| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply and fixing steel tubular pole, swaged, complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-55 ( 11 meter long) complete all as specified and directed .
Note:- Earth work and PCC shall be measured and paid separately as these respectively | 2 | Each | - | - |
| 2 | Supply and fixing mild steel galvanised stay assembly set complete comprising of 14mm dia, 400mm long stay bow, 2150mm long stay rod 20mm dia, 300mm x 300mm x 6mm stay plate, thimble, loop insulator large size all as shown in electrical plate No.1 of MES Schedule part-I 2010 complete all as specified and directed.
Note:- PCC, earth work and Insulators etc shall be measured and paid separately. | 2 | Each Set | - | - |
| 3 | Supply and fix gang operated air break switches, triple pole, manually operated, mounted on insulators and steel frame, with operating mechanism worked from ground level Vertical type for rating upto 400 Amps, 11000 volts complete with GI operating pipe of heavy duty complete all as specified and directed. | 3 | Each | - | - |
| 4 | Supply and fixing drop out fuse assembly complete set with Insulator-02 Nos and connected accessories for 11000 Volts grade of 400 Amps capacity complete all as specified and directed. | 1 | Each set of three | - | - |
| 5 | Supply & fix lightening arrestor linear resistance type distribution class discharge capacity 65 kilo amp suitable for 11 KV system pole mounting type conforming to IS - 3070 Part-I complete all as specified and as directed. | 1 | Set of three | - | - |
| 6 | M& L pin type/post top , porcelain, vitreous, white, brown or green insulator, 150 mm height, 150 mm dia for 11 KV grade including one galvanised iron washer, nut and pin complete all as specified and directed. | 3 | Each | - | - |
| 7 | M&L of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed. | 5 | Per Qtl | - | - |
| 8 | Supply, installation, testing and commissioning of Step down copper wound transformer of Capacity 400 KVA (LEVEL 3), outdoor type complete with standard fittings and accessories, HT 11 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit (tap range +5% in steps of 2.5% in 11KV side), all as per IS:1180 (Level 3) Oil Cooling with fins vector group: DYN 11, incl initial oil fitting complete all as specified incl the following accessories:-
(a) Three numbers porcelain bushing HT,11KV with Brass bushing Rod, Nuts, Bolts and washers etc inside cable end box
(b) One cable box LT Side consisting of 4 numbers porcelain with brass bushing rods complete with nuts and washers suitable for runs of 3.5 Core LT UG Cables
(c) Oil Conservator with filter type drain valve and oil level Guage
(d) Dehydrating breather with fast feel of Dehydrating agent
(e) Explosion Vents
(f) thermometer pocket on tank cover
(g) Rating Plate on terminal marking plate
(h) Earthing arrangement (i) Oil drain filter valve (j) Oil Drain Valve
(k) Lifting Hook (l) Oil Conservator with filling hole and cap
(m) Air release valve plug
(n) Four Plate solid Cast steel detachable rollers
(o) Earth Bushing for Neutral Outside the cable box for providing independable earthing for neutral
(p) Suitable size of Channel on foundation for fixing the transformer with joint and stoppper
(q) PCC Platform complete for transformer | 1 | Each | - | - |
| 9 | Supply, installation, testing and commissioning of Step down copper wound transformer of Capacity 500 KVA (LEVEL 3), outdoor type/indoor, complete with standard fittings and accessories, HT 11 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as perIS:1180 (Level 3) Oil Cooling with fins vector group: DYN 11, incl initial oil fitting complete all as specified incl the following accessories:-
(a) Three numbers porcelain bushing HT,11KV with Brass bushing Rod, Nuts, Bolts and washers etc inside cable end box
(b) One cable box LT Side consisting of 4 numbers porcelain with brass bushing rods complete with nuts and washers suitable for runs of 3.5 Core LT UG Cables
(c) Oil Conservator with filter type drain valve and oil level Guage
(d) Dehydrating breather with fast feel of Dehydrating agent
(e) Explosion Vents
(f) thermometer pocket on tank cover
(g) Rating Plate on terminal marking plate
(h) Earthing arrangement (i) Oil drain filter valve (j) Oil Drain Valve
(k) Lifting Hook (l) Oil Conservator with filling hole and cap
(m) Air release valve plug
(n) Four Plate solid Cast steel detachable rollers
(o) Earth Bushing for Neutral Outside the cable box for providing independable earthing for neutral
(p) Suitable size of Channel on foundation for fixing the transformer with joint and stoppper
(q) PCC Platform complete for transformer | 2 | Each | - | - |
| 10 | Supply, stringing and fixing of Aluminium conductor steel reinforced (ACSR) OH conductor of any type including binding wire complete all as specified and directed. | 0.5 | Per Qtl | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.32 MB
Tender1739.pdf
Tender Documents • 0.61 MB
BOQ_880405.xls
BOQ • 0.48 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].