SPECIAL REPAIR TO EARTHING, EXTERNAL SERVICES AND ALLIED SERVICES FOR BLDG NO. P-18 AND P-19 UNDER GE NARANGI
2024_MES_655071_2
8773/NAR/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Narangi
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
GE Narangi
₹1.1 L
Yes
18 Nov 2024
26 Jul 2024
21 Sept 2024
26 Jul 2024
18 Sept 2024
2 Aug 2024
Amount
Supply & fix IN REPAIRS Air termination, single pointed, copper rod 12mm dia and 300mm long complete all as specified and as directed by Engr-in-Charge at site.
Supply & fix IN REPAIRS Aluminium strip 25 x 3.15mm with "V" type porcelain insulator or DMC insulator of suitabe size and fixing with GI screws etc. for roof conductors and down conductors, complete all as specified and as directed by Engr-in-Charge at site.
Supply & fix IN REPAIRS including fabrication, display board of size 30cm x 25cm for earth pit Nos, location and periodical test results, lightening arrester, earthing etc., made out of MS sheet 4.0 mm thick, rectangular shape and welding to and including 12 mm dia rod of 50cm length, 30cm above ground level including fixing in PCC 1:2:4 type B-2 below ground level in earth pit of size 20 cm X 20 cm X 20 cm, painting all steel surfaces with two coats of synthetic enamelled paint (black colour) over a coat of red oxide zinc chrome primer and thereafter writing instructions on display board in white letters not less than 5cm size for all type of boards complete all as specified and as directed by Engr-in-Charge at site. NOTE: Excavation and earthwork in any type of strata, PCC work, formwork including screws, nuts & bolts etc. required for erection of display board as specified above is deemed to be included in the rates quoted for the above item.
Supply & fix IN REPAIRS Test point terminal box made out of Gun metal or Phosphorus Bronze of size 75mm x 75mm x 25mm, drilled and screwed, including 3Nos 8mm dia, 25 mm long hexagonal head screws, etc ccomplete all as specified and as directed by Engr-in-Charge at site.
Material and labour for providing IN REPAIRS, copper strip 20 x 3.15mm with "V" type porcelain insulator or DMC insulator of suitabe size and fixing with GI screws etc. for roof conductors and down conductors above ground, complete all as specified and as directed by Engr-in-Charge at site.
M&L for providing IN REPAIRS after taking down old unserviceable earthing, Advance encapsulated compound based Chemical earthing, CPRI tested, maintenance free, pipe-in-pipe technology, upgraded (Zinc coated), Zinc & Alloy coated (80-100 microns) with pure zinc 99.9% & Alloy coating (200-250 microns) Earthing system, conforming to IS 3034; The outer and inner pipe should be 76.2mm and 41.9mm dia respectively 3 mtrs long, zinc coated with additional special alloy coating 300mm on top side for additional protection of the terminal; The annular space between the pipes to be filled up with Compact fill (CF) Crystalline Conductive mixture, which should be machine pressed in the pipes not to disintegrate or collapse when outer pipe corrodes; The inner pipe should be extended with terminals for connectivity; The job includes digging the pits, lowering the pipe in pipe earth electrode, filling of pure conductolite back filling compound (BFC Conductolite) 250mm around the electrode (minimum 4 bags of 25 kg per unit, having excellent moisture retaining capacity; The BFC should be eco friendly and it should not contain environmentally hazardous material/metal, having ROHS certification from NABL accredited lab; The earth pit should be provided with a FRP earth pit cover for protection and to safe guard terminals; The material of earth electrode should have good electrical conductivity & anti corrosion property in wide range of soil conditions; The job also includes for providing PCC (1:3:6) type C-1 around the FRP cover for support and foundation and colouring the PCC work with desired colour including necessary excavation and earthwork in any type of soil complete all as specified and as directed by Engr-in-Charge at site.
NOTE: (i) Design of earth electrode should be of pipe-in-pipe technology. (ii) Contractor has to submit literature of earth electrode and get the make approved from GE before procurement. (iii) The earth electrode shall be CPRI tested to withstand short current test for 60kA rms for 1.0 second and 150kA for peak current. (iv) Contarctor has to fill pure back fill compound 250 mm all around the earth electrode up to full depth of pit. (v) Copper strip will be laid 20 cm below ground level and shall be connected to the test point drawn through HDPE pipe of 25mm dia for protection. (vi) Contarctor shall submit the test report of earthing after satisfactory completion of earthing. (vii) Cost for providing HDPE pipe is deemed to be included in the rate quoted for this item No. 6.00. (viii) The work of Advance encapsulated compound based Chemical earthing shall be carried out all as specified under BOQ item No. 6.00 above including notes mentioned at 6.01 above.
Supply & fix IN REPAIRS GI tubing, 40mm bore, light grade, for cable protection and fixing to the existing pole with and including flat iron clamp 25x 3mm of suitable size including nuts, bolts & washers complete all as specified and as directed by Engr-in-Charge at site.
Supply & fix IN REPAIRS including fabrication, LT Panel Board of suitable size, floor mounted, outdoor cubical type (with compartments for each out going and incoming feeders) made of CRCA sheet of 3.15 mm thick MS sheet, powder coated, mounted on and including angle iron frame and bottom legs made out of angle iron of size 50mm x 50mm x 6 mm, LT Panel Board having front and rear opening hinged doors, with projected and raised platform of suitable size, weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, nuts/ bolts made of rust proof material, LT panel board provided with and including IS tinned Aluminium bus bar suitable for three phase and neutral LT, AC, 50 Hz, 415 V, 600 Amp capacity complete for accomodating and including the following items:- INCOMING:- (a) MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA-01 No. OUTGOING:- (a) MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA-08 No.s (07 for VTPN, 01 spare) (b) On load Changeover switch 200 Amps 4 Pole 415 Volts - 02 No.s (c) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (d) LED indicating lamps with colour Red, Yellow, Blue - 01 Set
Supply & fix IN REPAIRS including fabrication, LT Panel Board of suitable size, floor mounted, outdoor cubical type (with compartments for each out going and incoming feeders) made of CRCA sheet of 3.15 mm thick MS sheet, powder coated, mounted on and including angle iron frame and bottom legs made out of angle iron of size 50mm x 50mm x 6 mm, LT Panel Board having front and rear opening hinged doors, with projected and raised platform of suitable size, weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, nuts/ bolts made of rust proof material, LT panel board provided with and including IS tinned Aluminium bus bar suitable for three phase and neutral LT, AC, 50 Hz, 415 V, 1000 Amp capacity complete for accomodating and including the following items:- INCOMING:- (a) ACB , 4P, 630 Amp, 36 KA, thermal magnetic release, Manual draw out type - 01 No OUTGOING:- (a) MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA-01 No. (b) MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA-02 Nos. (c) On load Changeover switch 200 Amps 4 Pole 415 Volts - 01 No. (d) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (e) LED indicating lamps with colour Red, Yellow, Blue - 01 Set
Supply & fix IN REPAIRS including fabrication, LT Panel Board of suitable size, floor mounted, outdoor cubical type (with compartments for each out going and incoming feeders) made of CRCA sheet of 3.15 mm thick MS sheet, powder coated, mounted on and including angle iron frame and bottom legs made out of angle iron of size 50mm x 50mm x 6 mm, LT Panel Board having front and rear opening hinged doors, with projected and raised platform of suitable size, weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, nuts/ bolts made of rust proof material, LT panel board provided with and including IS tinned Aluminium bus bar suitable for three phase and neutral LT, AC, 50 Hz, 415 V, 1000 Amp capacity complete for accomodating and including the following items:- INCOMING:- (a) MCCB 4 Pole, 415 V, Adjustable type, 630 Amps with breaking capacity 36 KA-01 No. OUTGOING:- (a) MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA-01 No. (b) MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA-03 Nos. (c) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (d) LED indicating lamps with colour Red, Yellow, Blue - 01 Set
Supplying & Laying in trenches or fixing on wall or passing through pipe or in cable ducts, 1100 volts grade 3.5/4.0 core XLPE insulated, armoured, heavy duty electric cables with aluminium conductor including taking down of old unsv cable, of the following sizes complete all as specified and as directed by Engr-in-Charge at site:- NOTE: (i)The rate quoted is inclusive for providing cable glands with suitable aluminium lugs wherever required. (ii) Excavation and earthwork, sand cushioning, cable protection shall be measured and paid separately under respective items in this BOQ.
3.5 core x 240 sqmm
3.5 core x 185 sqmm
3.5 core x 400 sqmm
3.5 core x 50 sqmm
3.5 core x 35 sqmm
Material and labour IN REPAIRS, earthing complete with galvanised steel earth plate electrode of size 600mm x 600mm x 6 mm thick burried directly in ground (Earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below ground level connected to galvanised earth lead GI strips 32 X 6mm as earthing lead, by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part-I, connected to earthing test point, including providing GI pipe 40mm bore(dia) light grade for earth lead protection, GI pipe 20mm Bore(dia) Medium grade for watering, including necessary excavation and earthwork in any type of soil, RCC earthing pit/ chamber, cover plate, wire mess, funnel, etc complete all as specified and as directed by Engr-in-Charge at site. NOTE: Excavation and earthwork in any type of soil, PCC / RCC work with reinforcement and formwork required for above item is included in the rate quoted for above item.
Material and labour IN REPAIRS for providing aluminium strip 25 x 3.15mm with "V" type porcelain insulator or DMC insulator of suitabe size and fixing with GI screws etc. for roof conductors and down conductors above ground complete all as specified and as directed by Engr-in-Charge at site.
Material and labour for Manual boring under roads/hard standing by reqd T&P without disturbing the top surface of the road for drawing GI pipe of 80mm dia for cable protection complete all as specified and as directed by Engr-in-Charge at site. NOTE: GI pipe shall be measured and paid separately under respective item in this BOQ.
Excavation in trenches n. exc 1.5mtr wide and n. exc. 1.5m in depth for foundation and getting out in soft/loose soil complete all as specified and as directed by Engr-in-Charge at site.
Supplying and spreading fine dry river sand for cushioning to underground cable including spreading, levelling and hand punning etc complete all as specified in SSR Part-I 2010 and as directed by Engr-in-Charge at site.
Material and labour for laying sub class ‘B’ bricks, old size for cable protection laid flat, in trenches over the cable, perpendicular to the direction of cable, complete all as specified and as directed by Engr-in-Charge at site.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc. 25cm, complete all as specified and as directed by Engr-in-Charge at site.
Removing of excavated soil not exc 50m & depositing where as directed at a level n.exc 1.5m above starting point complete all as specified and as directed by Engr-in-Charge at site.
Material and labour IN REPAIRS for laying GI pipe, light grade, 80mm bore with all fittings to be laid in trenches or in floors, on poles, in manual horizontal bore under item No. 14.00 for cable protection, complete all as specified and as directed by Engr-in-Charge at site.
Material and labour IN REPAIRS for laying GI pipe, light grade, 100mm bore with all fittings to be laid in trenches or in floors, on poles, in manual horizontal bore under item No. 14.00 for cable protection, complete all as specified and as directed by Engr-in-Charge at site.
Material and labour IN REPAIRS for laying GI pipe, light grade, 40mm bore with all fittings to be laid in trenches or in floors, on poles, in manual horizontal bore under item No. 14.00 for cable protection, complete all as specified and as directed by Engr-in-Charge at site.
Material and labour for for PCC 1:3:6 type C-1 (using 20 mm graded stone aggregates) as in foundation filling, mass concrete including necessary formwork for coping to the new/existing Steel Poles complete all as specified and as directed by Engr-in-Charge at site.
Material and labour for Cutting road/ wall to a width of 20cm and depth of 30cm for inserting GI protection pipe required for drawing cable and making good the same by filling back the excavated groove/trench with PCC 1:3:6 type C1 after laying of pipes for cable protection, to match the adjoining surfaces complete all as specified and as directed by Engr-in-Charge at site.
PURBANCHAL BUILDERS (BID ID -3089160)
SANJIB GOSWAMI (BID ID -3099184)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .