Refurbishment work for OPD OT block and IPD block in respect of ESIC Hospital, Andheri, Mumbai Pin 400093
SBG/ITPO/ESIC/Andheri/2025/14
SBG/ITPO/ESIC/Andheri/2025/14
Open Tender-Domestic
Electrical Work
Mumbai Suburban, Maharashtra
₹11,800
₹20.6 L
28 Oct 2025
28 Oct 2025
14 Nov 2025
14 Nov 2025
18 Nov 2025
NAME OF WORK :-Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri
Mumbai, Maharashtra - 400093
SUMMARY SHEET OF BILL OF QUANTITY
Sr No. SUB HEAD OF WORK DSR AMOUNT NON-DSR AMOUNT REMARKS
1 Total Cost of Lift Servicing, Reconditioning, - 1,03,65,286.49
2 Total Cost Of Servicing, Reconditioning, of STP - 32,13,581.97
3 Total Cost of Servicing, Reconditioning, of Fire Fighting Work - 1,15,59,916.32
4 Total Cost of Servicing, Reconditioning, of HVAC Syatem - 5,48,98,443.60
6 Total Cost of Servicing, Reconditioning, of Electrical Work - 5,07,92,130.13
7 Total Cost of Servicing, Reconditioning of Bus Duct & Rising Main - 49,95,179.30
8 Total Cost of Servicing, Reconditioning of OT Door & Light Etc. - 76,38,529.32
9 Total Cost of Servicing, Reconditioning of Curtain & Nurse Call System - 1,09,51,755.50
10 Total Cost of Servicing, Reconditioning of Panels - 43,14,554.36
11 Total Cost of Servicing, Reconditioning of CSSD - 24,42,355.74
12 Total Cost of Servicing, Reconditioning, of TSSU - 39,80,943.52
13 Total Cost of Servicing, Reconditioning,of Transformer - 20,06,514.48
14 Total Cost of Servicing, Reconditioning of DG Set's - 1,09,63,463.56
15 Total Cost of Servicing, Reconditioning of Laundary - 29,51,522.50
16 Total for IPD Reconditioning & Upgradation Civil Work - 2,00,34,918.12
17 Total Cost of Servicing, Reconditioning of MGPS Sysytem - 47,67,938.92
18 Total Cost of Kitchen & Canteen Equipments Reconditioning - 5,83,177.54
TOTAL COST - 20,64,60,211.37
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
Servicing, Reconditioning, Testing and commissioning of Lift with power operated center / Side doors and AC variable voltage
13 Passanger Lift 1M/Sec B+G+7
13 Passanger Lift 1 M/Sec B+G+7 Nos 22,36,974.45 2.00 44,73,948.91
Servicing, Reconditioning, Testing and commissioning of Lift with power operated center / Side doors and AC variable voltage
8 Passanger Lift 1M/Sec B+G+7 floors
8 Passanger Lift 1 M/Sec B+G+7 Nos 18,25,803.45 1.00 18,25,803.45
Servicing, Reconditioning, Testing and commissioning Lift with power operated center / Side doors and AC variable voltage 20
Passanger Bed Lift 0.75 M/sec B+G+7
20 Passanger Bed Lift 0.75 M/sec B+G+7 Nos 29,51,534.83 1.00 29,51,534.83
4 Lift-4 Servicing, Reconditioning, Testing and commissioning Dumbwaiter Lift G+4 Nos 5,56,999.65 2.00 11,13,999.30
Sub-Head-I Total Cost of Lift Servicing, Reconditioning, 1,03,65,286.49
NDSR SUB-HEAD WORK-II REPAIR AND Servicing, Reconditioning, STP
Servicing, Reconditioning, & commissioing package vertical treated water transfer pumps, comprising of 2 nos. Electrical
Driven inline pumping sets each of 6 LPS to a head to 35 meter (1 working + 1 stand by) with all accessories
Soft Water Transfer Pumps as described below -
Servicing, Reconditioning, testing & commissioing package vertical soft water transfer pumps, comprising of 2 nos. Electrical
Driven inline pumping sets each of 6 LPS to a head to 55 meter (1 working + 1 stand by) with all accessories
Softener feed pumps as described below -
Servicing, Reconditioning, testing & commissioing package vertical softner feed pumps, comprising of 2 nos. Electrical
Driven inline pumping sets each of 6 LPS to a head to 35 meter (1 working + 1 stand by) with all accessories,
Filter feed Transfer Pumps - STP -
Servicing, Reconditioning, testing & commissioing package vertical filter feed pumps, comprising of 2 nos. Electrical
Driven inline pumping sets each of 6 LPS to a head to 35 meter (1 working + 1 stand by) with all accessories
Servicing, Reconditioning, testing & commissioing of centrifugal non clogging submersible sump pumps for plant room
drainage. Pump capable capable of handling 25 mm dia soft solids. Motor suitable for 415 + 10% volts, 3 phase, 50 Hz
9 AC Power supply. Pumps shall be suitable for automatic/manual operation (Overall depth of sump – 1.5 M). -
Submersible sump pump shall be provided with dry running protection. Inclusive of supporting arrangement for
stationary type.
Waste Water Drainage Sump Pump Set 33,099.27 15.00 4,96,489.05
Servicing, Reconditioning, testing & commissioing of Iron removal filter having M.S. fabricated pressure vessel suitable for
10 test pressure of 7 Kg./Cm2 including valves for back-wash arrangement complete with initial charge of media to remove the -
iron from the water.
Capacity : 6 LPS Each 54,548.69 1.00 54,548.69
Working Pressure : (5 ± 2.5) Kg/cm² -
MOC of vessel : MS with epoxy lining -
Servicing, Reconditioning, testing & commissioing of Dual Media filter having M.S. fabricated pressure vessel suitable for test
11 pressure of 7 Kg./Cm2 including valves for back-wash arrangement complete with initial charge of media to remove the -
total suspended particles from the water.
Capacity : 6 LPS Each 57,426.88 1.00 57,426.88
Working Pressure : (5 ± 2.5) Kg/cm² -
MOC of vessel : MS with epoxy lining -
Servicing, Reconditioning, testing & commissioing of Activated Carbon Filter having M.S. fabricated / N.F.R.L. / FRP
12 pressure vessel suitable for test pressure of 7 Kg./Cm2 including valves for back-wash arrangement complete with -
initial charge of media to remove the total suspended particles from the water .
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
Capacity : 3 LPS -
Working Pressure : (5 ± 2.5) Kg/cm² -
MOC of vessel : MS with epoxy lining / N.F.R.L. / FRP Each 61,333.01 1.00 61,333.01
Servicing, Reconditioning, testing & commissioing of FAB system based sewage treatment plant including all equipment &
accessories as per detail speciftcation / drawings.
Following equipments shall be part of Sewage Treatment Plant (for detail of equipment refer technical specification -
Sewage Water Transfer Pumps for STP (1 Duty + 1 Stand by) -
Sludge Transfer Pumps for STP (1 Duty + 1 Stand by) -
Blower Air Feeder Line (1 Duty + 1 Stand by) -
Back Wash Pumps -
Filters (DMF & ACF) -
Softener with brine tank -
UV Treatment with Dosing units -
All accessories and media required for STP and WTP -
Instrumentation -
Piping and valves as per specification and drawings -
All elctrical works including all wiring and accessories in side STP. -
Additional Feature For Pannel: -
i) For 2 x 1 HP Sewage Water Transfer Pumps for STP (1 Duty + 1 Stand by) -
25A TPN SDFU with HRC fuses, 25 A DOL starter, overload relay, start / stop push buttons, phase indication lights with
protection fuse, on / off / trip indication lights with protection fuse, including single phase preventer. - 02 SET
ii) For 2 x 7.5 HP irrigation System Feed Pumps (1 duty + 1 stand by) -
40A TPN SDFU with HRC fuses, 40 A DOL starter, overload relay, start / stop push buttons, phase indication lights with
protection fuse, on / off / trip indication lights with protection fuse, including single phase preventer. - 02 SET
iii) For 2 x 3 HP Filter Feed Pumps set (1 duty + 1 stand by) -
32A TPN SDFU with HRC fuses, 32 A DOL starter, overload relay, start / stop push buttons, phase indication lights
with protection fuse, on / off / trip indication lights with protection fuse, including single phase preventer. - 02 SET
iv) For 2x3 HP Softener Feed Pumpset (1 duty + 1 stand by) -
32A TPN SDFU with HRC fuses, 32 A DOL starter, overload relay, start / stop push buttons, phase indication lights
with protection fuse, on / off / trip indication lights with protection fuse, including single phase preventer. - 02 SET
v) For 2x6 HP Soft Water Transfer Pumpset (1 duty + 1 stand by) -
40A TPN SDFU with HRC fuses, 40 A DOL starter, overload relay, start / stop push buttons, phase indication lights
with protection fuse, on / off / trip indication lights with protection fuse, including single phase preventer. - 02 SET
14 Servicing, Reconditioning, testing & commissioing MAIN PLUMBING CUBICAL PANEL BOARD -
i) For 2 x 7.5 HP Treatment Plant feed Pumps (1 duty + 1 stand by) Set 2,98,098.98 1.00 2,98,098.98
ii) For 4 x10.0 HP Hydropneumatic Pumps (3 duty + 1 stand by) - only Feeder for sub- panel -
iii) For 2 x 2.0 HP Hydropneumatic Pump for drinking water (1 duty + 1 stand by) - only Feeder for sub-panel -
iv) For 2 x 1.0 HP R.O. Plant feed pumps system (1 duty + 1 stand by) - only feeder to sub panels. -
v) For 2 x 2.0 HP R.O. Plant high pressure pumps system (1 duty + 1 stand by) - only feeder to sub panels. -
vi) For 2 x 1.0 HP Hot water circulating Pumpset (1 duty + 1 stand by) - only feeder to sub panels. -
vii) For 2 x 1.5 HP HSD Pumps (1 Duty + 1 Stand by) - only feeder to sub panels. -
viii) For 2 x 1.5 HP Sewage Water Transfer Pumps (1 duty + 1 stand by) -
ix) For 2 x 2 HP Waste Water Transfer Pumps (1 duty + 1 stand by) -
x) For 4 x 3.0 HP Waste Transfer Pumps (1 duty + 1 stand by) -
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
Sub-Head II Total Cost Of Servicing, Reconditioning, of STP 32,13,581.97
SUB HEAD-III:FIRE FIGHTING WORKS -
Replacement of single headed internal hydrantvalve with instantaneous Gunmetal/Stainless Steelcoupling of 63 mm dia with
cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required :
Single headed Stainless Steel (Grade 304) Nos 8,041.27 30.00 2,41,238.24
Replacement testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked
complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :
Replacement, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber
gasket, GI bolts, nuts, washers etc.as required :
Replacement of 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire,
18 rivets etc. conforming to IS 636 -
(type-A) as required :
Stainless Steel (Grade 304) Nos 4,459.99 60.00 2,67,599.40
Replacement first-aid Hose Reel with M construction spray painted in post office red, conforming to IS 884 complete with the
following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm
nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from
riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.
Replacement 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle onforming to IS 903
suitable for instantaneous connection to interconnect hose pipe coupling as required :
Stainless Steel (Grade 304) Nos 1,670.72 30.00 50,121.60
Replacement testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required
21.1 Pendent Sprinkler Nos 522.45 1,590.00 8,30,697.09
21.2 Upright Sprinkler Nos 522.45 1,590.00 8,30,697.09
Replacement, fixing of Flexible pipe of 1500mm with all clamps,hardwares, fixing arrangement etc. as required -
Sprinkler System
23 Dismanteling & Removing Of Exixting MS Fire Pipe of Following dia
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
Replacement fabrication & laying heavy grade IS marked GI C-Class piping complete with all fittings, pipe supports,
clamps etc. as approved with weleded jointing for external
Total Cost of Servicing, Reconditioning, of Fire Fighting Work 1,15,59,916.32
SUB-HEAD IV HVAC SYSTEM
25 MACHINE WITH VARIABLE SPEED DRIVE & MICRO-PROCESSOR BASED CONTROL PANEL (600 TR)
Servicing, Reconditioning, testing and commissioning of Centrifugal Water Cooled Water Chilling M/C of 600 TR actual
capacity at below mentioned operating conditions with R - 134 A refrigerant, open / semihermatic / hermatically sealed
centrifugal compressor, direct / gear driven by suitable KW Sq. Cage induction motor complete with variable speed drive,
water-cooled shell & tube condenser, insulated shell and tube flooded chiller, flow switches at condenser & chiller
outlet, refrigerant piping, Refrigerant and Oil (First Charge), flexible pipe connector at condenser & chiller inlet / outlet,
integral lubrication system, Microprocessor based control panel, VSD & accessories etc. all mounted on M.S. frame. Motor
shall be suitable for 415 volts ± 10%, 50Hz ± 5 %, three phase A.C. supply. The chilling m/c as described above shall be in
line with specifications & shall have interface card compatible with BMS system.
Condenser CDW IN - 32.00º C.
CDW OUT - 36.14º C.
FLOW - 9072 LPM
Fouling Factor (MKS) - 0.0002
Pressure Drop Max - 6.5 Meter
Chiller CHW IN - 12.22º C.
CHW OUT - 6.67º C.
FLOW - 5443 LPM
Fouling Factor (MKS) - 0.0001
Pressure Drop Max - 6.0 Meter
IKW / TR (Maximum) - 0.67
The price quoted for Servicing, Reconditioning,, testing & commissioning of imported Centrifugal Chilling Unit shall be
inclusive of all duties & taxes, insurance, transportation / shipment cost from works to site, loading / unloading, port clearance NO 32,33,757.13 3.00 97,01,271.38
charges etc. as required in Indian Rupees.
Replacemnet, testing and commissioning of Centrifugal Water Cooled Water Chilling M/C of 600 TR actual capacity at
below mentioned operating conditions with R - 134 A refrigerant, open / semihermatic / hermatically sealed centrifugal
compressor, direct / gear driven by suitable KW Sq. Cage induction motor complete with variable speed drive, water-
cooled shell & tube condenser, insulated shell and tube flooded chiller, flow switches at condenser & chiller outlet,
refrigerant piping, Refrigerant and Oil (First Charge), flexible pipe connector at condenser & chiller inlet / outlet, integral
lubrication system, Microprocessor based control panel, VSD & accessories etc. all mounted on M.S. frame. Motor shall be
suitable for 415 volts ± 10%, 50Hz ± 5 %, three phase A.C. supply. The chilling m/c as described above shall be in line with
specifications & shall have interface card compatible with BMS system.
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
Condenser CDW IN - 32.00º C.
FLOW - 9072 LPM
Fouling Factor (MKS) - 0.0002
Pressure Drop Max - 6.5 Meter
Chiller CHW IN - 12.22º C.
CHW OUT - 6.67º C.
FLOW - 5443 LPM
Fouling Factor (MKS) - 0.0001
Pressure Drop Max - 6.0 Meter
IKW / TR (Maximum) - 0.67
27 Condenser Water Pumps Set
Servicing, Reconditioning,, testing and commissioning of Horizontal Split Casing condenser water centrifugal pump sets
with bronze impeller for condenser water recirculation complete with TEFC Sq. Cage induction motor with class "F"
insulation, base plate, coupling guard, vibration isolators, SS Shaft, factory fitted mechanical seal, flexible pipe
connector at inlet and outlet etc. conforming to technical specification & as per following parameters
Capacity of Each Pump LPM 9072
Pump Head (Mt) 30.00
Motor HP 100.0
Minium Efficiency 80 %
28 Primary Chilled Water Pumps Set
Servicing, Reconditioning,, testing and commissioning of End Suction chilled water centrifugal pump sets with bronze
impeller for chilled water recirculation complete with TEFC Sq. Cage induction motor with class "F" insulation, base plate,
coupling guard, vibration isolators, SS Shaft, factory fitted mechanical seal, flexible pipe connector at inlet and outlet NO 74,490.48 4.00 2,97,961.92
etc. conforming to technical specification & as per following parameters. The chilled water pumps shall also include the cost
of thermal insulation.
Capacity of Each Pump LPM 5443
Pump Head (Mt) 12.00
Minium Efficiency 70 %
29 Secondary Chilled Water Pumps
Servicing, Reconditioning,, testing and commissioning of End Suction chilled water centrifugal pump sets with bronze
impeller for chilled water recirculation complete with TEFC Sq. Cage induction motor with class "F" insulation, base plate,
couplingguard, vibration isolators, SS Shaft, factory fitted mechanical seal, flexible pipe connector at inlet and outlet etc.
conforming to technical specification & as per following parameters. The chilled water pumps shall also include the cost of
thermal insulation. Secondary chilled water pumps shall be suitable for operation on adjustable frequency drives &
conforming to the specifications of variable speed pumping system.
Capacity of Each Pump LPM 6170
Pump Head (Mt) 24
Pump Motor HP 50
Minium Efficiency 80 %
Working + Standby 1+1
Capacity of Each Pump LPM 5079
Pump Head (Mt) 28
Pump Motor HP 50
Minium Efficiency 80 %
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
Working + Standby 2+1
30 Variable Speed Pumping System For Zone 1
Supply, installation, testing and commissioning of Variable Speed Pumping system consisting of two numbers 50 HP
adjustable frequency drive (AFD) suitably interfaced with other system components, hand / auto macro designed for
pumping application, 01 no. dedicated microprocessor based pump logic controller, parallel pumping software duly SET 9,98,824.43 1.00 9,98,824.43
downloaded, 02 No. Differential Pressure Sensor / Transmitters, interfacing amongst all components and compatibility of
I/O signals etc complete with other accessories as required.
31 Variable Speed Pumping System For Zone 2
Supply, installation, testing and commissioning of Variable Speed Pumping system consisting of three numbers 50 HP
adjustable frequency drive (AFD) suitably interfaced with other system components, hand / auto macro designed for
pumping application, 01 no. dedicated microprocessor based pump logic controller, parallel pumping software duly SET 13,81,179.73 1.00 13,81,179.73
downloaded, 02 No. Differential Pressure Sensor / Transmitters, interfacing amongst all components and compatibility of I/O
signals etc complete with other accessories as required.
32 FRP Induced Draft Cooling Tower (700 TR)
Servicing, Reconditioning,, testing and commissioning of FRP Induced draft, cross/counter flow, twin/four cell, direct/ gear
driven, site erected cooling tower of capacity 700 TR (25,40,160 Kcal/Hr) based on the parameters given below and
complete with PVC Fill, Louvers, Drift Eliminator, TEFC Motor, Propeller Fan, PVC Sump & Steel Ladder etc. The cooling
tower shall conform to technical specifications given in the tender. The maximum allowable sound power at a distance of 1
M from the cooling Tower shall be less than 75 dB. The cooling Tower Model shall be to suit site condition.
Duty Parameters
Water Flow - 2800 US GPM
Designed Wet Bulb Temperature - 28.3 °C
Water Inlet Temperature - 36.14 °C
Water Outlet Temperature - 32.00 °C NO. 5,34,453.77 4.00 21,37,815.08
33 Pressurised Expansion Tank
Servicing, Reconditioning,, installation, testing and commissioning of
pressurised chilled water Expansion Tank of capacity
as given below made of MS Sheet & finished with
epoxy enamel, having interchangeable butile - EPDM
membrane, operating pressure 10 Kg/cm², overall
height of the tank shall be limited to 3.0 meter & the
tank shall be complete with necessary controls as
required. Size of tank is for guidance only & AC Contractor
to quote as per actual requirement
Capacity of the pressurised tank - 5000 Litres
34 Air Separator
Servicing, Reconditioning,, installation, testing and commissioning of
Air Separator of size as given below made of MS
sheet, brass airvent, without strainer, working pressure
10 Kg/cm² & shall be complete with necessary controls
required. Size of air separator is for guidance only & AC
Contractor to quote as per actual requirement
Size of Air Seperator - 1200 dia x 1800 Ht. NO. 1,94,483.88 1.00 1,94,483.88
35 Hot Water Generator
Servicing, Reconditioning, testing and commissioning of
Hot Water Generator of capacity 150 KW in three
banks complete with controls, electrical panels etc.
confirming to technical specifications Section.
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
Inlet Water Temperature 45 °C
Outlet Water Temperature 55 °C
150 KW (For Monsoon Reheat - 1W+1S) NO 2,27,377.56 2.00 4,54,755.12
Hot Water Pump Sets For 150 KW HWG
36 Servicing, Reconditioning, testing and commissioning of
Monoblock hot water centrifugal pump sets with
bronze impeller for hot water recirculation complete
with TEFC Sq. Cage induction motor with class "B"
insulation, base plate, vibration isolators etc.
conforming to techinical specification and as
per following parameters. The hot water pumps
shall include thermal insulation & cladding.
Capacity of Each Pump LPM 230
Pump Head (Mt) 21.34
Part II AHU & their Controls
37 Double Skin Floor Mounted AHU -
Servicing, Reconditioning, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling
unit floor mounted (Horizontal / Vertical to suit site) fabricated out of extruded aluminium section with 0.6mm pre-plasticized /
pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and
blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 4/6 Row cooling coil made of
Aluminium finned Copper tube with coil section, pre-filter section with non woven synthetic media of 10 micron particle size
with an efficiency of 90%, polished stainless steel drain pan made out of 22 G sheet duly insulated complete with motor, belt
drive etc. without face and bypass dampers. The AHU panels shall be insulated with 23mm thick & 36 Kg/m³ density PU
foam & shall have thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only.
The complete AHU shall conform to standard specication. The face velocity across cooling coil shall be limited to 152
MPM maxm. The capacity of Air-handlers shall be as follows:
37.1 AHU 10,000 CFM, 50 mm St. Pr., 4 Row CC, 560 Dia Fan, 5.5 Kw Fan Motor. NO 1,04,711.55 12.00 12,56,538.60
37.2 AHU 14,000 CFM, 50 mm St. Pr., 4 Row CC, 630 Dia Fan, 7.5 Kw Fan Motor. NO 1,06,294.56 9.00 9,56,651.00
37.3 AHU 11,000 CFM, 50 mm St. Pr., 4 Row CC, 560 Dia Fan, 5.5 Kw Fan Motor. NO 1,08,686.20 19.00 20,65,037.80
37.4 AHU 9,000 CFM, 50 mm St. Pr., 4 Row CC, 500 Dia Fan, 5.5 Kw Fan Motor. NO 1,02,244.52 6.00 6,13,467.12
37.5 AHU 12,000 CFM, 50 mm St. Pr., 4 Row CC, 630 Dia Fan, 5.5 Kw Fan Motor. - NO 99,759.68 5.00 4,98,798.40
37.6 AHU 7,000 CFM, 40 mm St. Pr., 4 Row CC, 450 Dia Fan, 3.7 Kw Fan Motor. NO 96,625.19 8.00 7,73,001.52
38 Double Skin Floor Mounted AHU -
(For ICU, MRI, CT Scan, Cath Lab etc.) -
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
Servicing, Reconditioning,, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling
unit floor mounted fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised steel
sheet outside & 0.6 mm Galvanised steel sheet inside with fan & fan section, fan motor TEFC type suitable for operation
on 415 volts ± 10%, 50 Hz ± 5% AC supply, 4/6 row cooling & 2 row heating coil made of Aluminium finned Copper tube,
Copper header with coil section, pre-filter section with non woven synthetic media of 10 micron particle size with an
efficiency of 90%, fine filter section with filters of non woven synthetic media of 5 micron particle size, polished stainless -
steel drain pan made out of 22 G sheet duly insulated complete with motor, belt drive package, guard etc. without face and
bypass dampers. The AHU panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam & shall have thermal
break. The motor & blower assembly shall be mounted on Aluminium extruded section only. The complete AHU
shall conform to standard specication. The face velocity across cooling / heating coil shall be limited to 152 MPM maxm.
The capacity of Air-handlers shall be as follows:
38.1 AHU 6,000 CFM, 55 mm St. Pr., 4 Row CC, 2 Row HC, 450 Dia Fan, 3.7 Kw Fan Motor. NO 94,774.92 1.00 94,774.92
38.2 AHU/ 17,000 CFM, 50 mm St. Pr., 6 Row CC, 2 Row HC, 710 Dia Fan, 9.3 Kw Fan Motor. NO 2,04,454.78 1.00 2,04,454.78
39 Double Skin Floor Mounted AHU -
(For OT With 10 ACH/Hr) -
Servicing, Reconditioning, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling
unit floor mounted fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised steel
sheet outside & 0.6 mm polished SS sheet inside with backward curved fan in supply and forward curved in exhaust with
fan section and fan motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 8 row cooling & 2
row heating coil made of Aluminium finned Copper tube, Copper header with coil section, pre-filter section with non woven
synthetic media of 10 micron particle size with an efficiency of 90% in both the supply & exhaust side of AHU, fine filter
section with filters of non woven synthetic media of 5 micron particle size in supply after fan, (Hepa filters shall be at
terminals along with laminar flow plenum & not to be included in the cost), mixing chamber, polished stainless steel drain pan
made out of 22 G sheet duly insulated complete with motor, belt drive package, guard etc. without face and bypass
dampers. The AHU panels shall be insulated with 48mm thick & 36 Kg/m³ density PU foam & shall have thermal break. The
motor & blower assembly shall be mounted on Aluminium extruded section only. These AHUs shall have air inlet / outlet
connection made of aluminium 20 G & all fixing arrangement / blank off shall be of SS The complete AHU shall
conform to standard specication. The face velocity across cooling / heating coil shall be limited to 152 MPM maxm. The
capacity of Air-handlers shall be as follows:
2 Row HC, 125 mm St. Pr. For Supply Fan, -
Supply Fan, 1000 CFM Ex. Air Blower, 40 mm St. Pr. -
for Exhaust fan with other accessories as specified) -
40 Double Skin Floor Mounted AHU -
(For 100% Fresh Air OT) -
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
Servicing, Reconditioning,, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling
unit fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised steel sheet outside &
0.6 mm polished SS sheet inside with backward curved fan in supply and forward curved in exhaust with fan section and
fan motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 8 row cooling & 2 row heating coil
made of Aluminium finned Copper tube, Copper header with coil section, pre-filter section with non woven synthetic media of
10 micron particle size with an efficiency of 90% in both the supply & exhaust side of AHU, fine filter section with filters of
non woven synthetic media of 5 micron particle size in supply & exhaust after fan, (Hepa filters shall be at terminals along
with laminar flow plenum & not to be included in the cost), Heat Recovery Wheel with HRW Section, mixing chamber, polished
stainless steel drain pan made out of 22 G sheet duly insulated complete with motor, belt drive package, guard etc. without
face and bypass dampers. The AHU panels shall be insulated with 48mm thick & 36 Kg/m³ density PU foam & shall have
thermal break. The motor & blower assembly shall be mounted on Aluminium extruded section only. These AHUs shall
have air inlet / outlet connection made of aluminium 20 G & all fixing arrangement / blank off shall be of SS The complete
AHU shall conform to standard specication. The face velocity across cooling / heating coil shall be limited to 152 MPM
maxm. The capacity of Air-handlers shall be as follows:
(3500 CFM Supply Air Blower, 8 Row CC, 2 Row HC, -
140 mm St. Pr. for Supply Fan, 3000 CFM Ex. Air Blower, -
60 mm St. Pr. for Exhaust fan with other accessories as -
specified above) -
Servicing, Reconditioning, testing and commissioning of factory fabricated Double Skinned Chilled Water Air- handling
unit ceiling suspended type fabricated out of extruded aluminium section with 0.6mm pre-plasticized / pre-coated Galvanised
steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC type
suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, 4 Row cooling coil made of Aluminium finned Copper tube
with coil section, pre-filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90%,
41 polished stainless steel drain pan made out of 22 G sheet duly insulated complete with motor, direct / belt drive as -
mentioned below etc. without face and bypass dampers. All direct driven fan motor shall be sourced from fan manufacturer &
factory fitted only. The AHU panels shall be insulated with 23mm thick & 36 Kg/m³ density PU foam. The motor & blower
assembly shall be mounted on Aluminium extruded section only. The complete AHU shall conform to standard
specication. The face velocity across cooling coil shall be limited to 152 MPM maxm. The capacity of Air-handlers shall be
41.1 AHU/Bas/01 - 5,500 CFM, 40 mm St. Pr., 4 Row CC, 2 x 300 Dia Fan, 2.2 Kw Fan Motor. NO 76,546.33 4.00 3,06,185.32
41.2 3,500 CFM, 32 mm St. Pr., 4 Row CC, 1 x 355 Dia Fan, 1.5 Kw Fan Motor. NO 72,366.10 4.00 2,89,464.40
42 Pressure Independant Balancing Cum Two Way
Servicing, Reconditioning, testing and commissioning of
Pressure Independant Balancing Cum Two Way Control
Valve in a single body equipped with electronic
modulating actuator working on 2-10 V DC, 4- 20 mA
electric signal. The minimum close off Pressure of
actuator must be 1.5 times shut off head of pump as
per specifications of following sizes:
43 Inline Fans
Servicing, Reconditioning, testing and commissioning of Inline
fans with motor complete in all respect & of following
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
capacities. The casing of inline fans shall be
acoustically lined & shall be selected for lower noise
level. Fan motor shall have inbuilt speed controller.
43.1 a) 300 CFM (8mm static pressure, single phase) NO. 9,936.63 12.00 1,19,239.56
43.2 b) 500 CFM (10mm static pressure, single phase) NO. 11,992.49 7.00 83,947.43
43.3 c) 600 CFM (10mm static pressure, single phase) NO. 13,363.06 7.00 93,541.42
43.4 d) 700 CFM (10mm static pressure, single phase) NO. 15,144.80 1.00 15,144.80
43.5 e) 800 CFM (12mm static pressure, single phase) NO. 18,571.22 3.00 55,713.66
43.6 f) 900 CFM (12mm static pressure, single phase) NO. 19,941.79 12.00 2,39,301.48
43.7 g) 1400 CFM (15mm static pressure, single phase) NO. 25,012.90 11.00 2,75,141.90
44 Lift Well, Lobby & Staircase Pr. Fan
Servicing, Reconditioning, testing & commissioning of floor
mounted Tube Axial flow fans with adjustable pitch
blade, MS casing, cast aluminium alloy impeller
complete with TEFC Sq.Cage Induction motor suitable
for 415 volts ± 10%, 50Hz ± 3 %, three phase A.C
supply with support, mountings and flexible connection
etc. & of following capacity.
44.1 7000 CFM (15mm static pressure) For Lift Well NO. 80,178.35 14.00 11,22,496.90
44.2 10000 CFM (15mm static pressure) For Staricase NO. 1,00,736.90 2.00 2,01,473.80
44.3 15000 CFM (15mm static pressure) For Lobby NO. 1,55,559.70 7.00 10,88,917.90
45 Servicing, Reconditioning, of Check Valves
46 Replacement of Y-strainer -
47 Replacement of Butterfly Valves
48 Replacement of Single louvered supply/ return air registers (diffusors) Sqmt 9,517.47 36.50 3,47,387.58
49 M.C.C. FOR CHILLER
Servicing, Reconditioning, of HVAC Panel Set 23,69,509.94 1.00 23,69,509.94
a) Water Cooled Centrifugal Chiller With VSD
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
b) CHW Primary Pump Sets
(25.0 HP each) - 04 Nos. (3W+1S)
c) CHW Secondary Pump Sets For Zone I
(50.0 HP each) - 02 Nos. (1W+1S)
d) CHW Secondary Pump Sets For Zone II
(50.0 HP each) - 03 Nos. (2W+1S)
e) CDW Pumps Sets
(100.0 HP each) - 04 Nos. (3W+1S)
f) Cooling Towers (4x10.0 HP each) - 04 Nos. (3W+1S)
g) Hot Water Generator - 150 KW (For RH Control)
(150 KW each) - 02 Nos. (1W+1S)
h) Hot Water Pumps Sets (2 x 3.0 HP) - (1W+1S)
50 Repalacmenet of AL Arm Power Cabling
i) For Chilling Machines
ii) For Condenser Water Pumps
iii) For Chilled Water Primary Pumps
iv) For Chilled Water Secondary Pumps
v) For Cooling Towers
v) For Air Handling Units & Vent Fan Motor
Total Cost of Servicing, Reconditioning, of HVAC Syatem 5,48,98,443.60
ELECTRICAL WORK REPAIR & Servicing, Reconditioning,
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single
core cable in existing surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and
earthing the point with 1.5 sq.mm FRLS PVC insulated
copper conductor single core cable etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed
52 medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop Mtr 341.23 21,366.00 72,90,698.81
earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single
core cable in surface/ recessed medium class PVC conduit as required.
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
Replacement and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including
cutting the wall and making good the same in case of recessed conduit as required.
Replacement and fixing following modular switch/ socket on the existing modular plate & switch box including connections but
excluding modular plate etc. as required.
55.3 3 pin 5/6 A socket outlet Nos 111.86 700.00 78,302.70
55.5 Telephone socket outlet Nos 118.94 350.00 41,627.60
56 Repalcement of Moduler Face Plate
Addressable Fire Alarm System -
Replacement, Testing & Commissioning of UL listed Fire alarm control panel having microprocessor based 4 loops card ( 252
intelligent addressable devices / loop card) Intelligent addressable fire alarm system. The panel shall have six inch long LCD
touch screen and LED's for displaying system status. In addition to the digital screen, the user can view a graphics map which
57 can show a simple building floor plan. The panel shall provide the user with 40 programmable macro or function buttons, which Nos 2,95,208.59 5.00 14,76,042.95
can be programmed for a variety of usages like controlling AHU's, Pressurisation fans, fire pumps, monitoring of flow switches
in fire pipe line etc. The panel shall have 240 V AC power supply, automatic battery charger, 24 V SMF batteries sufficient for
24 hour in standby and 5 minutes in alarm and complete as per specification.
Replacement Testing & Commissioning of UL listed Intelligent addressable tri colour LED Multi Sensor Detector with standard
base complete as per specification.
Replacement Testing & Commissioning of UL listed Intelligent addressable Manual Call Point / Pull station complete as per
60 Replacement Testing & Commissioning of UL listed Fault Isolators complete as per specification. Nos 1,656.56 56.00 92,767.36
Replacement Testing & Commissioning of wall mounting addressable type Hooter suitable for Alarm siren with suitable
power supply unit.
62 Replacement Testing & Commissioning of Response Indicator. Nos 1,750.00 850.00 14,87,500.00
Replacement testing and commissioning of False Ceiling Mounted High Quality Polycarbonate 6 Watt Ceiling Speaker with
connections, connecting wires etc. complete as required.
Drawing following pair 0.51 sqmm FR PVC insulated copper conductor, unarmoured telephone cable in the existing
surface/ recessed PVC
65 laying Cat.6 E computer (lan) wire in existing conduit. Metre 80.70 9,950.00 8,02,994.85
66 Replacement & Laying 2 X 1.5 sqmm (for fire alarm system) Metre 135.92 14,500.00 19,70,898.00
Supplying and drawing of 1 pair 32/24 (1.0 sq.mm), twisted, stranded annealed electolytic copper conductor, colour coded,
PVC sheathed and insulated FRLS wire, in existing recess / surface conduits including connections etc. complete as required.
Replacement Installation Testing & Commissioning of FUSION – Recess mounted direct-indirect downlight luminaire with
Paralite P5 louvers WCP 64236 SGW 36 W LED (TC-L)
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
69 Replacement Installation Testing & Commissioning of Mirror Light - DUOLITE-P 15414 1x10 W LED(T5) Nos 1,182.26 45.00 53,201.48
Replacement Installation Testing & Commissioning of COMFORT – Wall mounted personal light luminaire WVF 90118 1x
Replacement Installation Testing & Commissioning of VENUS-Recess mounted low depth downlighter with frosted diffuser
WCP 27218 SGW 2x18 W LED (TC-DE)
72 Supply Drawing & Termisnation of AL Arm Cable Cables A2XFY/A2XWY
Total Cost of Servicing, Reconditioning, of Electrical Work 5,07,92,130.13
BUS DUCT Servicing, Reconditioning,
73 Servicing, Reconditioning,, testing & commissioning of 3200 Amps-Indoor Type Bus Duct Mtr 18,201.17 55.00 10,01,064.35
74 Servicing, Reconditioning,, testing & commissioning of 2500 Amps-Indoor Type Bus Duct Mtr 14,185.40 55.00 7,80,197.00
75 Servicing, Reconditioning,, testing & commissioning of 2000Amps-Indoor Type Bus Duct Mtr 11,855.43 35.00 4,14,940.05
76 Servicing, Reconditioning,, testing & commissioning of 1600 Amps-Indoor Type Bus Duct Mtr 9,936.63 35.00 3,47,782.05
RISING MAINS -
77 Servicing, Reconditioning,, testing & commissioning of 800 amps TP MDO ACB (50 KA) Raising main endfeed Unit Nos 1,29,724.45 3.00 3,89,173.35
78 Servicing, Reconditioning, testing & commissioning of 800 Amps Air insulated type raising main Mtr 19,941.79 70.00 13,95,925.30
79 Servicing, Reconditioning, testing & commissioning of 200 A TP+N MCCB tapoff box Nos 18,502.70 36.00 6,66,097.20
Total Cost of Servicing, Reconditioning of Bus Duct & Rising Main 49,95,179.30
OT DOOR & LIGHT -
80 Servicing, Reconditioning, testing & commissioning of OT Door ( Patient Entry, Doctor Entry) Nos 1,97,567.67 27.00 53,34,327.09
81 Servicing, Reconditioning, testing & commissioning of Ceiling mounted Dual Dome LED OT lights and camera complete Nos 1,41,511.35 9.00 12,73,602.15
82 Servicing, Reconditioning, of OT Diffuser, HEPA Filter, Pass Box, Control Panel Etc. Nos 1,14,511.12 9.00 10,30,600.08
Total Cost of Servicing, Reconditioning of OT Door & Light Etc. 76,38,529.32
CURTAINS & Nurse Call System -
83 Replacment of old Fastrack Curtains Standard size 4ft * 7ft & Fixing Nos 1,557.46 2,625.00 40,88,332.50
84 Reconditioning, Installation testing Commissioning of Nurse Call System Nos 19,609.78 350.00 68,63,423.00
Total Cost of Servicing, Reconditioning of Curtain & Nurse Call System 1,09,51,755.50
Servicing, Reconditioning, testing & commissioning of Main LT & LT-2 Panel, All Floor Panel, AHU Panel, Starter Panel, Etc.
85 LT Panel-1, LT Panel-2, Lift Panel, Sub-Lift Panel, MDB-1A for AHU, MDB-1B & 1C for AHU, FDB , Lighting nad Power Panel, Ls 43,14,554.36 1.00 43,14,554.36
Capacitor, AUX Panel, CSSD, Launday panel Etc.
Total Cost of Servicing, Reconditioning of Panels 43,14,554.36
Servicing, Reconditioning, testing & commissioning of All CSSD Equipments. Door Sterilizer, Washer Disinfector, Ultrasonic
Cleaner, Drying Cabinet with single door,
Total Cost of Servicing, Reconditioning of CSSD 24,42,355.74
Servicing, Reconditioning, testing & commissioning of all TSSU Equipments. First Floor Cylindrical Steam Sterilizer, Washer
Disinfector, Drying Cabinet with single door, Hot & Cold Water Sterilizer
Servicing, Reconditioning, testing & commissioning of all TSSU Equipments. Second Floor Cylindrical Steam Sterilizer,
Washer Disinfector, Drying Cabinet with single door, Hot & Cold Water Sterilizer
Digitally signed by RAKESH
NBCC (INDIA) LTD.
NAME OF WORK :- Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra - 400093
SR No BOQ ITEM BRIEF DESCRIPTION OF ITEM UNIT RATE QTY AMOUNT REMARKS
Servicing, Reconditioning, testing & commissioning of all TSSU Equipments. Third Floor Cylindrical Steam Sterilizer, Washer
Disinfector, Drying Cabinet with single door, Hot & Cold Water Sterilizer
Total Cost of Servicing, Reconditioning, of TSSU 39,80,943.52
90 Servicing, Reconditioning, Dehumidification, Testing & Commissioning of 2000 KVA Transformer Nos 6,68,838.16 3.00 20,06,514.48
Total Cost of Servicing, Reconditioning,of Transformer 20,06,514.48
91 Servicing, Reconditioning, testing & commissioning of 1500 KVA DG Set Job 26,72,337.39 3.00 80,17,012.17
92 Servicing, Reconditioning, testing & commissioning of 1010 KVA DG Set Job 29,46,451.39 1.00 29,46,451.39
Total Cost of Servicing, Reconditioning of DG Set's 1,09,63,463.56
93 Servicing, Reconditioning, testing & commissioning of all Laundary Equipments L/s 29,51,522.50 1.00 29,51,522.50
Total Cost of Servicing, Reconditioning of Laundary 29,51,522.50
Servicing, Reconditioning,testing & commissioning of Complete MGPS Sysytem, (Vaccum, Commpressor, Plant Room
Equipments, Gas Outlets)
Total Cost of Servicing, Reconditioning of MGPS Sysytem 47,67,938.92
95 Reconditioning of Kitchen and Canteen Equipments and Buffing of SS Table on Lumpsum Basis L/s 5,83,177.54 1.00 5,83,177.54
Total Cost of Kitchen & Canteen Equipments Reconditioning 5,83,177.54
Digitally signed by RAKESH
NATIONAL BUILDINGS CONSTRUCTION CORPORATION LTD.
NAME OF WORK: Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra
IPD Reconditioning & Upgradation CIVIL WORK
CIVIL & PLUMBING WORK
SL.NO DESCRIPTION UNIT RATE AMOUNT Remarks
Removing of exesitng damege flooring & Providing Fixing flexible PVC sheet
flooring in 2.0mm thickness. It shall be homogeneous and monolayer in
construction, and shall be manufactured by calendering and presssing, to
MR ensure a dense, smooth surface and non-directional design. The flooring sqm 1,750.00 710.40 12,43,200.00
shall incorporate a specially formulated polyurethane reinforcement, to
significantly reduce maintenance costs. [Equivalent to Polyfloor Mystique
Removing of exesitng damege flooring & Providing Fixing flexible PVC sheet
flooring in 2.0mm thickness. It shall be homogeneous and monolayer in
construction, and shall be manufactured by calendering and presssing, to
MR ensure a dense, smooth surface and non-directional design. The flooring sqm 1,750.00 186.40 3,26,200.00
shall incorporate a specially formulated polyurethane reinforcement, to
significantly reduce maintenance costs. [Equivalent to Polyfloor Mystique
PUR] skirting/dado
MR Extra P/F Profiles rounded at top and bottom 180.00 186.40 33,552.00
Scrapping of old paint & new Painting with silicon & acrylic emulsion based
MR water thinnable sealer of approved brand and manufacture on wet or patchy sqm 161.70 8,300.00 13,42,110.00
portion of plastered surfaces : Two coats
Digitally signed by RAKESH
CIVIl BOQ THAKUR 16 OF 19
NATIONAL BUILDINGS CONSTRUCTION CORPORATION LTD.
NAME OF WORK: Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra
IPD Reconditioning & Upgradation CIVIL WORK
CIVIL & PLUMBING WORK
SL.NO DESCRIPTION UNIT RATE AMOUNT Remarks
Removing of exesitng damege ceiling & install new false ceiling at all heights
including providing and fixing of frame work made of special sections, power
pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm
(both side inclusive) as per IS : 277 and consisting of angle cleats of size 25
mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm
centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm
dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle
hangers of 25x10x0.50 mm of required length with nuts & bolts of required
size and other end of angle hanger fixed with intermediate G.I. channels
45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which
the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges
of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be
fixed in a direction perpendicular to G.I. intermediate channel with
connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every
MR junction, including fixing perimeter channels 0.5 mm thick 27 mm high sqm 1,529.10 1,000.00 15,29,100.00
having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to
wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm
long dry wall screws @ 230 mm interval, including fixing of gypsum board to
ceiling section and perimeter channel with the help of dry wall screws of size
3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish
of tapered and square edges of the board with recommended jointing
compound , jointing tapes , finishing with jointing compound in 3 layers
covering upto 150 mm on both sides of joint and two coats of primer suitable
for board, all as per manufacturer’s specification and also including the cost
of making openings for light fittings, grills, diffusers, cutouts made with
frame of perimeter channels suitably fixed, all complete as per drawings,
specification and direction of the Engineer in Charge but excluding the cost
of painting with : 12.5 mm thick tapered edge gypsum moisture resistant
Digitally signed by RAKESH
CIVIl BOQ THAKUR 17 OF 19
NATIONAL BUILDINGS CONSTRUCTION CORPORATION LTD.
NAME OF WORK: Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra
IPD Reconditioning & Upgradation CIVIL WORK
CIVIL & PLUMBING WORK
SL.NO DESCRIPTION UNIT RATE AMOUNT Remarks
Removing of exesitng damege ceiling & install new false ceiling 15 mm thick
densified tegular edged eco friendly light weight calcium silicate false ceiling
tiles of approved texture of size 595 x 595 mm in true horizontal level,
suspended on inter locking metal grid of hot dipped galvanised steel sections
(galvanising @ 120 grams per sqm including both side) consisting of main ‘T’
runner suitably spaced at joints to get required length and of size 24x38 mm
made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to
centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum)
sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to
form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and
size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked
at middle of the 1200x 600 mm panel to from grid of size 600x600 mm,
resting on periphery walls /partitions on a Perimeter wall angle pre-coated
steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with
the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall
MR screws @ 230 mm interval and laying 15 mm thick densified edges calicum sqm 2,158.15 6,500.00 1,40,27,975.00
silicate ceiling tiles of approved texture in the grid, including, cutting/
making opening for services like diffusers, grills, light fittings, fixtures,
smoke detectors etc., wherever required. Main ‘T’ runners to be suspended
from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling
with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods
with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm
centre to centre along main ‘T’. Bottom exposed with 24 mm of all T-sections
shall be pre-painted with polyster baked paint, for all heights, as per
specifications, drawings and as directed by Engineer-in-Charge. Note :- Only
calcium silicate false ceiling area will be measured from wall to wall. No
deduction shall be made for exposed frames/opening (cut outs) having area
less than 0.30 sqm.The calcium silicate ceiling tile shall have NRC value of
0.50 (Minimum), light reflection > 85%, non- combustible as per B.S. 476
part IV, 100% humidity resistance and also having thermal conductivity
Removing of exesitng damege wall clading in confrance room & Providing and
fixing 38mm thick cladding comprising of Wooden framwork using
25mx50mm sections at a maximum spacing of 600mm in any one direction
(including adding members as required) covered with12mm thick BWP ply
layered with 1 mm thk Laminate(Basic Rate Rs.25/-sqft)on one side pasted
and pressed with adhesive to give a uniform and smooth finish, including top
mouldings / margins, melamine polish etc. to finish the thickness, as shown
complete in drawing. All members / ply etc. shall be treated with anti-termite
solution as per norms. No extra shall be paid for making of openings, door /
window frames and for making provisions for electric conduits.
Digitally signed by RAKESH
CIVIl BOQ THAKUR 18 OF 19
NATIONAL BUILDINGS CONSTRUCTION CORPORATION LTD.
NAME OF WORK: Refurbishment work for OPD/OT block and IPD block in respect of ESIC Hospital, Andheri Mumbai, Maharashtra
IPD Reconditioning & Upgradation CIVIL WORK
CIVIL & PLUMBING WORK
SL.NO DESCRIPTION UNIT RATE AMOUNT Remarks
Removing of exesitng damege Scaffolding & install new double scaffolding
system (cup lock type) on the exterior side, up to seven story height made
with 40 mm dia M.S. tube 1.5 m centre to centre, horizontal & vertical tubes
joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S.
clamps and M.S. staircase system in the scaffolding for working platform etc.
and maintaining it in serviceable condition for the required duration as
MR approved and removing it there after. The scaffolding system shall be sqm 338.25 4,000.00 13,53,000.00
stiffened with bracings, runners, connection with the building etc wherever
required for inspection of work at required locations with essential safety
features for the workmen etc. complete as per directions and approval of
Engineer-in-charge. The elevational area of the scaffolding shall be measured
for payment purpose. The payment will be made once irrespective of duration
of scaffolding.
Total for IPD Reconditioning & Upgradation Civil Work 2,00,34,918.12
Digitally signed by RAKESH
CIVIl BOQ THAKUR 19 OF 19
aoc.pdf