Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹2.4 LAdmitted-Finance | -6.52% | ₹2.4 L | L1 | Admitted-Finance |
Tender Value
₹19 L
EMD Value
₹38,000
Closing Date
18 Mar 2026, 6:00 pmClosed
CEO SSMM Mandfiya
Office of the CEO SSMM Mandfiya
02 - SITC of Servo Voltage Stabilizer work in ShreeSawariya Ji Mandir Mandal Mandafiya. Dist.- Chittorgarh.
2026_SANWA_542696_2
NIT No. 26/2025-26 CEO SSMM Mandfiya
Open Tender
Electrical Works
60 days
Chittorgarh
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
Through RTGS/NEFT
₹38,000
3 Apr 2026
27 Feb 2026
20 Mar 2026
27 Feb 2026
18 Mar 2026
27 Feb 2026
Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.
25mm x 3mm G.I. ( Hot Dipped ) Strip
SITC of Strip in Pipe Earthing using hot-dip galvanized 'B' class G.I. pipe, as secondary conductor. The system shall incorporate a crystalline conductive compound between the primary and secondary conductors to enhance conductivity and long-term stability. of following size and length and as per point mentioned (a), (b), [c), (d), (e) (f) as below
(a) Bore a hole of dia. 150 mm of required length, Place the rod in the centre of Hole
(b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 30 kg for 3000 mm. 20 Kg. for 2000 mm The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7
© Connect the Strip Terminal (110 mm long) with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
(d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm.
(e) Testing of earth resistance for value of 5 ohms or less as required.
(f) Test certificates for confirming above standards from OEM is mandatory.
Outer Pipe - 76 mm dia GI pipe , Inner Conductor- GI strip 50x6 mm Length 2 meter.Terminal 50x6mm GI.
SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-
(a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided
(b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.
[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra )
(d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.
(e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.
(f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra )
(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.
(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted)
Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves.
Electrolytic grade Aluminium bus bar 6010 grade
Providing & Fixing of IS: 13875 & IEC :61326/IEC:62053-22 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT opertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.
Three phase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS Meter
Providing & Fixing of Current Transformer confirming IS 2705-I (1992) with secondary terminal and shorting Block , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required .
Ring type tape wound CT
C T Class 1, Ratio 200/5 to 600/5, Burden 10 VA
SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate.
4 pole MCCB With Thermal Magnetic release
400 Amp , 35 kA, adjustable O/L & adjustable S/C setting,
630 Amp , 50 kA, adjustable O/L & adjustable S/C setting,
ADD GST @ 18%
Item Rate BoQ
BoQ_Ver3.0
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
NUMBER #
Supply , Installation, Testing and Comissioning of Servo Voltage Stablizer, 3 Phase,Full Load Efficiency Better Than 95% Oil Cooled with first filled of oil bidder. Input Voltage range from 300V - 500V phase to phase, Output Voltage : 400 V+ 1% phase to phase.and input, output voltage metering confirming LED Digital type,suitable type ground earthingh . Provide baypass facility for output supply, insulation class F and Us for inductive load. Floor Mounting type complete as reqd. Certificate/ report with liablety warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. Make - Servokon,Servomax,Microtek and Servotech
400 KVA (Power House Near Syam Nikunj and new Bhojanshala)
300 KVA (Gokul)
Please Enable Macros to View BoQ information
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.31 MB
Tendernotice_2.pdf
PDF • 0.56 MB
2_SITC_Of_Servo_Voltage_Stablizer.pdf
Tender Documents • 7.92 MB
Common.pdf
Tender Documents • 1.59 MB
BOQ_967417.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid