Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.7 LAccepted-AOC | ₹31.7 L Quoted ₹32.3 L | L1 | Accepted-AOC L1 |
| 2 | L2₹33.8 L+₹1.5 L (4.72%)Rejected-AOC | ₹33.8 L+₹1.5 L (4.72%) | L2 | Rejected-AOC L2 |
| 3 | L3₹42.7 L+₹10.4 L (32.2%)Rejected-AOC | ₹42.7 L+₹10.4 L (32.2%) | L3 | Rejected-AOC L3 |
| 4 | L4₹44.5 L+₹12.2 L (37.8%)Rejected-AOC 2 EVEREST VIHAR PT T N MISHRA MARG NIRMAN NAGAR JAIPUR 302019 | JAIPUR | RAJASTHAN | 302019 | ₹44.5 L+₹12.2 L (37.8%) | L4 | Rejected-AOC L4 |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
12 May 2020, 3:00 pmClosed
Lt Col PK Morolia
GE (AFA) Hyd, Pin- 500043
REPAIRS AND RENEWALS TO EXTERNAL ELECTRIFICATION WORKS IN DOMESTIC AREA AT AFA HYDERABAD
2020_MES_338932_1
8977/02/E8
Open Tender
Civil Works
Item Rate
330 days
GE (AFA) Hyderabad
As per Tender Documents
5 documents required · 5 mandatory
₹500
Yes
GE (AFA) Hyderabad
₹70,000
Yes
6 Aug 2020
15 Apr 2020
13 May 2020
15 Apr 2020
12 May 2020
29 Apr 2020
15 Apr 2020 - 18 Apr 2020
Amount
Dismantling ACSR or AAC conductors from the disturbed span including removing the binding wire with insulators, removing line spacer, of any size for LT / HT OH Line, etc complete all specefied and as directed
Re Stringing and Fixing only in position of sagged ACSR conductor of required size in over head line including biniding with aluminium binding wire complete after removing and refixing of UG cables / services wires to the ACSR conductor complete all as specified and as directed.
M&L for Stringing and Fixing in position of New ACSR conductor in over Head lines conductor (squirre l /wessel / rabbit) including binding with aluminium binding wire complete all as specified and as directed
S&F in repairs pin type porcelain vitreous white brown or green insulators including one galvanized steel spindle two galvanized iron washers and one galvanized iron nut 100 mm height, 65mm dia for 1100 volts grade complete all as specified and as directed
S&F in repairs Shackle Type Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts 75 x 90mm for 1100 volts grade complete all as specified and as directed
Dismantling / taking down old unserviceable cross arms, bracings, supports , clamps including nuts, bolts and washers etc complete all as specified and as directed
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel section including nuts, bolts, washers, drilling holes for bolts in any shapes or size all as specified and directed complete incl painting of one primer coat one under coat and one finishing coat paint complete all as specified and as directed
Excavation in trenches in any kind of soil not .exc 1.5 mtr depth and n.ot exc 1.5 mtr width and getting out, including trimming the sides and forming bottom surface to required levels for laying cables etc complete all as specified and as directed.
Excavation in trenches in any kind of soil exc 1.5 mtr depth but not exc 3.0 mtr depth and n.ot exc 1.5 mtr width and getting out, including trimming the sides and forming bottom surface to required levels for laying cables etc complete all as specified and as directed.
M&L River dry sand cushioning to UG cables (8 cm deep before laying of cable and 15 cm deep over the cable) in trenches including punned thickness up to 18 cm and consolidation, complete all as specified and as directed. Note :- Punned thickness only will be considered for payment.
Returning, filling in trenches in any kind soil in layers not exc. 25 cm after laying of cables including spreading, levelling, and well ramming complete all as specified and as directed.
Re laying of old retreived serviceable bricks vide excavation in trenches of exisitng laid cables complete all as specified and as directed.
M&L for sub class 'B' bricks best locally available laid in trenches above sand cushioning for cable protection complete all as specefied and as directed.
Removing surplus excavated material (soil) to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed.
M&L for 100 mm bore light grade galvanized pipe ISI marked with all fittings laid in trenches, under road or fixing on wall / pole / crossing nallah etc complete all as specified and as directed .
M&L for 80 mm bore light grade galvanized pipe ISI marked with all fittings laid in trenches, under road or fixing on wall / pole / crossing nallah etc complete all as specified and as directed .
M&L for 50 mm bore light grade galvanized pipe ISI marked with all fittings laid in trenches, under road or fixing on wall / pole / crossing nallah etc complete all as specified and as directed .
M&L for 40 mm bore light grade galvanized pipe ISI marked with all fittings laid in trenches, under road or fixing on wall / pole / crossing nallah etc complete all as specified and as directed .
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 240 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 185 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 120 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 95 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 70 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 50 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 35 sqmm 3.5 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.
Laying only insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 16 sqmm 4.0 core including dismantling and taking out the unserviceable cable complete all as specified and as directed. Note:- Cable shall be issued under Schedule 'B'' Store free for laying.
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 10 sqmm 4 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.
Supply, laying & testing insulated XLPE UG cable 1100 volts grade, armoured confirming to relevant IS specifcations with aluminum conductor of size 10 sq mm 2 core including dismantling and taking out the unserviceable cable complete all as specified and as directed.
M&L straight through joints heat shrinkable cable joint kit including jointing materials for making joints of UG electric cable 1100 volts grade heavy duty with PVC / XLPE insulated aluminium conductor nominal cross sectional area 16 to 50 sqmm 3.5 / 4.0 core and testing complete all as specefied and as directed.
M&L straight through joints heat shrinkable cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 70 to120 sqmm 3.5 / 4.0 core and testing complete all as specefied and as directed.
M&L straight through joints heat shrinkable cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 150 to 185 sq mm. 3.5 core and testing complete all as specefied and as directed.
M&L straight through joints heat shrinkable cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 240 to 300 sq mm. 3.5 core and testing complete all as specefied and as directed.
Supply & Fix PVC LT line separators 4 way with nut, bolt arrangement, in the existing O/H line on pole on height 7.0 to 7.50 mtrs above ground level complete all as specified and as directed.
All as per Ser item No. 33 above, but 2 way complete all as specified and as directed.
Supply and fix Steel tubular swaged pole with M.S base plate, finial tapper plug, bolts, nuts, and screw as specified type 410 SP- 31 (9 mtrs long ) including taking out old unserviceable steel pole of any description complete all as specified and as directed. Note:- Excavation, earthwork, PCC foundation, copping etc will be measured and paid separately under relevant items of BOQ.
Material and labour for Pree-stressed concrete poles, 9.0 mtrs long, 102 mm x 172 mm at top and 102 mm x 279 mm at bottom, class 10 including taking out PCC/PSC pole of any description complete all as specified and as directed. Note:- Excavation, earthwork, PCC foundation, copping etc will be measured and paid separately under relevant items of BOQ.
M&L for PCC 1:2:4 type B-1 mix using 20 mm graded stone aggregate as in platform, filling and mass concrete, coping to pole for embedding stay rod etc including necessary form work and applying two coats of white wash to exposed surfaces of coping / platform complete all as specified and as directed.
M&Lfor PCC 1:4:8 type D-2 mix using 40 mm graded stone aggregate for pole foundations , filling and mass concrete complete all as specified and as directed.
Material and labour for PCC 1:3:6 type C-2 mix using 40 mm graded stone aggregate for fixing stay wire complete all as specified and as directed.
Trimming of trunk and branches of trees not exceeding 30 cm grith and disposal of the same to a distance not exc 50 mtr and clearing site tfor OH line (HT / LT) for a span irrespective of length complete all as specified and as directed.
M&L for Cutting of Vegetations, creapers, grasses, earth heaps etc, cleaning and levelling of cutting areas in various electrical installation areas, surrounding of HT / LT poles / structures complete all as spcified and as directed.
M&L for one coat of Aluminium paint over the exisiting steel tubular poles 7.5 / 9.20 mtrs above ground including cross arms / bracings / clamps etc after cleaning the existing poles and making good surface and surroundings and writing the pole numbers with white letters on black paint background complete all as specified and as directed.
M&L for painting the PSC poles of height 7.0 to 9.20 mtr above ground with two coats of cement based paint complete all as specified and as directed.
M&L for stay assembly complete with accessories as shown in elect Plate No- 1 of SSR Part -I (2009) for dia of stay rod 20 mm incl GI stay strand of size 7/3.15 mm (maximum length 11.00 mtr) to keep the pole in vertical position including loop insulator stay including dismantling and taking out old unserviceable stay assembly set complete all as specified and as directed. (NOTE :- PCC will be measured and paid separately under relevant items of BOQ)
Dismantling Air Circuit Breaker 4 pole / 3pole, 1250 Amps, 415 Volts, draw out / fixed type from location and repair / overhauling of spring drive mechanism, coil, auxiliary switch including setting of over load coil, no volt coil, tripping coil & apply multi grease for mechnical parts, cleaning and inspecting male and female contacts and apply dry graphite conductive sealant for contacts, checking of electrical wiring system, testing, and assembling all items/components parts to the respective position and testing complete all as specified and as directed by Engineer-in-Charge. (Note : - Spare parts will be measured and paid separately under relavent items of BOQ)
Supply and fix LED Street light fitting 1 X 45-48 Watt LED pressure die cast aluminum housing heat resistant toughened glass with frame, IP - 66 protection, uniform distribution including 40 mm dia GI pipe and connecting up etc complete with 3 core 1.5 Sq mm PVC insulated sheathed copper wire ISI marked from terminal box to light fitting, including taking out the existing fully rusted unserviceable fitting complete all as specified and as directed. Make:-Crompton Cat Part No:- LSTP-45-CDL or equivalent to Philips / Havells / Bajaj / Wipro
Supply and fix LED Flood light fitting 1 X 50 / 60 Watt LED pressure die cast aluminum housing heat resistant toughened glass with frame, IP - 66 protection, uniform distribution, including taking out the existing fully rusted unserviceable fitting complete all as specified and as directed. Make:-Crompton Cat Part No:- LFL-60-CDL / 60 or equivalent to Philips / Havells / Bajaj / Wipro
Supply and fix LED Flood light fitting 1 X 150 / 160 Watt LED pressure die cast aluminum housing heat resistant toughened glass with frame, IP - 66 protection, uniform distribution,including taking out the existing fully rusted unserviceable fitting complete all as specified and as directed. Make:-Crompton Cat Part No:- LFLN-150-CDL or equivalent to Philips / Havells / Bajaj / Wipro
S & F cable junction box 200 x 160 x 98 mm in size, made out of thermoplastic, having IP 65 protection for outdoor installation fixed with 4 way bakelite cable terminals including 03 Nos polymide gland with check nut (M-32-02 N0 N0 & M- 25 -01 N0 ) fixed on poles with aluminium clamps of size 25 x 3, nuts, bolts, washers etc., including taking out of old unserviceable cable junction box complete all as specified and as directed. Make :- Cat No . K-8250 of HENSEL or equivalent in SPELSBERG / RITTAL.
S & F cable junction box 167 x 125 x 82 mm in size, made out of thermoplastic, having IP 65 protection for outdoor installation fixed with 4 way bakelite cable terminals including 03 Nos polymide gland with check nut (M-32-02 N0 N0 & M- 25 -01 N0 ) fixed on poles with aluminium clamps of size 25 x 3, unts, bolts, washers etc., including taking out of old unserviceable cable junction box complete all as specified and as directed. Make :- Cat No . K-8100 of HENSEL or equivalent in SPELSBERG / RITTAL.
M&L for GI tubing light grade 20 mm bore for protection of service connection for protection of connection wire from junction box to street light fittings ( Note :- Necessary clamps, nuts, bolts etc deemed to be included in the quoted rate)
M&L for cable two core PVC insulated, PVC sheathed multi stranded copper conductor size 1.5 Sqmm for connection junction box to security light complete all as specified and as directed.
Dismantling and taking out Rusted LT Panel Board enclosure with switchgear,bus bar including dismantling and re connecting of all cable connetions with new glands and suitable size of Aluminum Lugs and Supply & fix, install, testing and commissioning of LT Panel Board, Indoor type IP 52, cubical shape,three phase, 4 wire, made out of CRCA sheet ,2 mm thick ,factory fabricated , CPRI approved , poweder coating dust and vermin proof , provn for ventilation and suitable size of base frame, enclosure should be suitable size to accomodate the items mentioned below and having seperate compartment /chambers for cable gallery, busbar,switch gear etc including controle wiring for meters and lamps all as specified and and as directed by Engineer-In-Charge. Location:- OMQ / SMQ Area
S & F in repairs of ACB, 4 pole, 630 / 800 Amps,50kAwith bmicrsoft bsaed releases = 01 No
S & F in repairs of MCCB, 3 pole, 400 Amps to 315Amps,36 kA = 02 Nos
S & F in repairs of MCCB, 3 pole, 250 Amps to 200 Amps 25 kA = 06 Nos
S & F in repairs of MCCB, 3 pole, 160 Amps t o 125 Amps,25 kA = 04 Nos
S & F in repairs of MCCB, 3 pole, 100 Amps to 63 Amps,10 kA = 02 Nos
S & F in repairs of Change over switch,4 pole,400 Amps to 250 Amps,onload type = 01 No
S & F in repairs of Phase indicating lamps in red / blue / yellow colours "LED type" = 03 Nos
S & F in repairs of Digital type Voltmeter,96 x 96 mm, 0-500 Volts = -01No.
S & F in repairs of Digital type Ammeter, 96 x 96 mm with suitable CT's Ratio 250 / 5 Amp = 01 Set
S & F in repairs of suitable cacity of Aluminum Bus bars for Incomming and outgoing feeders including supporters
Dismantling and taking out Rusted LT Feeder Pilar Box enclosure with switch gear,bus bars including dismantling and re connecting of all cable connetions with new glands and suitable size of Aluminum Lugs and Supply & fix, install, testing and commissioning of LT Feeder Pillar Box platform mounted (to be mounted on the P.C.C. brick pedestal), out door , IP 55, cubical shape,three phase, 4 wire, made out of CRCA sheet ,3mm thick ,factory fabricated , CPRI approved , poweder coating dust and vermin proof , provn for ventilation and suitable size of base frame, enclosure should be suitable size to accomodate the items mentioned below and having seperate compartment /chambers for cable gallery, busbar,switch gear etc including controle wiring with protection MCB's and foundation for meters and lamps all as specified and as directed by Engineer-In-Charge :- Location :- OMQ / SMQ Area
S & F in repairs of MCCB, 4 pole, 400 Amps to 315 Amps,36 kA = 01 No
S & F in repairs of MCCB, 3 pole, 250 Amps to 200 Amps 25 kA = 04 Nos
S & F in repairs of MCCB, 3 pole, 160 Amps t o 125 Amps,25 kA = 03 Nos
S & F in repairs of MCCB, 3 pole, 100 Amps to 63 Amps,10kA = 02 Nos
S & F in repairs of Change over switch,4 pole,400 Amps to 250 Amps,onload type = 01 No
S & F in repairs of Phase indicating lamps in red / blue / yellow colours "LED type" = 03Nos
S & F in repairs of Digital type Voltmeter,96 x 96 mm,0-500 Volts = 01No.
S & F in repairs of Digital type Ammeter, 96 x 96 mm with suitable CT's Ratio 250 / 5 Amp = 01 Set
S & F in repairs of suitable cacity of Aluminum Bus bars for Incomming and outgoing feeders including supporters
S&F in repairs ACB, 4 pole, 630Amps, 50 kA,MDO in existing panel board complete all as specified and as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 3 pole, 400 Amps, 36 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 3 pole, 315 Amps, 36 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 3 pole, 250 Amps, 25 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs of MCCB, 3 pole, 200 Amps, 25 kAadjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 3 pole, 150 Amps, 25 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 3 pole, 125 Amps, 25 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 3 pole, 100 Amps, 10 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 3 pole, 63 Amps, 10 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 4 pole, 400 Amps, 36 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 4 pole, 320 Amps, 36 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 4 pole, 250 Amps, 25 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 4 pole, 200 Amps, 25 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 4 pole, 150 Amps, 25 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 4 pole, 125 Amps, 25 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 4 pole, 100 Amps, 10 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs MCCB, 4 pole, 63 Amps, 10 kA adjustable thermal and fixed magnetic settings in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs Change Over switch 4 pole, 250 Amps, open execution type in existing panel board complete all as specified and all as directed. Make :- L&T / Legrand / Havells / C&S
S&F in repairs Phase indicating LED lamps (Red,Yellow, Blue) 230Volts in existing panel board complete all as specified and as directed. Make :- L&T / TEKNIC / C&S
S&F in repairs Aluminium Bus Bar stips with colour code PVC heat shrinkable sleev, of any size/Capacity, for extention/connections of ACB/MCCB terminals connections, inside LT panel board / FPB , duly supported on the FRP / DMC support insulators including necessary drilling / bending to obtain required shape and size complete all as specified and as directed.
M&L for Dismantling and taking out care fully and re connecting and proper re arrangement of LT cabeles size 3.5 core 400Sqmm from LT panels / FPB / Cable ducts / Cable Tray at various electrical intallations with new Gland and alluminum Lugs complete all as directed by the Engineer-in-Charge.
All as per Ser Item No 77 above but of size 3.5core 300 Sqmm complete all as directed by the Engineer-in-Charge.
All as per Ser Item No 77 above but of size 3.5 core 240 Sqmm complete all as directed by the Engineer-in-Charge.
All as per Ser Item No 77 above but of size 3.5 core 185 Sqmm complete all as directed by the Engineer-in-Charge.
All as per Ser Item No 77 above but of size 3.5 core 150 Sqmm complete all as directed by the Engineer-in-Charge.
All as per Ser Item No 77 above but of size 3.5 core 120 Sqmm complete all as directed by the Engineer-in-Charge.
All as per Ser Item No 77 above but of size 3.5core 95 Sqmm complete all as directed by the Engineer-in-Charge.
All as per Ser Item No 77 above but of size 3.5 core 70 Sqmm complete all as directed by the Engineer-in-Charge.
All as per Ser Item No 77 above but of size 3.5 core 50 Sqmm complete all as directed by the Engineer-in-Charge.
All as per Ser Item No 77 above but of size 3.5 core 35 Sqmm complete all as directed by the Engineer-in-Charge.
All as per Ser Item No 77 above but of size 3.5 / 4core 25 to 16 Sqmm complete all as directed by the Engineer-in-Charge.
S&F in repairs Hot Dipped Galvanised perforated Cable Tray, sie 300 mmx 50 mm ,2 mm thick including necessary supports,bends and extensions complete all as specified and all as directed by the Engineer-In-Charge.
All as per Ser Item No 88 above but of size 250 mm x 50 mm complete all as specified and all as directed by the Engineer-In-Charge.
All as per Ser Item No 88 above but of size 200 mm x 50 mm complete all as specified and all as directed by the Engineer-In-Charge.
All as per Ser Item No 88 above but of size150 mm x 50 mm complete all as specified and all as directed by the Engineer-In-Charge.
All as per Ser Item No 88 above but of size100 mm x 50 mm complete all as specified and all as directed by the Engineer-In-Charge.
S&F in repairs in required shape of GI sheet, 1.6 mm thick including necessary fixing hard ware as required at site complete all as specified and all as directed by the Engineer-In-Charge.
Dismantling and taking down the high mast light of height 16 mtr by engaging crane checking thouroughly and replacing the brocken steel rope including supply and fix the new steel rope complete all as specified and all as directed.
Supply and fix ed in repairs the worn out gear wheel system of the winch arangement of the high mast light of upto 16 mtr high complete all as specified and all as directed.
Supply and fixed in repairs the motor assembly of the winch arangement of the high mast light of upto 16 mtr high complete all as specified and all as directed..
Supply , laying & testing in maintenance Copper Trailing Cable 5 core, 4.0 Sq mm EPR Insulated PCP scheathed, connected high mast lights confirming to relevant IS specifcations including dismantling and taking out the unserviceable cable complete all as specified and all as directed.
M&L for Pre-cast cement concrete block masonry PCC 1:3:6 type C-1 mix using 20mm graded stone aggregate with solid blocks, exc. 10 cm in width and setting in mortar 1:6 for foundations / platform / pedestal etc complete all as specified and all as directed.
M&L for rendering 10 mm thick in CM 1:6 on brick / concrete / block masonery surfaces and rendering is to be finished fair and even complete all as specified and all as directed.
M&L for laying for stone course boulders exceeding 7 cm and upto 15 cm thick to avoid growth of grass / weeds and protection against soil errosion at ou tdoor electrical sub stations complete all as specified and all as directed.
M&L for Repairing of Feeder Pillar Box by welding of broken door with new accessaries and making all doors to freely operatable by using grease and applying two coats of spay paint approved shade complete all as specified and all as directed.
Material & labour for chequered plate 6.0 mm thick and size as per site requirement including cutting to required shape and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and all as directed.
Material and labour for fault finding on LT cables of any size and any length with fault detective machine by thumbing method (high voltage) and apply high Voltage including excavation earth work of any type soil after located cable fault complete all as specified and all as directed.
Supply only spare parts suitable for existing ACB' s of Capacty 4 pole / 3 pole, 630 Amps to 1200 Amps of Make :- Havells / C&S / L&T / GE / Schnieder / ABB / Siemens complete all as specified and as directed.
(i) Microprocessor release / relay
(ii) Under /Over Voltage Trip Coil assembly
(iii) Shunt Trip Coil Assembly
(iv) Closing Coil Assembly
(v) Universal Charging Motor.
(vi) Mismatch prevention Device
(vii) Current Transformer,Class1 Accuracy,ratio 630 / 5 Amps
(viii) Current Transformer,Class1 Accuracy,ratio 800 / 5 Amps
(ix) Current Transformer,Class1 Accuracy,ratio 1000 / 5 Amps
(x) Current Transformer,Class1 Accuracy,ratio 1250 /5 Amps
(xi) Auxiliary Switch 14 Way
S&F in repairs GI Braket Light grade,40 mm dia,bend to shape upto length 1.5 Mtr including suitable size of GI clamps,nut bolts and washers etc with all accessaries complete all as specified and as directed.
M & L for Boaring of holes for road pavment , hard standing by using trenchless technology and necessary using ultra sound technique and necessary machine to insert pipe of 50 mm to 100 mm light grade as per site requirement with all fitting such as bends, elbow, tee etc. for protection complete all as specified and as directed.
S & F Electric Shock Treatment Chart ( As per Sample) in language English & Local ( Telugu) on PVC sheet with white colour letter on red colour base complete all as specified and as directed.
M&L for earthing complete with Galvanised steel earth plate eletrode 600 mm x 600 mm x 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filled in alternate layers and electrode connections by using Galvanised iron 32 x 6 mm strip connected by means of bolts, nuts, check nuts and washer of galvanised iron or steel, provision of 40mm dia GI pipe medium grade for protection of GI earth strip and 20mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) type C1 chamber of size 45cm X 45cm X 45cm including, MS funnel, wire mesh, 50 mm thick RCC 1:2:4 type B1 earth pit cover with 6 Nos, 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance n exc 50 mtr, provision of charcoal and salt complete all as shown in electrical plate No 4 of MES Schedule Part-I (2009) (For VCB , Lt Panel, and Transformer)
Note :- (i) Cost of GI earth strip and GI protection pipe upto 7.5mtr length shall deemed to be included in the unit rate quoted for this item
(ii) The unit rate shall also includes for wire mesh, funnel, excavation , REF , removal of earth . PCC chember pit , RCC cover slab for earth pit, test point etc.
(iii) All joints between earth plate and earth srip to be welded. Nut bolts should not be used except test point.
EXELLENT POWER CORPORATION
POWER CONSTRUCTION COMPANY
RASAM ENGINEERING COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .