Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.1 LAccepted-AOC OFFICE NO 101 MALAN PLAZA NEXT TO ESSAR PETROL PUMP NEAR GODAMBLE CORNER RAHATNI PIMPRI DP ROAD RAHATANI PUNE 411 017 | PUNE | PUNE | MAHARASHTRA | 411017 | ₹31.1 L Quoted ₹31.8 L | L1 | Accepted-AOC Being over all reasonable |
| 2 | L2₹34.2 L+₹2.4 L (7.65%)Rejected-Finance | ₹34.2 L+₹2.4 L (7.65%) | L2 | Rejected-Finance Not lowest bidder |
| 3 | L3₹34.6 L+₹2.8 L (8.81%)Rejected-Finance | ₹34.6 L+₹2.8 L (8.81%) | L3 | Rejected-Finance Not lowest bidder |
| 4 | L4₹35.8 L+₹4.0 L (12.7%)Rejected-Finance 704 SILVER DEAL DAFFODIL WING 1 B T KAWADE ROAD PUNE 411 001 | PUNE | PUNE | MAHARASHTRA | 411001 | ₹35.8 L+₹4.0 L (12.7%) | L4 | Rejected-Finance Not lowest bidder |
| 5 | L5₹36.2 L+₹4.4 L (13.9%)Rejected-Finance | ₹36.2 L+₹4.4 L (13.9%) | L5 | Rejected-Finance Not lowest bidder |
Tender Value
₹46.6 L
EMD Value
₹93,120
Closing Date
24 Feb 2021, 6:00 pmClosed
GE CENTRAL KIRKEE
GE CENTRAL KIRKEE RANGE HILLS ROAD KIRKEE PUNE 411003
REPAIR REPLACEMENT OF LT SWITCHGEAR LT UG CABLE OF DIFFERENT SIZE AND ITS CONNECTED WORKS UNDER AGE EM II IN GE C KIRKEE
2021_MES_414612_2
8439/E8 OF 2020-2021
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
KIRKEE
AS PER NIT
7 documents required · 7 mandatory
₹500
Yes
GE CENTRAL KIRKEE
₹93,120
Yes
11 Jun 2021
6 Feb 2021
25 Feb 2021
6 Feb 2021
24 Feb 2021
13 Feb 2021
6 Feb 2021 - 12 Feb 2021
Amount
Dismantling and Taking out old unserviceable feeder pillar/panel boards including discnnecting and removing of all incoming and out going cables gland lugs/thimbles, etc carefuly so that same can be reused with new panels with all connecting accessories and making good to the disturbed wall / floor surface and painting the same with matching paint as of existing wall including material all as specified and directed by Engineer in charge.
Supply, fixing, commissioning and testing LT Distribution panel board (With 50 KA RMS for 1 sec CPRI approved) made out of 2mm thick CRCA sheet for laod bearing members and 1.6 mm thick CRCA sheet for non-load bearing members duly powder coated, RAL 7035 (Siemens gray) with seven tank pre-treatment confirming to IS 8623, in door type with IP 43 protection, totally enclosed weather dust and vermin proof with a single front and rear opening, 415V, 3 phase, 4 wire, AC, 50Hz having aluminium bus bar insulated with PVC sleeves coloured in RYB complete with internal wiring with copper conductor, and foundation with thick angle iron frame grouted in PCC 1:3:6 not less that 0.6 mtrs from ground level or as directed complete suitable for and including of following items (all panels should be with digital multifunctional meters and LED indicating lamps for incoming. All MCCBs (Thermal magnetic and mictoprocessor based ) should be adjustable with Icu= Ics 100% and should be with suitable extended rotary hangle and spreader links at both side. All incoming & outgoing cable entries from bottom and incoming and outgoing cables to be fixed on concreate based or in cable ducts or fixed on wall as per site requirement. Note: 1 .. Drawing should be approved by Engr-in-Charge before manufacturing . Two stage inspection of manufacturing i.e. fabrication before powder coating & during swith gear installation, inspection /factory visit of Engg-in-Charge is compulsory to be arranged by contractor at no extra cost. 3. Contractor should visit the site to understand the scope of work before quoting the tender.
INCOMER : MCCB FP, 25 kA, 250 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4202 19 /L&T /ABB
OUTGOINGS a) MCCB FP, 25 kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 55 /L&T /ABB
b) MCCB FP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 53 /L&T /ABB
c) MCB four pole 20 to 32 Amps, 415 volts, 10 kA breaking capacity, 'C' curve Make Legrand Ct No 4086 78-80 /L&T /ABB
All as per Item No.02 above but suitable for and including following accessories :
INCOMER : MCCB FP, 25 kA, 250 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4202 19 /L&T /ABB
OUTGOINGS a) MCCB FP, 25 kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 55 /L&T /ABB
b) MCCB FP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 53 /L&T /ABB
c) MCB four pole 20 to 32 Amps, 415 volts, 10 kA breaking capacity, 'C' curve Make Legrand Ct No 4086 78-80 /L&T /ABB
All as per Item No.02 above but suitable for and including following accessories :
INCOMER : MCCB FP, 36 kA, 800 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4222 57 /L&T /ABB
OUTGOINGS a) MCCB FP, 36 kA, 630 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4220 09 /L&T /ABB
b) MCCB FP, 25 kA, 200 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4202 18 /L&T /ABB/
c) MCCB FP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 53 /L&T /ABB
d) MCB four pole 20 to 32 Amps, 415 volts, 10 kA breaking capacity, 'C' curve Make Legrand Ct No 4086 78-80 /L&T /ABB
All as per Item No.02 above but suitable for and including following accessories :
INCOMER : MCCB FP, 36 kA, 400 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4220 07 /L&T /ABB
OUTGOINGS a) MCCB FP, 25 kA, 160 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 57 /L&T /ABB
b) MCCB FP, 25 kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 55 /L&T /ABB
c) MCCB FP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 53 /L&T /ABB
All as per Item No.02 above but suitable for and including following accessories :
INCOMER : MCCB FP, 36 kA, 630 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4220 09 /L&T /ABB
OUTGOINGS a) MCCB TPN, 25 kA, 250 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 420053 - 04 Nos. /L&T /ABB
b) MCCB TPN,25 kA,160 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 420055 - 02 No. /L&T /ABB
c) MCCB FP, 25 kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 55 /L&T /ABB
All as per Item No.02 above but suitable for and including following accessories :
INCOMER : MCCB TPN, 25 kA,200 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 422021 - 01 No. /L&T /ABB/C&S
OUTGOINGS a) MCCB FP, 25 kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 55 /L&T /ABB
b) MCCB FP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 53 /L&T /ABB
c) MCB four pole 20 to 32 Amps, 415 volts, 10 kA breaking capacity, 'C' curve Make Legrand Ct No 4086 78-80 /L&T /ABB
All as per Item No.02 above but suitable for and including following accessories :
INCOMER : MCCB FP, 25 kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 55 /L&T /ABB
OUTGOINGS a) MCCB FP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 53 /L&T /ABB
All as per Item No.02 above but suitable for and including following accessories :
INCOMER :MCCB FP, 36 kA, 630 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4220 09 /L&T /ABB
OUTGOINGS a) MCCB FP, 36 kA, 400 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4220 07 /L&T /ABB
b) MCCB TPN,25 kA,250 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 420055 /L&T /ABB
c) MCCB FP, 25 kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 55 /L&T /ABB
All as per Item No.02 above but suitable for and including following accessories :
INCOMER : MCCB FP, 36 kA, 400 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4220 07 /L&T /ABB
OUTGOINGS a) MCCB FP, 25 kA, 200 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4202 18 /L&T /ABB/
b) MCCB FP, 25 kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 55 /L&T /ABB
b) MCCB FP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 53 /L&T /ABB
All as per Item No.02 above but suitable for and including following accessories :
INCOMER :MCCB FP, 36 kA, 630 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4220 09 /L&T /ABB
OUTGOINGS a) MCCB FP, 25 kA, 200 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4202 18 /L&T /ABB/
b) MCCB FP, 25 kA, 160 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 55 /L&T /ABB
b) MCCB FP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 53 /L&T /ABB
All as per Item No.02 above but outdoor type IP 65 and suitable for and including following accessories :
INCOMER ; MCCB FP, 25 kA, 200 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4202 18 /L&T /ABB/
OUTGOINGS a) MCCB FP, 25 kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 55 /L&T /ABB
b) MCCB FP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 53 /L&T /ABB
All as per Item No.12 above but suitable for and including following accessories :
INCOMER ; MCCB FP, 25 kA, 100 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 55 /L&T /ABB
OUTGOINGS a) MCCB FP, 25 kA, 63 AMPS with thermal magnetic release, Ics = 100% Icu, Adjustable Over Load setting: 0.8 -1.0 x In, with spreader links , insulating shields and vary depth rotary handle Make - Legrand, Cat No. - 4200 53 /L&T /ABB
Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix MCCB thermal magnetic release 4P 25 KA 160 Amps Make Legrand Cat No 4200 57 /L&T /ABB with one way metal inclosure Cat No 5078 01 /L&T /ABB and making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complate all as specifide and directed.
Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix MCCB thermal magnetic release 4P 25 KA 100 Amps Make Legrand Cat No 4200 55 /L&T /ABB with one way metal inclosure Cat No 5078 01 /L&T /ABB and making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complate all as specifide and directed.
Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix MCCB thermal magnetic release 4P 25 KA 63 Amps Make Legrand Cat No 4200 53 /L&T /ABB with one way metal inclosure Cat No 5078 01 /L&T /ABB and making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complate all as specifide and directed.
Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix MCB "C" curve TPN 10 KA 20 to 32 Amps Make Legrand Cat No 4086 78-80 /L&T/ C&S and one way metal inclosure Make Legrand Cat No 507793 /L&T/ C&S including making good the disturbed suface of wall including material complate all as specifide and directed.
Supply and laying and fixing on wall /laid in floor/duct/drawn through conduit XLPE insulated PVC bedded armored heavy duty electric cable 1100 Volt grade with aluminum conductor of size 4 x 10 Sq mm all as specified and directed . Make Policab/ Gloster/ Finolex/ Havells
All as per item No 18 above but cable size 4x16 sqmm
All as per item No 18 above but cable size 4x25 sqmm
All as per item No 18 above but cable size 3.5x35 sqmm
All as per item No 18 above but cable size 3.5x50sqmm
All as per item No 18 above but cable size 3.5x70sqmm
All as per item No 18 above but cable size 3.5x120 sqmm
All as per item No 18 above but cable size 3.5x400 sqmm
Supply only aluminium tube terminal ( Lug) heavy duty suitable for XLPE conductor 50 sqmm size make Dowells / Comet
Supply only aluminium tube terminal ( Lug) heavy duty suitable for XLPE conductor 70 sqmm size make Dowells/ Comet
Supply only aluminium tube terminal ( Lug) heavy duty suitable for XLPE conductor 95 sqmm size make Dowells/ Comet
Supply only aluminium tube terminal ( Lug) heavy duty suitable for XLPE conductor 120sqmm size make Dowells/ Comet
Supply only aluminium tube terminal ( Lug) heavy duty suitable for XLPE conductor 150 sqmm size make Dowells/ Comet
Supply only Copper tube terminal ( Lug) heavy duty suitable for XLPE conductor 10 sqmm size make Dowells / Comet
Supply only Copper tube terminal ( Lug) heavy duty suitable for XLPE conductor 16 sqmm size make Dowells / Comet
Supply only Copper tube terminal ( Lug) heavy duty suitable for XLPE conductor 25 sqmm size make Dowells / Comet
Supply only Copper tube terminal ( Lug) heavy duty suitable for XLPE conductor 35 sqmm size make Dowells / Comet
M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 100 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed. NOTE - (a). Cost of cutting out of trench for accomodating the machine and making good to the surface after completion of the job are deemed to be inclusive in the quoted rate. (b). Contractor has to rectify any damage to cables, pipes or other govt. property free of cost to the complete satisfaction of Engr-in-Charge. (c). Any extra excavation or the any other connected jobs required for satishfactorly execution of this item is included in the rate of this item.
Techmat trading solution
Om Construction
M/S - KRUPA ELECTRICALS
Mahindra Electric Stores
AN-ICON Engineering Technologies And Infrastructure Developments Pvt. Ltd
Sachin Electricals
Adinath Technical Services
Leo Enterprises
M/s Vijay Airconditioning Pvt Ltd
CHAITANYA WINDWELL
REKHA ELECTRICALS
Rajan Traders
T.H.ASSOCIATES
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .