Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.2 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder for the work | |
| 2 | L2₹14.0 L+₹66,914.80 (5.03%)Rejected-AOC | L2 | Rejected-AOC Other than lowest bidder |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
22 Jul 2021, 6:00 pmClosed
Commander Works Engineer Bhopal
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
REPAIR AND MAINTENANCE OF OVERHEAD LINE, UNDERGROUND CABLE, 2 POLE AND 4 POLE STRUCTURE AND CONNECTED ACCESSORIES AT DRONACHAL UNDER GE DRONACHAL
2021_MES_452392_1
83657/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Bhopal
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹500
GE DRONACHAL
₹30,000
Yes
7 Aug 2021
17 Jun 2021
24 Jul 2021
17 Jun 2021
22 Jul 2021
8 Jul 2021
Amount
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in hard/ dense soil complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3.0 in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and exceeding 1.5 m but not exceeding 3 m in depth and getting out in hard/ dense soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
Supply & laying unreinforced precast concrete cable cover class HVP type 1, with peak shape, dimension 300 mm X 180 mm X 40 mm and 65 mm peak thickness as per IS 5820: 1970 complete all as specified and directed.
M & L for cement concrete in foundation, filling and mass concrete in M7.5(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs, slab staging for water tanks, filling of pressed steel door frame, fixing of hold fasts and the like including weathering, slightly rounded or chamfered angles and throating including necessary formworks complete all as specified and directed by Engineer- in-charge.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 11 kV, nominal cross sectional area of main conductor 120 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for reuse or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 6.35 kV/ 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 120 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, outdoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 50 sqmm to 95 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, outdoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 120 sqmm to 185 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, outdoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 240 sqmm to 300 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, indoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 50 sqmm to 95 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, indoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 120 sqmm to 185 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, indoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 240 sqmm to 300 sqmm complete all as specified and as directed.
S & F cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and as directed.
S & F cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and as directed.
S & F cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 400 sqmm complete all as specified and as directed.
M & L in repairs for danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolts and nuts of approved size, for HT, 250 mm X 200 mm complete all as specified and as directed.
Dismantling insulators any type, any size complete all as specified and as directed.
Supply and erection in repairs of three piece metal oxide lightning arrestor suitable for 33 kV continuous operating voltage (3 phase) with rated voltage 36 kV (rms) with nominal discharge current rating of 2.5 kA and complete with galvanised clamping arrangements, GI bolts, nuts, washers etc. complete as specified and as directed.
S & F in repairs porcelain pin insulator, Type B, Nominal System voltage 11 kV, highest system voltage 12 kV, visible discharge test voltage 9 kV, wet power frequency withstand voltage 35 kV, power frequency puncture withheld voltage 105 kV, impulse withstand voltage 75 kV, minimum total creepage distance 230 mm, minimum failing load 5 kN, of suitable size with galvanised steel insulator pin, nut, washers complete all as specified and as directed.
S & F in repairs porcelain disc insulator, ball and socket type, Type B, Nominal System voltage 11 kV, highest system voltage 12 kV, visible discharge test voltage 9 kV, wet power frequency withstand voltage 35 kV, impulse withstand voltage 75 kV, minimum total creepage distance 230 mm, minimum failing load 70 kN, of suitable size with galvanised steel stud pin, nut, washers complete all as specified and as directed.
Supply and erection in repairs of three piece metal oxide lightning arrestor suitable for 11 kV continuous operating voltage (3 phase) with rated voltage 12 kV (rms) with nominal discharge current rating of 2.5 kA and complete with galvanised clamping arrangements, GI bolts, nuts, washers etc. complete as specified and as directed.
Supply and replace drop out fuse assembly, triple pole mounted on polymer HT insulator 6 Nos and mild steel galvanised steel frame rating upto 200 Amp, 33 kV complete with drop out fuse and electrical connections, jumpering by ACSR conductor and connectors complete all as specified and directed.
Supply and replace drop out fuse assembly, triple pole mounted on polymer HT insulator 6 Nos and mild steel galvanised steel frame rating upto 200 Amp, 11 kV complete with drop out fuse and electrical connections, jumpering by ACSR conductor and connectors complete all as specified and directed.
Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism and taken on schedule of credit complete all as specified and as directed.
S & F gang operated air break switch, three poles, outdoor type, nominal system voltage 33 kV, rated voltage 36 kV, rated normal current 400 Amps, rated frequency 50 Hz, rated one minute power frequency withstand voltage between (i) earth & poles 70 kV (rms) (ii) across the isolating distance 80 kV (rms), rated lightning impulse withstand voltage (i) to earth and between poles 170 kV (Peak) (ii) across the isolating distance 195 kV (Peak), Rated short-time withstand current 20 kA for 3 seconds, rated peak withstand current 50 kA for climatic conditions at the site, mechanically operated mounted on polymer insulator and steel frame with operating mechanism worked from ground level for current complete all as specified and as directed.
S & F gang operated air break switch, three poles, outdoor type, nominal system voltage 11 kV, rated voltage 12 kV, rated normal current 200 Amps, rated frequency 50 Hz, rated one minute power frequency withstand voltage between (i) earth & poles 28 kV (rms) (ii) across the isolating distance 32 kV (rms), rated lightning impulse withstand voltage (i) to earth and between poles 75 kV (Peak) (ii) across the isolating distance 85 kV (Peak), Rated short-time withstand current 25 kA for 3 seconds, rated peak withstand current 63 kA for climatic conditions at the site, mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level for current complete all as specified and as directed.
M& L for servicing of 11 kV gang operated air break switch by cleaning the contact, pin insulator with CTs and applying petroleum jelly at the contact point and down rod links for smooth operation including replacing the rusted, corroded bolts, nuts (using galvanised iron nuts) along with replacing the burn aluminium thimbles and defective insulators, male and female contact as required at the site complete all as specified and as directed. Note: - (1) Insulator, male (moving) and female (fixed) contact shall be measured and paid separately under the relevant items. (2) The cost for replacement of aluminium thimbles, GI nuts, bolts, washers, lubricating, materials etc. shall be deemed to be included in the unit rate quoted by the contractor for the item.
Supply only male contact /moving contact blade for gang operated air break switch (Set of three)
Supply only female contact/fixed contact jaw for gang operated air break switch (Set of three)
Copper tinned striped 11 kV, 200 Amps (Set of three)
M & L for preparing and painting on steel tubular swaged pole 410 SP-55 (11.00 metre long) including cross arms, GI brackets with two coats of aluminium paint over a coat of aluminium red oxide primer on exposed portion and including making strips of width 30 cm upto 1.5 m from the ground level in black and white shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
Dismantling steel poles/ struts, any size, transporting to store and stacking or for schedule of credit
M & L for steel tubular swaged pole 410 SP-55 (11.0 metre long) including CI base plate, finial taper plug, bolts, nuts & screws as per IS 2713 Part -I & II including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer on exposed portion and making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and two coats of anticorrosive paint over a coat of red oxide primer to embedded portion of pole including making good to match existing area complete all as specified and as directed.
Dismantling ACSR or AAC conductors removing to store or taken on schedule of credit complete all as specified and as directed.
Supply, fixing and stringing ACSR (aluminium conductor galvanized steel-reinforced) of any size and type in accordance with site requirement and binding on insulator by means of 22 gauge aluminium binding wire to permissible sag complete all as specified and as directed.
Dismantling earth wire or copper conductor, service feeder or distributor span removing to store or taken on schedule of credit complete all as specified and as directed.
S & F galvanised mild steel wire 3.15 mm or 4 mm dia in overhead lines complete all as specified and as directed.
M & L for stay assembly of stay rod of diameter 20 mm complete with accessories as shown in electrical plate No. 1 (loop type insulator, stay clamps, excavation and concrete measured separately) complete all as specified and as directed.
M & L for loop type insulator (porcelain guy strain insulator), large size, with overall dimensions 140 mm X 85 mm, cable hole dia 25 mm, creepage distance 57 mm, minimum failing load 88000 N, vitreous porcelain, white, brown or green, Designation C as per IS 5300: 1969 complete all as specified and as directed.
Dismantling stay strand any size and type and M & L for hot dip galvanized stay strands of grade I, 7 Nos wires construction, wire diameter 4 mm, nominal strand diameter 12 mm, heavy zinc coating complete all as specified and as directed.
Dismantling cross-arms of mild steel channel or angle sections etc. complete and setting aside for re-use or removing to store or for schedule of credit
M & L for cross arms, bracings, supports, clamps, back plates and stay clamp fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
Restringing only ACSR (aluminium conductor galvanized steel-reinforced) of any size and type in accordance with site requirement and binding on insulator by means of 22 gauge aluminium binding wire to permissible sag and clearing tree branches upto 3 metre distance from conductor complete all as specified and as directed.
M & L for loose filling with broken stone or boulder aggregates of gauge 40 to 80 mm in soakage pits, soakage wells, on open space etc. complete all as specified and as directed.
Surface excavation not exceeding 30 cm deep and averaging 15 cm deep and getting out in hard/ sense soil complete all as specified and as directed.
PRADEEP SISODIYA
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .