Tender Value
₹2.1 Cr
EMD Value
₹2.5 L
Closing Date
20 Mar 2026, 4:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
ELECT.G
17 conditions · 5 needing a document upload
Financial Eligibility Criteria: (Ref: RB letter No. 2022/CE-I/CT/GCC- 2022/POLICY : Advance Correction Slip No.-1 dt 14.07.2022) The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-I, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
The intending tenderers should possess a valid electrical contractor license at the time of opening of tender, issued by any state government & same should be submitted along with tender documents by all bidders including working contractors of this unit otherwise offer shall be summarily rejected....... IT SHOULD BE NOTED BY THE TENDERER THAT ELECTRICAL LICENSE UNDER RENEWAL AT THE TIME OF TENDER OPENING WILL NOT BE CONSIDERED AND OFFER WILL BE SUMMARILY REJECTED. IT IS THE RESPONSIBILITY OF TENDERER TO UPLOAD VALID ELECTRICAL CONTRACTOR LICENSE ON THE DATE OF TENDER OPENING.
All requisite documents mentioned in clause 3.7 of the tender document attached pertaining to constitution of firm/concern. (As applicable).
31 conditions · 4 needing a document upload
The rate to be quoted by tenderer shall be inclusive of all state/central taxes including GST. THE TENDERER SHOULD UPLOAD VALID GST REGISTRATION CERTIFICATE ALONG WITH THE OFFER.
The tender shall comply with General Condition of contract (GCC),2022 of Indian Railways (file attached). and its latest amendment, if any. The tenderer shall submit the offer after duly satisfying himself/herself with the GCC,2022 in general.
Tenderers are required to upload the Bank details as per Annexure-XII (Real Time Gross Saving (RTGS)/National Electronic Fund Transfer (NEFT) Model Mandate Form)of tender document.
Tenderers are required to upload requisite details as per Annexure-VIIB (DETAILS OF CONTRACTUAL PAYMENT RECEIVED IN LAST THREE FINANCIAL YEARS AND CURRENT FINANCIAL YEAR) without which the offer is liable to be rejected.
Tenderers are compulsorily required to upload Affidavit as per Annexure-XXIV along with tender document, without which the offer will be considered incomplete and will be rejected summarily.
All requisite documents/credentials mentioned in clause 3.5 of the tender document attached pertaining to his/their technical and financial eligibility. (As applicable).
All requisite documents mentioned in clause 3.7 of the tender document attached pertaining to constitution of firm/concern. (As applicable).
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
The firm has to consider that certain cables are laid along platforms as well as along the Railway tracks or any other difficult location. The firm shall be required to make necessary arrangements for timely mobilization of men, materials, and machinery to attend to any fault at short notice. The bidder must consider these requirements while preparing and submitting their offer.
No post tender correspondence for submission of additional documents shall be entertained after opening of the Technical & Commercial offers. Even suo-moto post tender letters of the tenderer/s shall be treated as Null & Void.
This tender complies with Public Procurement Policy (Make in India) Order 2017, dated 15/06/2017, issued by Department of Industrial Promotion and Policy, Ministry of Commerce, circulated vide Railway Board letter no. 2015/RS(G)/779/5 dated 03/08/2017 and 27/12/2017.
IF ANY DISCREPANCY IS FOUND IN THE TENDER DOCUMENT, NAMELY SOR ITEM DESCRIPTION, SPECIAL TENDER CONDITION ETC., CLARIFICATION CAN BE SOUGHT FROM THE OFFICE OF SRDEE/G/DLI, DRM OFFICE, STATE ENTRY ROAD, NEW DELHI.
This tender complies with Railway Board instructions for Startups (recognized by Department of Industrial Policy and Promotion, Ministry of Commerce and Industry) for exemption from payment of Bid Security as detailed in GCC 2022 as amended from time to time. Such Startup firms may note that no other exemption is applicable to them in this particular tender.
On account payment, contractor shall submitted indemnity bond with validity up to the completion/extended period in the prescribed format (please refer Annexure-XXVIII) at the contractor's cost, vesting the ownership of such material with the railways.
i)After opening of tender, any document/credential pertaining to technical, financial eligibility and available Bid Capacity constitution of firm etc. shall neither be asked nor be entertained/ considered under any circumstances and no claim or representation whatsoever from the tenderer in this regard shall be entertained. Scanned copy of the documents, uploaded by the tenderer shall be clear & readable. However Railway reserves the right to ask for any clarification on the documents/credentials already submitted by the tenderer along with the offer. ii)Tenderer may have to produce the original Documents in physical form at short notice whenever asked by Railway at any stage of tender evaluation process or even after finalization of tender. iii)In E-tender, all submissions of documents are to be uploaded on web-site. There may be last minute hic-cups and delay in uploading the Documents and payment of Earnest Money etc. Tenderer's/Prospective bidders are advised to upload their offer well in time. Railway will not be responsible for any delay/non submission of offer due to any reason whatsoever
Electrical work in connection with Replacement of Rail pole/tubular pole with octagonal pole , cabling and old LED fittings with other associated works at stations over SPR section.
45-R1-SRDEE-G-DLI-2025-26
45-R1-SRDEE-G-DLI-2025-26
Open
Works - General
6 Months
Delhi, Delhi
₹0
₹2.5 L
20 Mar 2026
26 Feb 2026
6 Mar 2026
51 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 2,05,43,261 | ||
| — | 6500.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation((upto 75-100 cm depth and not less than 35 cm wide ), sand cushioning, protective covering and refilling the trench etc. as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Upto 35 sq. mm | — | — | — | 22,88,000 | |
| — | 900.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation((upto 75-100 cm depth and not less than 35 cm wide ), sand cushioning, protective covering and refilling the trench etc. as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Above 95 sq. mm and upto 185 sq. mm | — | — | — | 4,20,300 | |
| — | 750.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation(upto 75-100 cm depth and not less than 55 cm wide & maintaining gap not less than 20 cm between the cables), sand cushioning, protective covering and refilling the trench etc as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest and as per explanatory note. Upto 35 sq. mm | — | — | — | 2,16,000 | |
| — | 300.00 | — | — | ||
| Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation(upto 75-100 cm depth and not less than 55 cm wide & maintaining gap not less than 20 cm between the cables), sand cushioning, protective covering and refilling the trench etc as required as per detail drawing approved by competent authority and conforming to IS 1255 (Reviewed in 2016) or latest and as per explanatory note. Above 95 sq. mm and upto 185 sq. mm | — | — | — | 97,500 | |
| — | 1750.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Upto 35 sq. mm (clamped with 1mm thick saddle) | — | — | — | 1,03,250 | |
| — | 300.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) | — | — | — | 49,200 | |
| — | 5000.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in existing RCC/HUME/Metal pipe/HDPE pipe as per site requirement and satisfaction of railway representative conforming to IS 1255 (Reviewed in 2016) or latest & as per Explanatory Note. Upto 35 sq. mm. | — | — | — | 2,00,000 | |
| — | 1000.00 | — | — | ||
| Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required conforming to IS/IEC 61537:2006 & as per Explanatory Note. 150 mm width X 50 mm depth X 1.6 mm thickness | — | — | — | 7,42,000 | |
| — | 5000.00 | — | — | ||
| Supply & commissioning of HDPE (High Density Poly Ethylene polymers) pipe of Material Grade- PE 63 grade, IS 4984 (or latest) Resistance to chemicals Exceptional resistance to all external and internal corrosion. Resistant to electrolytic corrosion. Working pressure in KGF/CM²) Specified base density- 940 to 958 kg/mtr3, Size (b)Supply of HDPE pipe outer diameter 63 mm, wall thick Min. 3.0mm & Max 3.5 mm. Commissioning to be done in trenches made by dismantling of RCC/concrete done by the contractor & wall surface as per site requirement & as per Explanatory Note. | — | — | — | 7,00,000 | |
| — | 300.00 | — | — | ||
| Constructing brick masonary chamber 45x45x30 cm with bricks in cement mortar 1:4 (1 cement: 4 coarse sand) including 500x450 mm pre cast RCC horizontal grating with frame complete as per standard design. The dimension of the MS flat should be 40x6 mm and RCC standard should be 1:2:4 as per drawing approved by competent authority & as per Explanatory Note. With common burnt clay FPS(non modular) bricks of class designation 7.5. | — | — | — | 7,45,200 | |
| — | 120.00 | — | — | ||
| Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) conforming to DSR 2021 Vol -II (Civil) item no. 15.2.1. & as per Explanatory Note. | — | — | — | 2,40,840 | |
| — | 120.00 | — | — | ||
| Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 meters lead as per direction of Engineer - incharge conforming to DSR 2021 Vol -II (Civil) item no. 15.3 & as per Explanatory Note. | — | — | — | 3,51,360 | |
| — | 120.00 | — | — | ||
| Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level. 1:2:4 (1 Cement : 2 coarse sand (zone- III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) conforming to DSR 2021 Vol -I (Civil) item no. 4.1.3. & as per Explanatory Note. | — | — | — | 8,83,800 | |
| — | 120.00 | — | — | ||
| Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level. 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) conforming to DSR 2021 Vol -I (Civil) item no. 5.1.3. & as per Explanatory Note. | — | — | — | 9,53,400 | |
| — | 300.00 | — | — | ||
| Supply, Laying, Testing & Commissioning of HDPE pipe of 160 mm dia having material grade PE-100, wall thickness PN-6 and confirming to IS-4984 or latest as per IE rules and site requirement for cable laying through HDPE pipe of 160mm diameter by trench less method as per IS 1255 or latest & IE rules and site requirement & as per Explanatory Note. | — | — | — | 3,22,500 | |
| — | 700.00 | — | — | ||
| Supply & erection of hot dip galvanized octagonal pole 5 Mtrs. long Double Arms, confirming to IS 2629/BSEN ISO 1461 latest version with top 70 mm and bottom 130 mm around face made of 3 mm thick, steel base plate size 200 x200x12 mm complete with appropriate sleeve at the top of the pole for mounting arm bracket 300 mm long (or as per site requirement & approval of competent authority ) suitable for LED street light fittings including casting, muffing with cement concrete foundation (1:2:4) painting, earthing and foundation GI nut, bolts with washer and smart pack junction box with 1A single pole MCB and terminals. Pole junction box shall be sealed with water proof tape and display of danger sticker & numbering shall be done with sticker/paint. Pole junction box cover should be non detachable ( with hinge) for anti -theft conforming to IS 800:2007, IS 875 or latest and other relevant IS/IEC standards. Scope of work also include designing of pole for achieving uniform illumination and desired lux level as per Rly. Board guidelines and contractor shall get this design through computer modelling method from reputed manufacturer and will be submitted in hard/soft copy to Railways for approval. Note- Wiring in between pole junction box to fitting shall be done through 3 cores 1.5 sq. mm double insulated weather proof cables conforming to IS 456 & other relevant IS/IEC standards & as per Explanatory Note | — | — | — | 63,12,600 | |
| — | 872.00 | — | — | ||
| Supply, fixing, testing and commissioning of 45 watt LED based street light luminary with cool white light, pressure die cast aluminum housing, IP 66 or better having system complete confirming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per Explanatory Note. | — | — | — | 25,85,480 | |
| — | 50.00 | — | — | ||
| Supply, Fixing, Testing & Commissioning of hot dip galvanized octagonal pole 5 Mtrs. Long double arm in U -shape for illumination of station name board at the platform ends as per site requirement and drawing approved by Railway authority and as per IS and IE rules & Explanatory Note. | — | — | — | 5,25,000 | |
| — | 50.00 | — | — | ||
| Supply, installation, testing and commissioning of all in one solar street lighting system with 05 mtrs high octagonal GI pole as per IS 2629/BSEN ISO 1461, 30 - watt solar street light should be tested as per IS 10322 part- 5 Sec- 3 or IEC 60598-2-3, 120- watt solar panel, lithiumion storage battery 12.8 V /30 Ah complete with ingress protection IP67 complete & as per Explanatory Note. | — | — | — | 14,00,550 | |
| — | 50.00 | — | — | ||
| Supply and erection of anti-climbing device for poles complete as per explanatory note, drawing to be submitted by contractor and approved by competent authority of Railways. | — | — | — | 1,50,350 | |
| — | 600.00 | — | — | ||
| Cutting/removing of existing rail pole/ tubular pole/octagonal pole including over head conductor, bracket, insulators, earth wire, guard wire etc. as per site requirement and instruction of site In charge and after removal of material, it shall be handed over to site incharge and stacked at suitable location. All materials are to be transported from site to Railway Store as decided by Railway administration. Note: Measurement shall be done in items of number of poles dismantled & as per Explanatory Note. | — | — | — | 6,65,400 | |
| — | 45.00 | — | — | ||
| Earthing with 40 mm dia GI pipe class 'B' 4.5 meter long earth electrode as per IS:3043 (latest version)to achieve earth resistance less than 5 ohms including construction of masonry enclosures with hinged cover plate of cast iron with locking arrangement (approx. size 400 mmx 400 mm) on top, provision of earth plate, connections from earth electrode to switch gear/pole as per drawing & as per Explanatory Note. | — | — | — | 2,58,795 | |
| — | 500.00 | — | — | ||
| Supplying and laying 25 mm X 5 mm G.I strip confirming to relevant IS as per IS:3043 (Latest version), fixing on surface or as per site condition, clamping or fixing with suitable arrangement as per site requirement, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm) & as per Explanatory Note. | — | — | — | 72,000 | |
| — | 19.00 | — | — | ||
| Supply, fixing, testing and commissioning of LT distribution board double door outdoor type made up of CRCA sheet, IP 54 phosphatised powder painted with anti corrosion complete with neutral link, earth point, Din rail and prewired confirming to IS:13032, IEC 60947 & IS/IEC 60898-1:2002 or latest of make ABB, Siemens, L&T, Schneider, Legrand or equivalent with following items of matching make to be fixed in distribution board, confirming to & IS/IEC 60898- 1:2002 or latest, IE rules and site requirement. It should be rodent entry proof. It should also include well dressing and coding of circuit & as per Explanatory Note. 63A 4P RCBO 30/100/300mA= 01 No. (Incoming) 6-32A MCB SP ""C"" Series = 09 Nos. (Outgoing) It should be rodent entry proof. It should also include well dressing and coding of circuit IP2X terminal, reversible door with 180 degree opening, cement spill protection, detachable gland at top and bottom and short link for MCBs. It should also include proper tagging on electrical wires/cables which clearly indicate the incoming point or source and outgoing point of wires/cables. | — | — | — | 1,76,966 | |
| — | 8277.00 | — | — | ||
| Supplying and laying 8 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required & Explanatory Note. | — | — | — | 82,770 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
ExplanatoryNote45-R1_1.pdf
ATTACHMENT
TECHSPEC-I.pdf
ATTACHMENT
TECHSPEC-II.pdf
ATTACHMENT
TenderDocument45-R1.pdf
ATTACHMENT
GCC-2022-ACS10_merged.pdf GCC 2022 with ACS
ATTACHMENT
SpecialCondition45-R1.pdf
ATTACHMENT
GCC-2022-ACS10_merged.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .