Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹44.3 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹45.0 L+₹77,149 (1.74%)Rejected-Finance | L2 | Rejected-Finance Second Lowest | |
| 3 | L3₹47.5 L+₹3.2 L (7.22%)Rejected-Finance | L3 | Rejected-Finance Third Lowest | |
| 4 | L4₹49.8 L+₹5.5 L (12.5%)Rejected-Finance | L4 | Rejected-Finance Fourth Lowest |
Tender Value
₹47.2 L
EMD Value
₹94,500
Closing Date
23 Jul 2024, 6:00 pmClosed
GE AF Sambra
E AF Sambra ATS Sambra Belgaum 591124
SPECIAL REPAIR REPLACEMENT OF ELECTRIC LT OH LINES UG CABLES (PH III) AND PROVN OF POWER SOCKETS AND ASSOCIATED WORKS AT 7(T) MESS (02 JOBS) AT ATS BELAGAVI
2024_MES_661924_1
GE(AF)/SAM/TOK-22 OF 2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF Sambra
Please refer Tender documents
8 documents required · 8 mandatory
₹500
GE AF Sambra
₹94,500
Yes
22 Oct 2024
25 Jun 2024
25 Jul 2024
25 Jun 2024
23 Jul 2024
11 Jul 2024
Amount
Supplying, laying and testing cable XLPE Insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts grade of size 3.5 core 500 sqmm completeall as specified and directed
All as per Srl Item No.01 above but 3.5 core 400 sqmm cable
All as per Srl Item No.01 above but 3.5 core 240 sqmm cable
All as per Srl Item No.01 above but 3.5 core 120 sqmm cable
All as per Srl Item No.01 above but 3.5 core 95 sqmm cable
All as per Srl Item No.01 above but 3.5 core 70 sqmm cable
All as per Srl Item No.01 above but 3.5 core 50 sqmm cable
All as per Srl Item No.01 above but 3.5 core 35 sqmm cable
All as per Srl Item No.01 above but 4 core 25 sqmm cable
All as per Srl Item No.01 above but 4 core 16 sqmm cable
All as per Srl Item No.01 above but 4 core 10 sqmm cable
All as per Srl Item No.01 above but 2 core 10 sqmm cable
Excavation in trenches, not exceeding 1.50m wide and not exeeding 1.50m in depth for foundations, trenches of cable or pipe lines etc or and getting out in hard/dense soil complete all as specified and as directed.
S&F double wall corrugated HDPE Pipe IS-16205, outer dia 160 mm for cable protection in wall/under gorund laying of UG cables including SNAP-FIT Coupler and all fittings as required at site complete all as specified and as directed
All as per Srl Item No.14 above but 120 mm outerdia
All as per Srl Item No.14 above but 75 mm outerdia
All as per Srl Item No.14 above but 50 mm outerdia
All as per Srl Item No.14 above but 40 mm outerdia
M&L for cutting the tar macadam road / hard standings for laying cable and excavating not exe. 60cm wide and n. exc 75cm depth and getting out all as directed including filing back, consolidating etc complete and finishing it with 200mm thick PCC 1:4:8 type D-2 (using 40mm graded stone aggregates) complete all as specified and directed
S&F galvanised iron pipes 150 mm bore, light grade, with all fitting and fixed complete to poles/route/drains etc and ceillings or laid in floors complete all as specified & directed.
All as per Srl Item No.20 above but 100 mm outerdia
All as per Srl Item No.20 above but 80 mm outerdia
All as per Srl Item No.20 above but 50 mm outerdia
All as per Srl Item No.20 above but 40 mm outerdia
Returning filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soil complete all specified and as directed.
Removing excavated materials /soil to a distance not exceeding 50 meters and depositing where directed at a level not exceeding 1.5 meters above the starting point complete all specified and as directed.
S&F 4 Pole MCCB Adjustable Type 500 Amp, 50 Hz, 415 V with rupturing capacity 36 KA complete all as specified and directed Note: MCCB to be fixed in existing Feeder Pillar Box by connecting 750 Apms rated aluminium busbar including removing of old existed busbar in Feeder Pillar Box complete all as specified and directed
Supply, install, testing and commissioning of LT Feeder pillar Box AC 415 V, 50 HZ 3 Phase 4 wire of suitable size to accomodating the following accessories totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, vermin proof indoor type made out of 3.15 mm thick MS sheet protection IP 54, suitable for outdoor use, with bottom cable entry with suitable cable glands structure with angle iron frame work with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter and MCCBs, double hinged doors at front with suitable locking arrangement, Provision of louvers at sides, structure treated under 8 - tank metal treatment process and duly powder coated with 750 Amp's electrical grade aluminium bus bar for phases and neutral complete with suitable digital type meters resin cast CTs, CPRI approved type tested, internal wiring all including the following incoming and outgoing complete all as specified and directed:- Note:- Connection from Main bus bar to Outgoing MCCB should be provided through bus bar of suitable rating instead of copper wires. The pillar box shall be provided with durable and legible Aluminium nameplates for each MCCB containing Qtr No/Bldg No and FPB No.
Supply, install, testing and commissioning of LT Feeder pillar Box AC 415 V, 50 HZ 3 Phase 4 wire of suitable size to accomodating the following accessories totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, vermin proof indoor type made out of 3.15 mm thick MS sheet protection IP 54, suitable for outdoor use, with bottom cable entry with suitable cable glands structure with angle iron frame work with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter and MCCBs, double hinged doors at front with suitable locking arrangement, Provision of louvers at sides, structure treated under 8 - tank metal treatment process and duly powder coated with 750 Amp's electrical grade aluminium bus bar for phases and neutral complete with suitable digital type meters resin cast CTs, CPRI approved type tested, internal wiring all including the following incoming and out going complete all as specified and directed:- Note:- Connection from Main bus bar to Outgoing MCCB should be provided through bus bar of suitable rating instead of copper wires. The pillar box shall be provided with durable and legible Aluminium nameplates for each MCCB containing Qtr No/Bldg No and FPB No.
Supply, install, testing and commissioning of LT Feeder pillar Box AC 415 V, 50 HZ 3 Phase 4 wire of suitable size to accomodating the following accessories totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, vermin proof indoor type made out of 3.15 mm thick MS sheet protection IP 54, suitable for outdoor use, with bottom cable entry with suitable cable glands structure with angle iron frame work with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter and MCCBs, double hinged doors at front with suitable locking arrangement, Provision of louvers at sides, structure treated under 8 - tank metal treatment process and duly powder coated with 750 Amp's electrical grade aluminium bus bar for phases and neutral complete with suitable digital type meters resin cast CTs, CPRI approved type tested, internal wiring all including the following incoming and outgoing complete all as specified and directed:- Note:- Connection from Main bus bar to Outgoing MCCB should be provided through bus bar of suitable rating instead of copper wires. The pillar box shall be provided with durable and legible Aluminium nameplates for each MCCB containing Qtr No/Bldg No and FPB No.
Supply, install, testing and commissioning of LT Feeder pillar Box AC 415 V, 50 HZ 3 Phase 4 wire of suitable size to accomodating the following accessories totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, vermin proof indoor type made out of 3.15 mm thick MS sheet protection IP 54, suitable for outdoor use, with bottom cable entry with suitable cable glands structure with angle iron frame work with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter and MCCBs, double hinged doors at front with suitable locking arrangement, Provision of louvers at sides, structure treated under 8 - tank metal treatment process and duly powder coated with 700Amp's electrical grade aluminium bus bar for phases and neutral complete with suitable digital type meters resin cast CTs, CPRI approved type tested, internal wiring all including the following incoming and outgoing complete all as specified and directed:- Note:- Connection from Main bus bar to Outgoing MCCB should be provided through bus bar of suitable rating instead of copper wires. The pillar box shall be provided with durable and legible Aluminium nameplates for each MCCB containing Qtr Number and FPB No.
Supply, install, testing and commissioning of LT Feeder pillar Box AC 415 V, 50 HZ 3 Phase 4 wire of suitable size to accomodating the following accessories totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, vermin proof indoor type made out of 3.15 mm thick MS sheet protection IP 54, suitable for outdoor use, with bottom cable entry with suitable cable glands structure with angle iron frame work with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter and MCCBs, double hinged doors at front with suitable locking arrangement, Provision of louvers at sides, structure treated under 8 - tank metal treatment process and duly powder coated with 500Amp's electrical grade aluminium bus bar for phases and neutral complete with suitable digital type meters resin cast CTs, CPRI approved type tested, internal wiring all including the following incoming and outgoing complete all as specified and directed:- Note:- Connection from Main bus bar to Outgoing MCCB should be provided through bus bar of suitable rating instead of copper wires. The pillar box shall be provided with durable and legible Aluminium nameplates for each MCCB containing Qtr Number and FPB No.
Supply, install, testing and commissioning of LT Feeder pillar Box AC 415 V, 50 HZ 3 Phase 4 wire of suitable size to accomodating the following accessories totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, vermin proof indoor type made out of 3.15 mm thick MS sheet protection IP 54, suitable for outdoor use, with bottom cable entry with suitable cable glands structure with angle iron frame work with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter and MCCBs, double hinged doors at front with suitable locking arrangement, Provision of louvers at sides, structure treated under 8 - tank metal treatment process and duly powder coated with 700Amp's electrical grade aluminium bus bar for phases and neutral complete with suitable digital type meters resin cast CTs, CPRI approved type tested, internal wiring all including the following incoming and outgoing complete all as specified and directed:- Note:- Connection from Main bus bar to Outgoing MCCB should be provided through bus bar of suitable rating instead of copper wires. The pillar box shall be provided with durable and legible Aluminium nameplates for each MCCB containing Qtr Number and FPB No.
Supply, install, testing and commissioning of LT Feeder pillar Box AC 415 V, 50 HZ 3 Phase 4 wire of suitable size to accomodating the following accessories totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, vermin proof indoor type made out of 3.15 mm thick MS sheet protection IP 54, suitable for outdoor use, with bottom cable entry with suitable cable glands structure with angle iron frame work with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter and MCCBs, double hinged doors at front with suitable locking arrangement, Provision of louvers at sides, structure treated under 8 - tank metal treatment process and duly powder coated with 700Amp's electrical grade aluminium bus bar for phases and neutral complete with suitable digital type meters resin cast CTs, CPRI approved type tested, internal wiring all including the following incoming and outgoing complete all as specified and directed:- Note:- Connection from Main bus bar to Outgoing MCCB should be provided through bus bar of suitable rating instead of copper wires. The pillar box shall be provided with durable and legible Aluminium nameplates for each MCCB containing Qtr Number and FPB No.
Supply, install, testing and commissioning of LT Feeder pillar Box AC 415 V, 50 HZ 3 Phase 4 wire of suitable size to accomodating the following accessories totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, vermin proof indoor type made out of 3.15 mm thick MS sheet protection IP 54, suitable for outdoor use, with bottom cable entry with suitable cable glands structure with angle iron frame work with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter and MCCBs, double hinged doors at front with suitable locking arrangement, Provision of louvers at sides, structure treated under 8 - tank metal treatment process and duly powder coated with 700Amp's electrical grade aluminium bus bar for phases and neutral complete with suitable digital type meters resin cast CTs, CPRI approved type tested, internal wiring all including the following incoming and outgoing complete all as specified and directed:- Note:- Connection from Main bus bar to Outgoing MCCB should be provided through bus bar of suitable rating instead of copper wires. The pillar box shall be provided with durable and legible Aluminium nameplates for each MCCB containing Qtr Number and FPB No.
Supply, install, testing and commissioning of LT Feeder pillar Box AC 415 V, 50 HZ 3 Phase 4 wire of suitable size to accomodating the following accessories totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, vermin proof indoor type made out of 3.15 mm thick MS sheet protection IP 54, suitable for outdoor use, with bottom cable entry with suitable cable glands structure with angle iron frame work with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars voltmeter, ammeter and MCCBs, double hinged doors at front with suitable locking arrangement, Provision of louvers at sides, structure treated under 8 - tank metal treatment process and duly powder coated with 700Amp's electrical grade aluminium bus bar for phases and neutral complete with suitable digital type meters resin cast CTs, CPRI approved type tested, internal wiring all including the following incoming and outgoing complete all as specified and directed:- Note:- Connection from Main bus bar to Outgoing MCCB should be provided through bus bar of suitable rating instead of copper wires. The pillar box shall be provided with durable and legible Aluminium nameplates for each MCCB containing Qtr Number and FPB No.
M&L for earthing and testing complete with galvanized iron earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 M below normal ground level with top edge of earth plate at a depth not less than 1.5 M below normal ground level connected to and including GI strip 32x6mm as earth lead by means of bolts and nuts, check nuts and washers etc made of GI & connected to equipment and earthing test point , earth dolly all as shown in elect plate No 3 of SSR Pt-I including all necessary earth work, excavation PCC chamber cover with handle (PCC 1:2:4) and 20mm dia GI watering pipe and 40 mm dia light grade GI for protection of earth strip, wire mesh, funnel, charcoal dust & common salt, etc complete all as specified and directed
M&L for LT Cable route indicator with a welded/riveted disc of 4 inch dia and engraved with cable with cable route marker made out of angle iron 40 x 40 x4 mm thick dug in ground with in and incl PCC 1:3:6 type C1 using 20mm graded aggregate at approx distance 100 mtr including necessary earth work complete all as specified and directed
S&F loop in loop out box with transparent lid IP 65 weather proof of suitable size fixed to pole / wall with suitable FI clamp 20mmX3mm nuts, bolts and washers incl provision of 01 No miniature circuit breaker (MCBs) SPN 'C' Series, 240 volts 10 KA 06 Amps and incl suitable for 1 Nos 50/16 sqmm x 3.5/4 core XLPE incoming and 1 Nos 50/16 sqmm x 3.5/4 core XLPE outgoing cable, complete all as specified and as directed
M&L for connecting the Street Light point from loop in loop out box by using a two runs of single core 1.5 Sq.mm. PVC insulated sheathed FR copper conductor cable including PVC conduit/Floxole Pipe of Suitable dia along with one run of 1.5 Sq.mm FR copper cable for earth continuity conductor as earth lead for street light.
Dismantling of ACSR Conductor complete all as directed
Dismantling insulator of any specification complete all as directed
Dismantling iron scrap complete all as directed
Dismantling stay assembly complete all as sdirected
M&L for sub main wiring with 2runs of 4 Sqmm PVC insulated FR Copper conductor cable including PVC conduit/ Casing capping of Suitable dia along with one run of 4 Sq.mm FR copper cable for earth continuity conductor as earth lead for sub main wiring and connecting to common earth dolly complete allas specifiedand directed
M&L for point wiring for the following one light/exhaust fan/fan point controlled by one switch. with two runs of single core 2.5 Sq.mm. (Nominal area) PVC insulated unsheathed multistranded copper conductor cable confirming to IS drawn through and including non metallic PVC conduit concealed/semi concealed including Flush type metal GI boxes for fixing modular type switches, sockets, regulators etc. including provision of multistranded 2.5 Sq.mm. copper conductor as earth wire connected to common earth dolly and earth in distribution board including cutting of stone masonary/ wall complete all as specified and directed
S&F SPN DB 4 Way with 200 amps rated bus bar Double Door complete all as specified and directed
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not le. than 2.25 m deep below normal ground level) with top edge of the plate not le. than 1.5 m below normal ground level connected to GI Earth wire 4 mm dia by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no.5 of .R part I including nece.ary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia light grade for protection of earth electrode 20 mm dia for watering all as specified and directed and tested on completion.
S&F amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) SPN and current carrying capacity 40 Amps in the MCB DB complete with connection testing and commissioning complete all as specified and directed .
S&F 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning complete all as specified and directed .
S&F 16A, 5 in 1 flush type switch socket combinastion with box and fuse & neon indicator complete all as specified and directed
RAJENDRA KRISHNA SARAF (BID ID -3063383)
M/s PRATAP VIJAYSINGHRAO DESAI (BID ID -3071942)
M/s. VIJAY ELECTRICALS (BID ID -3064140)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .