 744 302.
SPEICIAL REPAIRS AND REPLACEMENT OF POST TOP LANTERN LIGHTS AT INS BAAZ AND PROVISION OF CHEMICAL ERATHING IN MSO AND SERVER ROOM AT INS BAAZ AND PROVISION OF FLAME PROOF LIGHTS IN BLDG NO S-58 AT INS KARDIP UNDER GE(I) CAMPBELL BAY
2020_MES_327988_2
8666/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Campbell Bay and Kamorta
As per NIT
3 documents required · 3 mandatory
₹500
GE(I) CAMPBELL BAY
₹38,200
Yes
9 Jun 2020
12 May 2020
30 May 2020
13 May 2020
28 May 2020
13 May 2020
Amount
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 mtr depth and getting out in any type of soil for erection for RCC poles laying of LT UG cables complete all as specified and directed by Engineer-in-charge
Returning filling in including spreading leveling, watering and well ramming in layers not exceeding 25 cm all as specified and directed by Engineer-in-charge
Removing excavated material to a distance no exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point all as specified and directed by Engineer-in-charge
Material and Labour for PCC 1:2:4 type B1 using 20 mm graded stone aggregate as column for post top lanterns including necessary form work complete all as specified.
Material and Labour for Rendering 10mm thick with cement plaster 1:6 on fair faces of concrete surface all as specified.
Taking out unserviceable UG cable of any size in any position.
Supply and laying of LT UG cable PVC insulated, PVC sheathed steel armoured 1100 volts grade multistranded aluminium conductor of size 2 core 10 Sqmm complete all as specified and directed by Engineer-in-Charge.
Material and Labour for HDPE (DWP) pipe of size 50mm outer dia and 38mm inner dia confirming to IS:14930 Part-II including necessary pipe fittings laid in trenches for cable protection complete all as specified and as directed.
Supply and laying of GI tubing medium grade 40 mm bore dia on pole/ in floor/ on wall for cable protection and post for post top lanterns all as specified and as directed.
Supply and Fixing of loop in /loop out box of size 200 x 150 x 100 mm PVC moulded terminal box with front open able hinged door and locking arrangement comprising of one 4 way connector all as specified and as directed
Taking down of sub main wiring of any description in any condition.
Material and Labour for sub main wiring along with earth wire with 2 x 2.5 Sqmm + 1 x 2.5 Sqmm FRLS PVC insulated, unsheathed, multistranded, 1100 Volts grade copper conductor cable single core, drawn through and including PVC Conduit of size 20mm bore and its all accessories of suitable size on wall/roof surfaces complete all as specified and directed by Engineer-in-Charge. Note: Two runs of 2.5 Sqmm, one run of 2.5 Sqmm copper cable and one run of PVC Conduit shall be measured as one unit length.
Supply and Fixing of LED post top lantern ,30W ,single phase with decorative LED post top lantern luminaire with diffuser and painted spun aluminium deflector pre wired and provision of twin core flexible wire, copper conductor of 0.5 Sqmm from light fitting to loop in box complete all as specified and as directed. .Make: LED Post top lantern, CETUS SERIES, C&S, Product code-LTGLC30WHPLED/W 30w or Equivalent in CG/Philips/Havells.
Supply and Fixing of MCB SPN, C curve, 32 Amp 240 volts.
Supply and Fixing of MCB single pole, C curve, 6 to 32 Amps.
Material and labour for point wiring 1.50sqmm FRLS Copper cable1100 volt grade drawn in and including stove enamelled steel ERW conduit not less than 19mm including spacers, saddles, screws etc and 1.50sqmm PVC insulated copper earth wire including connected to flame proof switches etc on independent all as specified and as directed.
Supply and Fixing of Fluorescent Tube light fittings 1x36 WATT flame proof FLP-WP made aluminium alloy LM6 with electronic ballast bipin holders connector block complete with accessories prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size all as specified and as directed
Supply and Fixing of Flame proof switch rotary type with termination box in LM6 single pole 250V.
Material and Labour for sub main wiring along with earth wire with 2 x 4 Sqmm + 1 x 2.5 Sqmm FRLS PVC insulated, unsheathed, copper cable multistranded, 1100 Volts FRLS grade with drawn copper conductor cable single core, drawn through and including stove enamelled conduit pipe of size 20mm bore and its all accessories of suitable size on wall/roof surfaces complete all as specified and directed by Engineer-in-Charge. Note: Two runs of 4.0 Sqmm, one run of 2.5 Sqmm copper cable and one run of stove enamelled conduit shall be measured as one unit length.
Supply and Fixing of MCB SPN-16Amps,'C' Curve 240 volts make: - Havells DHMGCSNF016 PVC plastic 16 A MCB SPN C curve (white) or equivalent all as specified and as directed.
Supply and Fixing of MCB single pole, C curve, 6 Amps DHMGCSPF006 PVC plastic 6 A MCB SP C curve (white) or equivalent all as specified and as directed.
Supply and Fixing of SHETT METAL ENCLOSURE factory made double door for DB 240 Volts with 200 Amps rated bus bar SPN 08 Way complete all as and as directed.
Material and Labour for Chemical earthing complete with copper each plate eletrode 900mm x 600mm x 5mm thickness buried directly in ground (Earth pit not less than 3 mtrs deep below ground level) with top edge of the plate not less than 1.8 mtrs below normal ground level connected to copper strip 32mm x 6mm by means of bolts nuts, check nuts and washer of brass or steel and earth strip and connected to distribution board/earthing test point or any other indicated situation all as shown the in electrical plate no. 3 of SSR part - I (2009) and testing on completion complete including necessary excavation in any type of soil, returning filling, removing of soil and 1.8 mtrs length GI pipe medium grade 20mm dia with funnal and wire mesh PCC chamber of 1:2:4 type B1 using 20mm grade stone grade aggregate, RCC precast chamber cover of 80mm thick with lifting handle arrangement, GI pipe medium grade 50mm dia for earth strip protection and chemicals copper sulphate 100 kgs and magnesium sulphate 50kgs in addition to char coal and common salt 200 kgs each all as specified and directed.
NOTE : An Amount of Rs 6,114 /- towards Schedule of Credit shall be deducted to arrive the Contract Sum
kakolil trade agencies
M/S RAJBUILDERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .