Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.0 CrAccepted-AOC | ₹18.0 Cr Quoted ₹18.5 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹21.0 CrRejected-Finance | ₹21.0 Cr | L2 | Rejected-Finance Being L2 |
| 3 | L3₹21.0 CrRejected-Finance PARISHRAM MADAN MAHAL CHOWK NAGPUR ROAD JABALPUR 248001 | JABALPUR | DEHRADUN | UTTARAKHAND | 248001 | ₹21.0 Cr | L3 | Rejected-Finance Being L3 |
| 4 | L4₹22.3 CrRejected-Finance | ₹22.3 Cr | L4 | Rejected-Finance Being L4 |
| 5 | L5₹22.4 CrRejected-Finance | ₹22.4 Cr | L5 | Rejected-Finance Being L5 |
Tender Value
Refer Docs
EMD Value
₹12.1 L
Closing Date
10 Feb 2021, 6:00 pmClosed
Brig Mukund Sharma CE
CE FY HYDERABAD SECUNDERABAD
PROVISION OF NEW WORKSHOP BY DEMOLITION OF BLDG NO P 8 AT GCF JABALPUR
2020_MES_385957_1
880158/JAB/E8
Open Tender
Civil Works
540 days
Kamaria
As per tender and NIT
7 documents required · 7 mandatory
₹3,000
GE (I)(P) Fy JABALPUR
₹12.1 L
Yes
5 Mar 2021
13 Oct 2020
15 Feb 2021
13 Oct 2020
10 Feb 2021
27 Jan 2021
14 Oct 2020 - 23 Nov 2020
Amount
Lump sum price worked out by the Contractor for “BUILDINGS AND STRUCTURES” as listed in Schedule ‘A’ Part-I Representing ** _______ % ____________ percent *Above / Below the lump sum price of Rs. 7,21,00,000.00 inserted by the MES in Schedule ‘A’ Part-I
Lump sum price worked out by the Contractor for “EARTH WORK EXCAVATION/SITE CLEARANCE” as listed in Schedule ‘A’ Part-II Representing ** _______ % __________ percent *Above / Below the lump sum price of Rs. 3,75,215.15 inserted by the MES in Schedule ‘A’ Part-II
Lump sum price worked out by the Contractor for DEMOLITION/DISMANTLING” as listed in Schedule ‘A’ Part-III Representing ** _______ % ____________ percent *Above / Below the lump sum price of Rs. 17,01,483.40 inserted by the MES in Schedule ‘A’ Part-III
Lump sum price worked out by the Contractor for “INTERNAL ELECTRIC SUPPLY” as listed in Schedule ‘A’ Part-IV Representing ** _______ % ____________ percent *Above / Below the lump sum price of Rs. 9,54,609.12 inserted by the MES in Schedule ‘A’ Part-IV
Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY ” as listed in Schedule ‘A’ Part-V Representing ** _______ % ____________ percent *Above / Below the lump sum price of Rs. 35,507.70 inserted by the MES in Schedule ‘A’ Part-V
Lump sum price worked out by the Contractor for “ROAD / PATH/ CULVERT / HARDSTANDING” as listed in Schedule ‘A’ Part-VI Representing ** _______ % __________ percent *Above / Below the lump sum price of Rs.45,00,491.36 inserted by the MES in Schedule ‘A’ Part-VI
Lump sum price worked out by the Contractor for “SEWAGE DISPOSAL ” as listed in Schedule ‘A’ Part-VII Representing ** _______ % ____________ percent *Above / Below the lump sum price of Rs.46,301.85 inserted by the MES in Schedule ‘A’ Part-VII
Lump sum price worked out by the Contractor for “AREA DRAINAGE ” as listed in Schedule ‘A’ Part-VIII Representing ** _______ % ____________ percent *Above / Below the lump sum price of Rs.12,02,934.60 inserted by the MES in Schedule ‘A’ Part-VIII
Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIC SUPPLY ” as listed in Schedule ‘A’ Part-IX Representing ** _______ % ____________ percent *Above / Below the lump sum price of Rs. 20,97,156.60 inserted by the MES in Schedule ‘A’ Part-IX
Lump sum price worked out by the Contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part-X Representing ** _______ % ____________ percent *Above / Below the lump sum price of Rs.32,405.50 inserted by the MES in Schedule ‘A’ Part-X
Lump sum price worked out by the Contractor for “LIGHTENIG PROTECTION” as listed in Schedule ‘A’ Part-XI Representing ** _______ % ____________ percent *Above / Below the lump sum price of Rs. 40,870.60 inserted by the MES in Schedule ‘A’ Part-XI
SCHEDULE 'A' PART-IIIA : DEMOLITION/ DISMANTLING Disconnecting cable connections, taking down carefully switch fuses, DBs of any size/capacity complete with all accessories and deposit to users all as directed.
Taking out carefully PVC insulated/sheathed sub main wiring with copper/aluminium conductor cable of size upto 16 sqmm on wooden batten/PVC conduits complete with batten/conduits, remove from size and hand over to users all as directed.
Disconnecting and taking out carefully aluminum conductor cable LT, PVC, 1100 volts grade of size upto 185 sqmm 3.5 core from the ducts laid in floors, along poles/walls/equipments etc laid and passed through pipes or laid bare in road crossing/drains/ paths/along walls/poles/floors etc and in similar locations and hand over to users complete all as specified and directed.
Disconnecting all cable connections and taking down carefully EOT crane of capacity 5 Ton complete with all accessories including over head traction, control gears etc and hand over to users complete all as specified and directed.
Disconnecting all incoming and out going and taking out carefully LT panel board LT panel board indoor type ACBs/OCBs and MCCBs starters etc any type/capacity and remove from site and hand over to users all as specified and directed
Dismantling glazed windows ventilators of size fixed with fillets complete all as specified and directed.
SCHEDULE 'A' PART-IVA (INTERNAL ELECTRIFICATION) Supply and fixing energy efficient, flicker free, surface mounted LED luminaire 20 watts, 230 volt, eye certification biologically tested, 4 feet long, with acrylic diffuser, surge protection 3KV complete with constant current electronic driver and all accessories including connecting up with ceiling rose using twin core twisted flexible copper conductor cable of suitable size all as specified and as directed. Make :- Philips Cat No BN308CLED20S-6500 L120PSUWH or equivalent of Wipro/C&S/Bajaj
Supply & Hanging Ceiling Fan, 1200 mm sweep, 5 Star rated, complete with Blades, down rod and all accessories, 230 Volt complete all as specified and directed. Make : Havells/Usha/Crompton Greaves
Supply and fixing Security lighting luminaire for use with LED lamps, of capacity not less than 40 watts, 230 Volts, with high quality lenses & reflector, High grade aluminium pressure Die-Cast Housing with toughened glass cover, IP-65 class of protection, complete with control gear and all accessories fixed with 25 mm bore Light grade GI Pipe Bracket 1.2 mtr long bent to shape, fixed on wall with MS Flat Clamps, nuts & Bolts as required complete all as specified and directed. Make : Philips Cat No. BRP409 LED040CWHOMRFGS1PSUGR or Equiv of Wipro/C&S
Supply & Fixing Surface mounted LED flat pannel (2' x 2') light fitting 34 watts with integrated electronic driver complete all accessories, prewired, including lamp and flexible wire twin core from ceiling rose to terminal block complete all as spepcified directed. Make : Havells Cat No : PLUTOSURFACE2X2 PLS 34W LED 840S or equivalent of Wipro/C&S.
Supply and Fixing Exhaust fan, heavy duty, 230 Volt, 50 Hz, Single Pole, 450 mm sweep, 900 RPM complete with louvers and all accessories, including making necessary opening in the wall, fixing on wall using necessary nuts, bolts and washers complete all as spepcified directed
Supply and Fixing Exhaust fan, 230 Volt, 50 Hz, Single Pole, 300 mm sweep 1400 RPM complete with louvers and all accessories, including making necessary opening in the wall, fixing on wall using necessary nuts, bolts and washers complete all as spepcified directed Make item No 22 & 23 : Havells/Usha/CG/Bajaj
Supply and fixing energy efficient, wall mounted LED batten type fitting not less than 10W, 230 volts, provided with extruded aluminium housing for efficient heat dissipation with polycarbonate diffuser and all accessories alongwith integrated electronic driver including connecting up with ceiling rose using twin core twisted flexible copper conductor cable of suitable size complete all as spepcified directed. Make: Havells Cat No ENDURALINEARNEOBS10W LED865SPCWH or equivalent of Wipro/C&S
SCHEDULE 'A' PART-V(A) : INTERNAL WATER SUPPLY Supply and fixing Health faucet of PTMT with PVC connecting pipe any colour for fixing with 15mm dia pipe complete all as specified and directed.
Construction of soakage well of size 2.4 m dia x 3.0 m deep including excavation in any type of soil, foundation in PCC 1:3:6 type C2 using 40mm grade aggregate, Honey combed masonry walls with fly ash bricks in CM 1:4 with top ring of M-25 design mix concrete including intercepting chamber, screen chamber made of fly ash brick work in CM 1:4, RCC cover slab in M-25 design mix/SFRC cover, interconnecting pipes of RCC/DWP filled with brick bats complete all as specified and directed.
SCHEDULE 'A' PART-IXA : EXTERNAL ELECTRIC SUPPLY Supply, installation, commissioning and testing of Indoor type, cubical LT panel board, CPRI approved factory made, alround powder coated (Siemens grey structural RAL 7032 shade) suitable for 3 phase 4 wire 415 v, 50 Hz and provided with suitable 'U' type gasket to make it dust/vermin proof & general construction confirming to IS : 8623/93, floor block mounting type made out of 3.15 mm thick CRCA sheet with using 50mm x 50mm x 6mm angle iron frame, factory fabricated duly compartmentalized for cable alloy and each control gear with front openable, lockable / openable by keys louvers & air vent gasket for natural flow of air and to accommodate incommer / outgoing MCCBs and TPN copper bus bar of rating not less than the 1500Amps ACB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size on same type insulators and having provision for termination of incomer and outgoing cables. All inter connections between the main bus bar as well as outgoing feeders shall be carried out with TPN copper bus bar of rating not less than 1.5 times rated capacity of individual outgoing feeders & should be insulated with heat shrinkable PVC sleeves. All control wires shall be with FRLS PVC insulated, unsheathed 1.5 sqmm multistranded copper conductor and shall be properly bunched, tied, ferrulated for proper identification and crimped with aequate size of lugs. A detachable predrilled gland plate of thickness 2 mm powder coated should be used at the bottom with and including necessary earth work and PCC work for fixing panel legs. The degree of protection for inner shell shall be IP-54 & including the following provisions all as specified and directed :-
Outgoing (a) MCCB 400 A, 4 pole 50 KA-03 Nos (out goings) (ultimate breaking capacity 50 KA with thermal and magnetic release, suitable for isolation, adjustable over load setting & adjustable short circuit setting conforming to IEC-60947-2 and IS-13947-3 complete all as specified) (b) MCCB 63 -100 Amps , 4 pole (ultimate breaking capacity 25 KA with fixed magnetic release, suitable for isolation, adjustable over load setting & adjustable short circuit setting conforming to IEC-60947-2 and IS-13947-3 complete all as specified) - 05 Nos (out goings)
Supply, installation, commissioning and testing of Indoor type, cubical LT panel board, CPRI approved factory made, alround powder coated (Siemens grey structural RAL 7032 shade) suitable for 3 phase 4 wire 415 v, 50 Hz and provided with suitable 'U' type gasket to make it dust/vermin proof & general construction confirming to IS : 8623/93, floor block mounting type made out of 3.15 mm thick CRCA sheet with using 50mm x 50mm x 6mm angle iron frame, factory fabricated duly compartmentalized for each control gear with front openable, lockable / openable by keys, louvers & air vent gasket for natural flow of air and to accommodate incommer / outgoing MCCBs and TPN copper bus bar of rating not less than the 1500Amps ACB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size on same type insulators and having provision for termination of incomer and outgoing cables. All inter connections between the main bus bar as well as outgoing feeders shall be carried out with TPN copper bus bar of rating not less than 1.5 times rated capacity of individual outgoing feeders & should be insulated with heat shrinkable PVC sleeves. All control wires shall be with FRLS PVC insulated, unsheathed 1.5 sqmm multistranded copper conductor and shall be properly bunched, tied, ferrulated for proper identification and crimped with aequate size of lugs. A detachable predrilled gland plate of thickness 2 mm powder coated should be used at the bottom with and including necessary earth work and PCC work for fixing panel legs. The degree of protection for inner shell shall be IP-54 & provision of the following items complete all as specified and directed :-
Outgoing (a) MCCB 400 A, 4 pole (ultimate breaking capacity 50 KA with fixed magnetic release, suitable for isolation adjustable over load setting & adjustable short circuit setting conforming to IES-60947-2 and IS-13947-3 complete all as specified)-03 Nos (out goings). (a) MCCB 100 Amps , 4 pole (ultimate breaking capacity 25 KA with fixed magnetic release, suitable for isolation adjustable over load setting & adjustable short circuit setting conforming to IES-60947-2 and IS-13947-3 complete all as specified)-01 No (out goings). (c) MCCB 63 A, 4 pole (ultimate breaking capacity 50 KA with fixed magnetic release, suitable for isolation adjustable over load setting & adjustable short circuit setting conforming to IES-60947-2 and IS-13947-3 complete all as specified)-01 No (out goings).
Supply, installation, testing and commissioning of not less than 630 AMP, 45 KA breaking capacity (100% neutral bus bar) copper bus bar sandwich bus duct system made of CRCA sheet/hot galvanized enclosure of thickness not less than 1.5 IP 55 degree of prorection as per IEC/EN61439-6 painted with RAL 7035, the insulation between the bars is ensured by multilayer sheath made with polyester film PET (Polyethelene terapthalate) (total thickness 0.9 mm between phase to phase) and thermal class "F" (155 degree c) the bus bar conductors should have rectangular cross-section with round corner and made up of high conductivity copper with copper and tin coating over the sentire length of the conductors. PVC/plastic insulated bus bar in convenient section including end cover units and braided type copper flexible connectors as per site requirement suitable for 415 volts 3 phase, 4 wire, 50 Hz AC system etc (insulation voltage shall be 1000V) tapping at each floor/every meter continous earthing with 2 Nos aluminium strip of size (one on each side including GI champing, brackets, angle iron brackets, steel fasteners) connecting to earth system. Entire bus duct arrangement should be laid/connected with suspension brackets, wall brackets and any other supporting system required horizontally or vertically throughout the entire length alongwith necessary nuts, bolts and fixing items etc for satisfactory completion of job as per site requirement complete all as specified and directed. Note :- (i) Copper flexible length will be measured/counted as copper bus duct length. (ii) Purity of copper conductor shall not be less than 99.9%. Make : LT/Legrand
Supply, install, testing & commissioning of suitable end feed unit with flange joint (Flange end) to connect the sanwich (insulation voltage shall be 1000 volts) type copper bus bar trunking 3 Phase + 100% neutral, current capacity of each phase and neutral should not be less than 630 Amps 45 KA breaking capacity, 415 volts, 50Hz, 3 Phase, AC supply alongwith suspension backets with brackets supports required for spacing flange end. End feed unit is provided with sufficient space for direct cable connections by nuts and bolts & flange end box can be provided with end feed unit for accommodating protective devices like ACB/MCCB etc complete complete all as specified and directed.
Supply, install, testing & commissioning of suitable bend to connect the sandwich (insulation voltage shall be 1000 volts) type copper bus bar trunking 3 Phase + 100% neutral, current capacity of each phase neutral should not be less than 630 Amps 45 KA breaking capacity, 415 volts, 50 Hz, 3 Phase, AC supply alongwith suspension brackets, wall brackets, supports required nuts and bolts etc complete all as specified and directed.
Supply, install, testing & commissioning of suitable Tee bend to connect the sandwich (insulation voltage shall be 1000 volts) type copper bus bar trunking 3 Phase + 100% neutral, current capacity of each phase neutral should not be less than 630 Amps 45 KA breaking capacity, 415 volts, 50 Hz, 3 Phase, AC supply alongwith supports required nuts and bolts etc complete all as specified and directed.
Supply & fixing of suitable Terminal end cover to connect the sandwich (insulation voltage shall be 1000 volts) type copper bus bar trunking 3 Phase + 100% neutral, current capacity of each phase neutral should not be less than 630 Amps 45 KA breaking capacity, 415 volts, 50 Hz, 3 Phase, AC supply alongwith nuts and bolts etc complete all as specified and directed.
Supply, install, testing & commissioning of Top-Off units (plug in box) with provision for MCCB of capacity 200 Amps to tap power supply from sandwich (insulation voltage shall be 1000 volts) type copper bus bar trunking 3 Phase + 100% neutral nuts and bolts etc complete all as specified and directed :- Note for Item No 35 to 39:- (i) MCCB's shall be measured & paid separately under relevant items. (ii) All Tap-Off units can be interlocked to prevent removal when outgoing device is in 'ON' position. (iii) Misc items required to connect the plug in box deemed to be inclusive in the unit rate. (iv) The bolted boxes are to be installed directly on the junction when bus bar is disconnected and not energized plug in type top of boxes can be installed and removed when bus bar is energized.
Supply, install, testing & commissioning of Top-Off units (plug in box) with provision for MCCB of capacity 160 Amps for sandwich (insulation voltage shall be 1000 volts) type copper bus bar trunking 3 Phase + 100% neutral nuts and bolts etc complete all as specified and directed.
Supply, install, testing & commissioning of Top-Off units (plug in box) with provision for MCCB of capacity 125 Amps for sandwich (insulation voltage shall be 1000 volts) type copper bus bar trunking 3 Phase + 100% neutral nuts and bolts etc complete all as specified and directed.
Supply, install, testing & commissioning of Top-Off units (plug in box) with provision for MCCB of capacity 63 Amps for sandwich (insulation voltage shall be 1000 volts) type copper bus bar trunking 3 Phase + 100% neutral nuts and bolts etc complete all as specified and directed.
Supply, install, testing & commissioning of Top-Off units (plug in box) with provision for MCCB of capacity 32 Amps for sandwich (insulation voltage shall be 1000 volts) type copper bus bar trunking 3 Phase + 100% neutral nuts and bolts etc complete all as specified and directed.
Supply, install & commissioning of P17 Tempra plug IP 66/67 surface mounted socket 32 Amp, 415 volts, 50 Hz, AC supply, 3P+N+E alongwith necessary screws, nuts & bolts complete all as specified and directed.
Supply, install & commissioning of P17 Tempra plug IP 66/67 surface mounted socket 63 Amp, 415 volts, 50 Hz, AC supply, 3P+N+E alongwith necessary screws, nuts & bolts complete all as specified and directed.
Supply, install & commissioning of P17 Tempra plug IP 66/67 surface mounted socket 125 Amp, 415 volts, 50 Hz, AC supply, 3P+N+E alongwith necessary screws, nuts & bolts complete all as specified and directed.
Supply, install & commissioning of P17 Tempra plug IP 66/67 Straight plug 32 Amp, 415 volts, 50 Hz, AC supply, 3P+N+E alongwith necessary screws, nuts & bolts complete all as specified and directed.
Supply, install & commissioning of P17 Tempra plug IP 66/67 Straight plug 63 Amp, 415 volts, 50 Hz, AC supply, 3P+N+E alongwith necessary screws, nuts & bolts complete all as specified and directed.
Supply, install & commissioning of P17 Tempra plug IP 66/67 Straight plug 125 Amp, 415 volts, 50 Hz, AC supply, 3P+N+E alongwith necessary screws, nuts & bolts complete all as specified and directed.
Supply, install, testing & commissioning of 4 pole MCCB 200 Amp, 50 Hz, 415 V, breaking capacity 36 KA with thermal and magnetic release suitable for isolation, adjustable over load setting & adjustable short circuit setting conforming to IED-60947-2 and IS-133947-3 complete all as specified with suitable sheet metal enclosure alongwith connected items and fixing on wall/surface with necessary nuts & bolts etc complete all as specified and directed.
Supply, install, testing & commissioning of 4 pole MCCB 160 Amp, 50 Hz, 415 V, breaking capacity 36 KA with thermal and magnetic release suitable for isolation, adjustable over load setting & adjustable short circuit setting conforming to IED-60947-2 and IS-133947-3 complete all as specified with suitable sheet metal enclosure alongwith connected items and fixing on wall/surface with necessary nuts & bolts etc complete all as specified and directed.
Supply, install, testing & commissioning of 4 pole MCCB 125 Amp, 50 Hz, 415 V, breaking capacity 36 KA with thermal and magnetic release suitable for isolation, adjustable over load setting & adjustable short circuit setting conforming to IED-60947-2 and IS-133947-3 complete all as specified with suitable sheet metal enclosure alongwith connected items and fixing on wall/surface with necessary nuts & bolts etc complete all as specified and directed.
Supply, install, testing & commissioning of 4 pole MCCB 63 Amp, 50 Hz, 415 V, breaking capacity 25 KA with thermal and magnetic release suitable for isolation, adjustable over load setting & adjustable short circuit setting conforming to IED-60947-2 and IS-133947-3 complete all as specified with suitable sheet metal enclosure alongwith connected items and fixing on wall/surface with necessary nuts & bolts etc complete all as specified and directed.
Supply, install, testing & commissioning of 4 pole MCCB 32-40 Amp, 50 Hz, 415 V, breaking capacity 25 KA with thermal and magnetic release suitable for isolation, adjustable over load setting & adjustable short circuit setting conforming to IED-60947-2 and IS-133947-3 complete all as specified with suitable sheet metal enclosure alongwith connected items and fixing on wall/surface with necessary nuts & bolts etc complete all as specified and directed.
Supply and fixing high bay luminaire for use with LED lamps of capacity not less than 150 watts, 230 volts with high quality lenses & reflector, high grade aluminium pressure Die-cast housing with toughened glass cover, complete with control gear and all accessories and connecting the same to electrical source using suitable copper conductor PVC insulated and sheathed three core cable and including fixing the light to poles/walls/roofs etc using necessary fixing arrangement complete all as specified and directed. Make :- Philips Cat No BY415PLED145S CW WB FG PSDGR S5 or equivalent or Wipro/C&S/Bajaj.
M&L for cutting of existing Bituminous road/hard standing not exceeding 3 mtr wide and not exceeding 0.9 meter depth for laying pipe lines/cables and making good disturbed surfaces complete all as specified and directed.
SCHEDULE 'A' PART-XA : EXTERNAL WATER SUPPLY M&L for brick masonry valve chamber of size 600 mm x 600 min x 600 mm (Internal dimension) using one brick thick wall, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate or brick work in CM 1:6 including necessary excavation RFR, removal of surplus oil to a distance not exceeding 50 M, PCC,1:3:6 type C-2 in foundation, plastering 15 mm thick in CM (1:4) 6mm thick MS sheet cover with MS angle 40 x 40 x 6 mm including locking arrangment, 2 coat of bituminous painting over one coat of red oxide primer to steel surface complete all as specified and directed.
SCHEDULE 'A' PART-XII : CHEMICAL EARTHING Earthing complete, chemical type, with copper earth plate electrode 900mm x 600mm x 5mm thick buried directly in ground (earth pit not less than 3m deep and 1.5m side) with top edge of the plate not less than 2.25m below normal ground level connected to and including copper strip earth lead 32mm x 6mm size by means of copper brazing strip and layers of salt, charcoal & magnesium sulphate including funnel with wire mesh including testing of earthing on completion; minimum three chemical pits are to be made and connected in a grid to meet the earth resistance of the grid as a whole as <0.5Ω, complete all as specified and directed. Notes: (a) Earthing to be done in presence of Engineer-in-Charge. (b) Charcoal (small pieces) - 250Kg, Salt (Crystal) - 250 Kg, Magnesium suplhate (crystal) - 100 Kg. (c) Copper strip shall be brazed with copper plate electrode. (d) Alternate layers of charcoal and salts should be laid in the earth pit on the top of copper plate; at least 5 such layers shall be laid. (e) After laying the alternate layers of charcoal and salts, a two inch layer of magensium sulphate shall be laid. (f) The chemical salt and magnesium suplhate shall not be mixed, but are to be laid in layers only.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required, 32mm x 6mm copper strip complete all as specified and directed.
SCHEDULE 'A' PART-XIII : TELEPHONE AND LAN CONNECTION Supply & lay telephone switch board cable with tinned copper /bar copper PVC / polythene insulation over all concealed individual pair sheathed with polystered backed aluminium tape and fine copper cable braid PVC FR/FRLS of conductor size 0.5mm to 2/4 pair suitable for telephone connection complete all as specified and directed.
Supply and laying LAN Cable CAT - 6 drawn into PVC conduit 20 mm dia complete all as specified and directed. Note for item No 56 & 57 PVC conduit and accessories will be measured and paid separately under the relevant item of this schedule.
S&F PVC conduit 20mm dia medium grade complete all as specified and directed.
S&F RJ 11 telephone socket (jack type) double socket complete all as specified and directed.
S&F metal flush mounting box 1/2 module complete all as specified and directed.
S&F white cover plate with frame for monting of telephone socket complete all as specified and directed.
PRITHIPAL SINGH AND COMPANY
SATYA PRAKASH BUILDERS LTD
SHRE GURMUKHDAS CONTRACTOR PVT. LTD.
ASHISH JINDAL BUILDERS PVT. LTD.
RAGHUSONS INFRA ENGINEERING PVT. LTD
M/s RAJKUMAR AGARWAL
DHARIWAL TRADERS PRIVATE LIMITED
GANGA INFRABUILD PVT LTD
SOOD ASSOCIATES PVT LTD
M/s Madan Lal Bansal and Co. Contractors Pvt. Ltd.
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid