Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹61.2 LAccepted-AOC 209 210 AGGARWAL TOWER PLOT NO 2 SECTOR 5 ROHINI NORTH WEST DELHI DELHI 110085 | DELHI | NORTH WEST DELHI | DELHI | 110085 | L1 | Accepted-AOC accepted | |
| 2 | L2₹64.2 L+₹3.1 L (5.03%)Rejected-AOC 315 INDUSTRIAL AREA II PANCHKULA 134113 | PANCHKULA | HARYANA | 134113 | L2 | Rejected-AOC rejected | |
| 3 | L3₹64.5 L+₹3.3 L (5.42%)Rejected-AOC 2ND FLOOR PLOT NO 338 UDHYOG VIHAR PHASE IV GURUGRAM 122015 HARYANA | GURUGRAM | HARYANA | 122015 | L3 | Rejected-AOC rejected | |
| 4 | Rejected-Technical C O SH JITENDER CHAUHAN 542 L MODEL TOWN PANIPAT HARYANA 132103 | PANIPAT | PANIPAT | HARYANA | 132103 | - | Rejected-Technical rejected |
Tender Value
₹52.5 L
EMD Value
₹1.1 L
Closing Date
2 Nov 2023, 5:00 pmClosed
VISHWNATH KHICHI
ED - Rohtak
Provision of fire alarm system has been made in this estimate
2023_HRY_319922_1
202331F5E305 000F 468D 91CC EF075F9991D2667BAR
Open Tender
Electrical Works
Works
180 days
Rohtak
Technical documents as per approved DNIT conditions.
3 documents required · 3 mandatory
₹5,000
₹1.1 L
Yes
30 Jan 2024
12 Oct 2023
3 Nov 2023
12 Oct 2023
2 Nov 2023
12 Oct 2023
Amount
HSR Items
[23.3.6.1]COPPER WIRING IN PVC CONDUIT (SURFACE/RECESS) 6.1. Wiring main and sub mains in two single core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in PVC Conduit etc as required. 1 run of Size 1.50 Sqmm(1/1.40mm)
[23.7.6.1]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.1. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 20 mm dia.
NS Items
SITC of Micro processor based 2 wire fault tolerant, networkable type minimum 2 loop fire alarm and Detection Control Panel (having nos. of loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 characters LCD unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80 LED Indicators. The Panel shall have 3 Serial Ports. The pane\l shall have a built in power supply and battery charger along with maintenance free 24 AH,2 x 12 volt SMF lead acid batteries capable of running for a minimum 24 hours with battery charger complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS/ as per specifications complete in all respect up to the entire satisfaction of Engineer-in – charge of work. Make: Bosch FPA Series/ Honeywell Morley DXE Series/GST-200 (EN) /Siemens Cerberus
SITC of intelligent Analog Addressable type Manual Call Point having Surface or flush mounting option fully compliant to EN 54 having Rotary Decade switches for addressing with Back Box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make: Bosch FPA 1000 Series/ Honeywell Morley DXE/ GST-200 (EN) / Siemens Cerberus
SITC of Addressable Loop powered hooter with strobe complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make: Bosch/ Honeywell Morley/GST/Siemens Cerberus.
SITC of addressable Control Relay Module with flexible network structur4es with a maximum switching current of 1 A @ 30V DC shall be EN54/UL/VDS Certification with all labour and material required to complete the job in all respect upto the entire satisfaction of Engineer-in-charge of the work Makes: Bosch / Siemens Cerberus / Honeywell Morley /GST.
`SITC` of online UPS with rack and required batteries 1KVA Make: Microtek/Luminous/AARKEY/APC
`SITC` of intelligent Analog Addressable type Smoke Detector that combine photo Electronic and fixed temp thermal with inbuilt isolator or isolator base complete with LED Hard Addressable Having rotary decade Address switches, with Mounting Base detectors without inbuilt isolator should be provided separate isolator after 20 detectors Complete as required conforming to BS 5839 standards and duly approved by EN54/UL/VDS respect up to the entire satisfaction of Engineer – in Charge of work. Make: Bosch /Honeywell Morley /GST/Siemens Cerberus
`SITC` of addressable heat detector with fixed and rate of raise feature including mounting base with LED etc. complete as required. Each Detector should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005. Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/VDs/UL certification. (Detectors without inbuilt isolators may be considered with an additional isolator Module after 20 detector in the loop. detector) Make: Bosch, GST / Siemens Cerberus/ Honeywell Morley
SITC of Analog Addressable type Active Repeater panel with Backlit LCD Display, having controls for reset, mute, Accept, Silence alarms and self test conforming to BS5839 standards and Duly approved by EN54/UN54/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer in Charge of work.(Make: Bosch / Honeywell Morley /Siemens Cerberus / Edwards.
SITC of UL/EN54/LPCB listed and FM. Approved Line isolating for isolation the section of circuit in case of short in the addressable Loop wiring Makes: Bosch / Siemens Cerberus / Honeywell Morley /Edwards
SITC of Glow Type EXIT Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink sulphate as bare chemical class 1 material PSPA fixed on 3mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including all accessories upto the entire satisfaction of Engineer-in-Charge of the work. Make:-Glolite/PES/OMEX
SITC of minimum 1000 Mtr. Range Kheraj / National make SIRON generator provided at the roof of the building with separate Power SITC, relay complete in all respect. Make National / Kheraj
SITC of 6 watt ceiling / wall mounted speaker complete in all respect. Make: Bosch, Honeywell, Henrich
`SITC of Intelligent Analog Addressable Type Monitor Modules` having option of RAIL or Surface Mounting with Tri Color LED status indicator with Built in Short Circuit Isolators having Visible Rotary Decade Address Switch from 01-99 dully approved to GEA GEW1-082 conforming to BS5839 Standards and Duly approved by EN54/LPCB/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. Makes-Bosch/Honeywell Morley /Siemens Cerberus/Edwards
Insat Techno Services
Netromics Engineering Solutions Private Limited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .