Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.8 CrAccepted-AOC | ₹4.8 Cr | L1 | Accepted-AOC Being Lowest |
| 2 | L2₹5.0 Cr+₹24.2 L (5.09%)Rejected-Finance | ₹5.0 Cr+₹24.2 L (5.09%) | L2 | Rejected-Finance Not Being Lowest |
| 3 | L3₹5.1 Cr+₹31.3 L (6.58%)Rejected-Finance | ₹5.1 Cr+₹31.3 L (6.58%) | L3 | Rejected-Finance Not Being Lowest |
| 4 | L4₹5.1 Cr+₹36.3 L (7.64%)Rejected-Finance PLOT NO 46 WARD NO 08 OPPOSITE RADIO TOWER SAGAR ROAD TILAK NAGAR BIKANER 334003 RAJ | BIKANER | BIKANER | RAJASTHAN | 334003 | ₹5.1 Cr+₹36.3 L (7.64%) | L4 | Rejected-Finance Not Being Lowest |
| 5 | L5₹5.2 Cr+₹45.5 L (9.58%)Rejected-Finance | ₹5.2 Cr+₹45.5 L (9.58%) | L5 | Rejected-Finance Not Being Lowest |
Tender Value
₹5.2 Cr
EMD Value
₹5.8 L
Closing Date
6 Sept 2022, 6:00 pmClosed
Chief Engineer Bathinda, Bathinda Mil Stn
HQ Chief Engineer Bathinda Zone Bathinda Mil Stn - 151004
AUGMENTATION OF WSS FOR EAST and SOUTH CAMP AT MFFR MIL STN
2022_MES_535179_1
CE BTZ/BKN/TOKEN-10 OF 2022-23
Open Tender
Civil Works
Lump-sum
540 days
Bikaner
As per NIT
9 documents required · 9 mandatory
₹3,000
GE (N) Bikaner
₹5.8 L
Yes
30 Sept 2022
1 Jul 2022
9 Sept 2022
1 Jul 2022
6 Sept 2022
23 Aug 2022
Amount
Lump sum price worked out by the tenderer for "Building / Structure Work" as listed in Schedule ‘A’ Section - I.
Lump sum price worked out by the tenderer for “BITUMINOUS ROAD WORKS" as listed in Schedule ‘A’ Section - II (Part-I)
Sch 'A' Sec - II (Part-II), (BITUMINOUS ROAD WORK)
Material and labour for continous Jodhpur stone slab edging 7.5cm to 10cm thick, 30cm wide (for depth of edging) and 35 to 45cm long, lad dry vertically jointing and pointing in CM (1:4), each stone slab self faced on both the vertical sides, edges slightly true and square on top edge hammer dressed for the full thickness so that the depression from the straight edge held against the surface shall not exceed 20mm between two slabs including excavation and embedding to depth required and temping ground around stone edging, returning filling and disposal of surplus soil to a distance not exceeding 50m, complete all as specified and as directed.
Thermo plastic road marking 2mm thick ainting (lines, dashes, arrows, letters etc on new or previously treated road surfaces) with road safety spikeries glass beads including preparation of new or previously treated road surface and applying paint by using special applicater machine with heating arrangement complete all as specified and as directed by Engineer-In-Charge.
Subtotal
Lump sum price worked out by the tenderer for “SECURITY WALL, CHAIN LINK FENCING, AND STEEL GATE WORKS" as listed in Schedule ‘A’ Section - III
Lump sum price worked out by the tenderer for “EXTERNAL WATER SUPPLY WORKS" as listed in Schedule ‘A’ Section - IV (Part-I)
Sch 'A' Sec - IV (Part-II) (EXTERNAL WATER SUPPLY WORKS)
Supply, Fixing, testing, and commissioning Digital water level indicator (digital size 100mm) with five stage Magnetic level sensing probe unit made of stainless steel (SS-304) of minimum 16 mm dia probe stem customized to depth of the tank and sensors epoxy sealed in the probe stem actuated by float that moves on the probe stem with the level of water in the tank and reading shown in LED digital panel including connection from probe unit to panel and panel to DB with copper conductor cable of suitable size as per manufacturer instructions drawn through & including 20 mm dia PVC rigid conduit (heavy duty, ISI marked) fixed along RCC pillar/wall surface including all fitting arrengement i.e. PVC clamp, rawl plug, screw terminal etc. Level indicator should be complete with alarm on low and high level (both visual and Audio) along with by pass facility for audio alarm complete all as specified and as directed. Make: Actice controls/ RAWACO/Century21st/Unison/Alphatech
.Supply and fixing 150mm dia sluice valve PN 1:0, ISI marked confirming to IS-14846, flanged and drilled, steel spindle and iron wheel, brass ring including jointing material such as nuts, bolts, washers and rubber sheet etc all directed by Engr-in-Charge Make as per group one
.Supply and fixing 100mm dia sluice valve PN 1:0, ISI marked confirming to IS-14846, flanged and drilled, steel spindle and iron wheel brass ring including jointing material such as nuts, bolts, washers and rubber sheet etc all directed by Engr-in-Charge
Supply and Fixing foot valve of any type & in any condition CI Foot Valve size 100 mm dia conforming to IS suitable for 100mm bore pipe fianged type including jointing material i.e rubber gasket, nut, bolts and washers etc.complete all as required at site.
Supply and fixing cast iron double air relase valve isolating type (ISI marked), flanged type and drilled, confirming to IS-14845, suitable for 80mm bore pipe including jointing materials such as nuts, bolts, washers, rubber gaskets etc complete all as specified and as directed.
Supplying, laying, jointing and testing Ductile iron pipe class K-9 confirming to IS : 8329 of bore 200 mm (ISI marked), spigot & socketed ends centrifugally cast suitable for rubber tyton joints complete all as specified and as directed. Note : (a) Earth work and DI specials/ fittings shall be measured and paid separetly. (b) Cost of joints including jointing materials shall deemed included in unit rate quoted by contractor.
Supplying, laying, jointing and testing Ductile iron pipe class K-9 confirming to IS : 8329 of bore 150 mm (ISI marked), spigot & socketed ends centrifugally cast suitable for rubber tyton joints complete all as specified and as directed. Note : (a) Earth work and DI specials/ fittings shall be measured and paid separetly. (b) Cost of joints including jointing materials shall deemed included in unit rate quoted by contractor.
Supplying, laying, jointing and testing Ductile iron pipe class K-9 confirming to IS : 8329 of bore 100 mm (ISI marked), spigot & socketed ends centrifugally cast suitable for rubber tyton joints complete all as specified and as directed. Note : (a) Earth work and DI specials/ fittings shall be measured and paid separetly. (b) Cost of joints including jointing materials shall deemed included in unit rate quoted by contractor.
Material and labour for DI pipe cutting upto 150 mm dia for reducing to required length for insertion of new branches, tees, collar, tail pieces etc in position complete all as specified. Note : 1. Excavation ,earth works required for job are deemed to be included in the rate quoted by the Tenderer. 2 CI/DI fitting to be measured and paid seperatly
Excavation by trenchless technology for boring of holes under road, pavement, hard-standing using trenchless boring machine or by means of manual manpower suitable for inserting upto 200 mm dia pipe including removal of surplus soil and making good distrub surface complete all as specified and as directed. NOTE:- Pipe for inserting as required shall be measured and paid for separately.
Material and labour for Construction of brick masonary valve pit chamber size 120 X120 X120 cm (internal dimension) using sub class 'B' bricks complete including excavation & earth work, returning fillig and disposal of surplus soil to distance not exceeding 50m and deposited where directed, PCC 1:5:10 type E-2 using 40 mm graded stone aggregate in foundation, coping on top in PCC 1:2:4 type B-2 using 20 mm graded stone aggregate, brick work in cement mortar (1:4), inner plaster 12 mm thick in cm (1:4) finished even and smooth and pionting flush externally as the work proceeds in the same mortar, MS sheet cover 3.15mm thick mounted on angle iron frame of size 40 x 40 x 6mm with handle and locking arrangement duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and embeded portion of MS work duly applying black bitumenous paint before embeded complete all as specified and as directed and shown on drawings.
Supply,installation,testing and commissioning of pump set centrifugal type mounted on common base foundation electric motor driven complete with all accessories and comprising of the following:- ( RD-160)
Pump centrifugal horizontal mounting type horizontal split type, cast iron body, multistage with CI impellers and stainless steel shaft 1000LPM discharge at 100 metre head, directly coupled with electric motor,1500 RPM
Squireel cage induction motor TEFC Type Energy IE-2, 3 phase 415 volts 50 c/s AC supply,1450 RPM suitable for above pump set but not less then 50 HP, mounted on common base foundation and directly coupled with above pump set and motor.
Suction pipe line using 100 mm dia class K9, DI flanged pipe from pump to Jack well (suitable length required) including all DI flanged fittings and making flanged joint with nuts,bolt, washers etc complete.
Delivery line of pump set using 200 mm dia flanged delivery pipe DI class k9 from pump to delivery header (approx distance between pump to delivery head upto 3 RM) including DI flanged fittings and joint with nut,bolts,washer etc complete. (Sluice valve & Reflex valve in delivery line shall be measured and paid separetaly)
Electrical cable PVC insulated, 3core 16 sqmm flexible drawn through and including 63 mm dia PVC pipe (4 kg/Sqcm) from motor to starter panel for star and delta connections separately complete with copper lungs, cable gland etc.
Bourden's type pressure gauge 100 mm dial type on delivery of pump set.
Common base foundation for pump set made of ISMC 100 suitable for above pump set as for manufacturers recommendation.
PCC foundation in CM 1:2:4 type B-2 using 20 mm graded aggregate 20 cm above GL and 30 cm below GL including grounding of eye bolts nuts etc for pump set of adequate size as per manufactureres reccommendations.
Supply,installation,testing and commissioning of pump set centrifugal type mounted on common base foundation electric motor driven complete with all accessories and comprising of the following:- ( South camp -02 and East camp -02)
Pump centrifugal horizontal mounting type horizontal split type,cast iron body, multistage with CI impellers and stainless steel shaft 1350LPM discharge at 45 metre head, directly coupled with electric motor,1500 RPM
Squireel cage induction motor TEFC Type Energy IE-2, 3 phase 415 volts 50 c/s AC supply,1450 RPM suitable for above pump set but not less then 30 HP, mounted on common base foundation and directly coupled with above pump set and motor.
Suction pipe line using 100 mm dia class K9, DI flanged pipe from pump to Jack well (suitable length requried) including all DI flanged fittings and making flanged joint with nuts,bolt,washers etc complete.
Delivery line of pump set using 200 mm dia flanged delivery pipe DI class k9 from pump to delivery header (approx distance between pump to delivery head upto 3 RM) including DI flanged fittings and joint with nut,bolts,washer etc complete. (Sluice valve & Reflex valve in delivery line shall be measured and paid separetaly)
Electrical cable PVC insulated, 3core 10 sqmm flexible drawn through and including 63 mm dia PVC pipe (4 kg/Sqcm) from motor to starter panel for star and delta connections separately complete with copper lungs, cable gland etc.
Bourden's type pressure gauge 100 mm dial type on delivery of pump set.
Common base foundation for pump set made of ISMC 100 suitable for above pump set as for manufacturers recommendation.
PCC foundation in CM 1:2:4 type B-2 using 20 mm graded aggregate 20 cm above GL and 30 cm below GL including grounding of eye bolts nuts etc for pump set of adequate size as per manufactureres reccommendations.
Supply,installation,testing and commissioning of pump set centrifugal type mounted on common base foundation electric motor driven complete with all accessories and comprising of the following:- ( RD-535)
Pump centrifugal horizontal mounting type horizontal split type, cast iron body, multistage with CI impellers and stainless steel shaft 1200LPM discharge at 53 metre head, directly coupled with electric motor,1500 RPM
Squireel cage induction motor TEFC Type Energy IE-2, 3 phase 415 volts 50 c/s AC supply,1450 RPM suitable for above pump set but not less then 30 HP, mounted on common base foundation and directly coupled with above pump set and motor.
Suction pipe line using 100 mm dia class K9 ,DI flanged pipe from pump to Jack well (suitable length requried) including all DI flanged fittings and making flanged joint with nuts,bolt,washers etc complete.
Delivery line of pump set using 200 mm dia flanged delivery pipe DI class k9 from pump to delivery header (approx distance between pump to delivery head upto 3 RM) including DI flanged fittings and joint with nut,bolts,washer etc complete. (Sluice valve & Reflex valve in delivery line shall be measured and paid separetaly)
Electrical cable PVC insulated, 3core 10 sqmm flexible drawn through and including 63 mm dia PVC pipe (4 kg/Sqcm) from motor to starter panel for star and delta connections separately complete with copper lungs, cable gland etc.
Bourden's type pressure gauge 100 mm dial type on delivery of pump set.
Common base foundation for pump set made of ISMC 100 suitable for above pump set as for manufacturers recommendation.
PCC foundation in CM 1:2:4 type B-2 using 20 mm graded aggregate 20 cm above GL and 30 cm below GL including grounding of eye bolts nuts etc for pump set of adequate size as per manufactureres reccommendations.
Material & Laeour for disconnecting suction and delivery connections of Existing Pumpset of any capacity/make at RD-535 including disconnecting electric connection from starter to motor LT panel board carefully without causing damage to the existing installed equipment and transporting of same to Gourisar PHED complex (qapprox 7 KM distance) with all Conneecting accessories , LT panel board and installing the same with all jointing material complete all as specified NOTE (a) All necessary T & P and transportation charges are deemed to included in item rate. (b) Necessary jointing material/ fittings required to complete the job is also deemed to be included in the quoted rate and nothing extra is admissible to the contractor on this account
Supply installation, testing and commissioning of silent Diesel Engine driven Generating set, capacity 40 KVA outdoor type, 415 Volts, 3 phase 4 wire, 1500 RPM, liquid cooled engine as per IS 10001/10002 and brushless Alternator as per IS: 13364 complete with foundation (as per OEM design), mechanical type governor, PF 0.8, control panel with Microprocessor controller with necessary meters and sound proof canopy as per CPCB norms and with maintenance free battery (as recommended by manufacturer of DG set) as per IS 14257, inbuilt battery charger and suitable size 3.5 core XLPE armoured electric cable from DG set to change over of electric panel of pump set and connection complete”.
Diesel engine: Diesel engine 4 stroke water cooled electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 47°C, 50% RH and conforming to BS 5514, BS 649, IS 10000 capable of taking 10 % over loading for one hour after 12 hour of continuous operation. The engine will be fitted complete with all the required accessories.
Engine mounted instrument panel fitted with and having digital display for following:- (i) Start top switch with key. (ii) Water temperature indication. (iii) Lubrication oil temperature indication. (iv) Battery charging indication. (v) RPM indication (vi) Over speed indication. (vii) Low lubrication oil trip indication (viii) Engine hour indication.
Alternator- synchronous alternator rated at 40 KVA, 415 Volts at 1500 RPM 3 Phase 50 Hz, AC supply with 0.8 lagging power factor at 47°C, 50 % RH. The alternator shall be having SPDP enclosure, brushless, continuous duty, self excitation and self regulated through AVR confirming to IS - 4722/BS 2613 suitable for tropical conditions and with class F/H insulations
Base frame and foundation. Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendation of manufacturer
Fuel Tank. In built fuel tank for 12 hours fuel capacity, fabricated out of 3 mm thick MS sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class C pipe of suitable dia complete with valves. Level indication and accessories as required as per specification.
Exhaust system Dry exhaust manifold with hospital exhaust silencer and catalytic converter
Starting system. 12 V/24 V starting system comprising of starter motors, Voltage regular and arrangement for initial excitation complete with suitable Nos of maintenance free batteries as per manufacturer design.
Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine and alternator, excitation, discharging hot air in to the atmosphere as per specification.
AMF as per manufacturer instruction for above DG set complete with all accesories shall be provided and the rate of the same shall be deemed to be included in quoted rate and nothing extra shall be admissible to the contractor on this account.
Note :- (a) All arrangement for pre-commissioning test shall be made by contractor with in overall cost quoted. (b) Pre commissioning test shall be carried out by rep of accepting officer. Test shall be carried out for duration of 12hrs..
Supply installation, testing and commissioning of silent Diesel Engine driven Generating set, capacity 62.5 KVA outdoor type, 415 Volts, 3 phase 4 wire, 1500 RPM, liquid cooled engine as per IS 10001/10002 and brushless Alternator as per IS: 13364 complete with foundation (as per OEM design), mehanical type governor, PF 0.8, control panel with Microprocessor controller with necessary meters and sound proof canopy as per CPCB norms and with maintenance free battery (as recommended by manufacturer of DG set) as per IS 14257, inbuilt battery charger and suitable size 3.5 core XLPE armoured electric cable from DG set to change over of electric panel of pump set and connection complete”.
Diesel engine: Diesel engine 4 stroke water cooled electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 47°C, 50% RH and conforming to BS 5514, BS 649, IS 10000 capable of taking 10 % over loading for one hour after 12 hour of continuous operation. The engine will be fitted complete with all the required accessories.
Engine mounted instrument panel fitted with and having digital display for following:- (i) Start stop switch with key. (ii) Water temperature indication. (iii) Lubrication oil temperature indication. . (iv) Battery charging indication. (v) RPM indication (vi) Over speed indication. (vii) Low lubrication oil trip indication (viii) Engine hour indication.
Alternator- synchronous alternator rated at 62.5 KVA, 415 Volts at 1500 RPM 3 Phase 50 Hz, AC supply with 0.8 lagging power factor at 47°C, 50 % RH. The alternator shall be having SPDP enclosure, brushless, continuous duty, self excitation and self regulated through AVR confirming to IS - 4722/BS 2613 suitable for tropical conditions and with class F/H insulations
Base frame and foundation. Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendation of manufacturer
Fuel Tank. In built fuel tank for 12 hours fuel capacity, fabricated out of 3 mm thick MS sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class C pipe of suitable dia complete with valves. Level indication and accessories as required as per specification.
Exhaust system Dry exhaust manifold with hospital exhaust silencer and catalytic converter
Starting system 12V/24V starting system comprising of starter motors, Voltage regulator and arrangement for initial excitation complete with suitable Nos of maintenance free batteries as per manufacturer design.
Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine and alternator, excitation, discharging hot air in to the atmosphere as per specification.
AMF as per manufacturer instruction for above DG set complete with all accesories shall be provided and the rate of the same shall be deemed to be included in quoted rate and nothing extra shall be admissible to the contractor on this account.
Note :- (a) All arrangement for pre-commissioning test shall be made by contractor with in overall cost quoted. (b) Pre commissioning test shall be carried out by rep of accepting officer. Test shall be carried out for duration of 12hrs.
Supply installation, testing and commissioning of silent Diesel Engine driven Generating set, capacity 82.5 KVA outdoor type, 415 Volts, 3 phase 4 wire, 1500 RPM, liquid cooled engine as per IS 10001/10002 and brushless Alternator as per IS: 13364 complete with foundation (as per OEM design), mehanical type governor, PF 0.8, control panel with Microprocessor controller with necessary meters and sound proof canopy as per CPCB norms and with maintenance free battery (as recommended by manufacturer of DG set) as per IS 14257, inbuilt battery charger and suitable size 3.5 core XLPE armoured electric cable from DG set to change over of electric panel of pump set and connection complete”.
Diesel engine: Diesel engine 4 stroke water cooled electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 47°C, 50% RH and conforming to BS 5514, BS 649, IS 10000 capable of taking 10 % over loading for one hour after 12 hour of continuous operation. The engine will be fitted complete with all the required accessories.
Engine mounted instrument panel fitted with and having digital display for following:- (i) Start top switch with key. (ii) Water temperature indication. (iii) Lubrication oil temperature indication. (iv) Battery charging indication. (v) RPM indication (vi) Over speed indication. (vii) Low lubrication oil trip indication (viii) Engine hour indication.
Alternator- synchronous alternator rated at 82.5 KVA, 415 Volts at 1500 RPM 3 Phase 50 Hz, AC supply with 0.8 lagging power factor at 47°C, 50 % RH. The alternator shall be having SPDP enclosure, brushless, continuous duty, self excitation and self regulated through AVR confirming to IS - 4722/BS 2613 suitable for tropical conditions and with class F/H insulations
Base frame and foundation. Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendation of manufacturer
Fuel Tank. In built fuel tank for 12 hours fuel capacity, fabricated out of 3 mm thick MS sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class C pipe of suitable dia complete with valves. Level indication and accessories as required as per specification.
Exhaust system Dry exhaust manifold with hospital exhaust silencer and catalytic converter
Starting system. 12 V/24 V starting system comprising of starter motors, Voltage regular and arrangement for initial excitation complete with suitable Nos of maintenance free batteries as per manufacturer design.
Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine and alternator, excitation, discharging hot air in to the atmosphere as per specification.
AMF as per manufacturer instruction for above DG set complete with all accesories shall be provided and the rate of the same shall be deemed to be included in quoted rate and nothing extra shall be admissible to the contractor on this account.
Note :- (a) All arrangement for pre-commissioning test shall be made by contractor with in overall cost quoted. (b) Pre commissioning test shall be carried out by rep of accepting officer. Test shall be carried out for duration of 12hrs
Supply and fixing100mm dia Non Return valve PN 1:0, ISI marked confirming to IS-5312 Part-I both end flanged swing type with gun metal rings including jointing material such as nuts, bolts, washers and rubber sheet etc all directed by Engr-in-Charge
Supply and fix Aprroved LT panel distribution boards, weather /vermin/dust proof indoor type cubical type, factory fabricated made out 3.15 mm thick MS CRCA sheet powder coated of suitable size fixed on 50x50x6mm angle iron frame on bottom with lugs embedded in PCC 1:2:4 block of suitbale size buried in ground including neccessary earth work etc including seperate Bus Bar chamber having 4 wire 415 volt with aluminium bus bar of capacity 200 amps, including all control wiring for incoming/ out going electric connections with suitable size of copper cable conductor with suitable thimbles compirising of the following ( For RD-160 )
Incoming MCCB 4P 125 Amps, 25 kA-01 Nos
Outgoing MCCB 4P 100 Amps, 16 kA -04 Nos
MCB SPN, 63 Amps -02 Nos
Star delta Starter 50 HP -04 Nos
LED indicating Lamps ( R,Y,B) one set-01
On load change over switch front operated 4 pole 415 volts 125 Amp-01 No
Note :- Drawing of panel shall be approved by GE before fabrication.
Supply and fix Aprroved LT panel distribution boards, weather /vermin/dust proof indoor type cubical type, factory fabricated made out 3.15 mm thick MS CRCA sheet powder coated of suitable size fixed on 50x50x6mm angle iron frame on bottom with lugs embedded in PCC 1:2:4 block of suitbale size buried in ground including neccessary earth work etc including seperate Bus Bar chamber having 4 wire 415 volt with aluminium bus bar of capacity 200 amps, including all control wiring for incoming/ out going electric connections with suitable size of copper cable conductor with suitable thimbles compirising of the following ( For East and South Camp)
Incoming MCCB 4P 125 Amps, 25 kA-01 Nos
Outgoing MCCB 4P 100 Amps, 16 kA -02 Nos
MCB SPN, 63 Amps -03 Nos
Star delta Starter 30 HP -02 Nos
LED indicating Lamps ( R,Y,B) one set-01
On load change over switch front operated 4 pole 415 volts 125 Amp-01 No
Note :- Drawing of panel shall be approved by GE before fabrication.
Supply and fix Aprroved LT panel distribution boards, weather /vermin/dust proof indoor/outdoor type cubical type, factory fabricated made out 3.15 mm thick MS CRCA sheet powder coated of suitbale size fixed on 50x50x6mm angle iron frame on bottom with lugs embedded in PCC 1:2:4 block of suitbale size buried in ground including neccessary earth work etc including seperate Bus Bar chamber having aluminium bus bar fixed type of capacity 200 amps , making electrical connections of incoming and out going cables with suitable thimbles compirising of the following ( For RD-535 )
Incoming MCCB 4P 125 Amps, 35 kA-01 Nos
Outgoing MCCB 4P 100 Amps, 35 kA -04 Nos
MCB SPN, 63 Amps -03 Nos
Star delta Starter 30 HP -04 Nos
LED indicating Lamps ( R,Y,B) one set-01
Note :- Drawing of panel shall be approved by GE before fabrication.
Subtotal
Lump sum price worked out by the tenderer for “EXTERNAL ELECTRIFICATION AND LIGHTENING PROTECTION WORKS" as listed in Schedule ‘A’ Section - V (Part-I)
Sch 'A' Sec - V (Part-II), (EXTERNAL ELECTRIFICATION AND LIGHTENING PROTECTION WORKS)
Supply and installation, testing energy efficient type level-II transformer capacity 63 KVA , 11/.433 KV , 50Hz , Step down outdoor type ONAN Cooled oil immersed Copper wound transformer , complete with first filling of IS 335 ISI marked filtered & dehyrated treansformer oil and other standard fittings/accessories and 7 position ON LOAD circuit tap changer ( Tapping range +7.5% in steps of 2.5 % Each ) with vector group Dyn -11,with provision of HV and LV cable Box Suitable for making connection of incomming HT cable and outgoing LT cable all as per IS 1180-2014 and complete with including all required accessories for installaton of transformer all as specified and directed.
Supply and installation, testing energy efficient type level-II transformer capacityr 100 KVA , 11/.433 KV , 50Hz , Step down outdoor type ONAN Cooled oil immersed Copper wound transformer , complete with first filling of IS 335 ISI marked filtered & dehyrated treansformer oil and other standard fittings/accessories and 7 position ON LOAD circuit tap changer ( Tapping range +7.5% in steps of 2.5 % Each ) with vector group Dyn -11,with provision of HV and LV cable Box Suitable for making connection of incomming HT cable and outgoing LT cable all as per IS 1180-2014 and complete with including all required accessories for installaton of transformer all as specified and directed.
Supply and fixing Aviation obstruction light fitting, twin type with IP 06 protection, comprising of aluminium alloy housing with polycarbonate enclosure and accessories complete with LEDs to be fixed on the OHR with suitable fixing accessories as shown on drawing complete all as specified and as directed. Make :- Bajaj Cat part No BGAV302 LED or equivalent in Philips/Wipro/Crompton
Material and labour for Sub main wiring for connection to aviation light from DB to top of OHR /any other light fittings elsewhere with 2x 1.5 Sqmm+1x1.5sqmm earth wire single core FRLSH grade PVC insulated unsheathed, 1100V grade multistranded copper conductor drawn through & including 20mm dia PVC rigid conduit (heavy duty, ISI marked) fixed along RCC pillar/wall surfaces including all fitting arrangement i.e. PVC clamp, rawl plug, screw, terminal etc., complete all as specified and as directed. Note :-Two runs of copper conductor and one run of PVC conduit including accessories shall be measured and paid as one unit.
Supply and fixing Factory made DB (made out of CRCA sheet) SPN, 04 Way (04 modules) 230/240V, double door, dust and vermin proof, protection class IP-54 with and including 01 No MCB, SPN, 10KA, 10 Amp and 02 Nos MCB, SP, 6 Amp, 'C' curve including fixing arrangement complete all as specified and as directed.
Sand cushioning, with dry and clean local tibba sand (for under ground cable) 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable complete all as specified and as directed. (Note:- (i) Punned thickness shall be considered for payment purpose (ii) Approved local Tibba dry sand free from vegetations, grass and other deleterious substances shall be used.)
Supply and laying Best quality, locally available, sub class ‘B’ bricks (Old Size) for cable protection cover, laid flat and dry in trenches over the cable , perpendicular to the direction of cable complete all as specified and as directed.
S & F epoxy insulator fixed on OHRs wall for along with aluminium strip all as specified and directed by Engineer-in-Charge.
Supply and fixing LT panel pillar box cubical type of suitable size, with bus bar chamber having 4 wire 415 Volts, factory made dust proof vermin proof for out door use made out of CRCA sheet 3.15 mm thick powder coated, machine pressed, both side opening with double door (front & rear) in two shalves with provision of rubber beadings and locking system, danger Notice board infront and rear sides including insulated aluminium bus bar of 250 Amp capacity, 4 strip mounted on porcelain insulator, bus bar chamber shall be provided with inspection covers, each MCCB/ cubical switch shall have be independent opening, panel shall be mounted on angle iron frame and legs made from angle of size 50x50x6mm , frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) complete including all connections/control wiring incoming/out going with suitable size of copper conductor cable, Foundation is not less than 30 cm below ground level and not less than 45 cm above ground level, legs of panels will be grouted in centre of PCC foundation (suitable size of foundation ) centre place will be open for connection of Under ground cables complete all as specified and as directed and comprising with the following :-
MCCB 160 Amp Adjustable thermal setting 36 KA, FP, single frame, thermal magnetic trip (incoming) - 01 No
MCCB 125 Amp 25 KA, FP, single frame thermal magnetic trip (outgoing) - 01 No
Indicating lamps LED type (RYB) -01 set of three.
MCB SPN 32 Amp ( for street light)- 1 No
Note :- Drawing of panel shall be approved by GE before fabrication.
Supply & Fix Thermoplastic (polystreen) juction box having IP 65 protection of size 200 x 160 x 98mm fixed to pole with MS strip nuts bolts, having provision of 3 phase aluminium bus bar and MCB 1 to 6 AMP SPN, complete of Make Hnesel cat No K9255 of equivalent
Supply and fix capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase ,440 V, 50 Hz System for permissible non- linear load 15% of 15 KVAR capacity Each
Supply and fix capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase ,440 V, 50 Hz System for permissible non- linear load 15% of 20 KVAR capacity Each
Supply and fix capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase ,440 V, 50 Hz System for permissible non- linear load 15% of 25 KVAR capacity Each
Note for Item No 45 to 47 :- above mentioned items shall be fixed in Panel (Sr Item No-43)
Material & Labour for Earthing to Transformer / GOD switch / equipments / panels etc with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than 2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to transformer / GOD / Panel / equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including 25x3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed. Note : (a) PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner. (b) Earth testing arrangement shall be made by the contractor as per direction of Engineer-in-charge without any extra cost.
Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metre depth below normal ground level) with top edge of plate at a depth not less than 1.5 mtr below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to galvanized earth wire 04 mm dia with and including bolts, nuts, check nuts and washers of galvanised iron or steel and riveted to earth plate and one end and connecting to main switch board or metallic bodies of HT/LT equipments etc at the other end, GI wire encased in and including 15 mm bore GI light grade pipe with all fittings, from top of electrode to body of equipment fixed with and including flatiron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI light grade and including funnel, wire mesh, copper lugs etc from bottom of earth pit to top of electrode complete with earth pit in PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate and CI cover complete all specified and shown in electrical plate No 03 of SSR Pt-I connecting earth electrode to test point with and including earthing lead including neessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50m, material and labour complete all as specified and as directed by Engineer-in-Charge. (Notes 1. The rate quoted shall be deemed to include for all the above provisions. 2. PCC chamber shall be constructed at least 1.5 m away from the earth electrode and pipe for watering shall be provided in slanting maner) . Note Earth testing arrangement shall be made by the contractor as per direction of Engineer-in-charge without any extra cost.
Supply & Fix sheet metal distribution board, double door, 4 way with 200 amps rated bus bar all as specified and directed by Engineer-in-Charge.
S & F Analoge time switch (with battery back up) , 1 P Module 24 hours program, programmable every 15 min , back up of 100 hours current capacity 16 A, with 1 changeover (1 CO) , Cat part No TA916422 in INDOASIAN or techanically equivalent make L&T,C&S ,HPL
Supply and fixing energy efficient LED street light fitting of 35W pressure die cast aluminium housing/body, heat resistant clear toughened glass, better optics for uniform distribution street/Roadway luminaire, with driver, including electric connection, complete fitting with all accessories and following specifications and all as directed:- (a) Lumen system efficacy of luminaire should be minimum 110 Lumen per watt. (b) Input Voltage range : 140 to 270 volts (c) Temp operating range : Minus 10°C to Plus 50°C (d) Power factor : Minimum 0.95 (e) THD : Max10%. (f) CRI : Morethan 70 and CCT : 5700 K. (g) IP rating : IP66. (h) IK rating : Minimum IK07 (j) Built in potted LED Driver of the make as of the luminaire. (k) LED driver should be complete with all protections viz open/short circuit protection, over voltage protection, all as per standard design of manufacturer. (l) Surge protection 10 kV (inbuilt + extended) (m) Lens - High Efficiency wide angle lens. (n) BIS Approved fixtures and driver (o) Rated life time : 50000 burning hrs (Average 10 to 12 hrs daily)
Material and labour for Brackets made out of GI tubing light grade 40mm dia, or of size as recommended by the manufacturer 1.5 metre long bent to shape at 120 degree angle at half metre from bottom, including two Nos clamps made out of MS Flat iron size 50x3 mm for fixing of bracket on steel tubular/ PCC poles with suitable nuts and bolts including painting to MS clamp and nut bolts with two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
Subtotal
Lump sum price worked out by the tenderer for “Excavation and Earth work" as listed in Schedule ‘A’ Section - VI.
UNITED SAINI BUILDERS
RAJENDER ENTERPRISES
M/S BUDHRAM BISHNOI
SOM BUILDERS
JAGDISH PRASAD & CO
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .