| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.4 LAccepted-AOC FLAT NO 06 BLDG NO B 2 PLEASANT PARK WANWADI PUNE 411040 | PUNE | MAHARASHTRA | 411040 | L1 | Accepted-AOC Bidder quoted L1 rates | |
| 2 | L2₹31.2 L+₹1.7 L (5.86%)Rejected-Finance | L2 | Rejected-Finance Bidder not quoted L1 rates | |
| 3 | L3₹35.0 L+₹5.5 L (18.7%)Rejected-Finance | L3 | Rejected-Finance Bidder not quoted L1 rates | |
| 4 | L4₹1.1 Cr+₹80.6 L (273.0%)Rejected-Finance | L4 | Rejected-Finance Bidder not quoted L1 rates |
Tender Value
₹40.7 L
EMD Value
₹81,500
Closing Date
30 Mar 2024, 6:00 pmClosed
COMMANDER WORKS ENGINEERS PUNE
HEADQUARTERS COMMANDER WORKS ENGINEERS GEN CARIAPPA MARG, PUNE-411 001
85896 REPAIR / REPLACEMENT/MAINT OF PACKAGE SYSTEM / CENTRAL AIR CONDITIONER, COOLING TOWER, COLD STORAGE PLANT AND REPAIRS TO ELECTRIC CONTROL PANELS AT AICTS / MINTSD, CH COMPLEX AND OTHER CONNECTED AREA UNDER AGE EM SOUTH PUNE
2024_MES_644388_1
85896 CWE PUNE
Open Tender
Electrical and Maintenance Works
Item Rate
333 days
GE (SOUTH) PUNE
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE (SOUTH) PUNE
₹81,500
Yes
27 Apr 2024
28 Feb 2024
1 Apr 2024
28 Feb 2024
30 Mar 2024
18 Mar 2024
Amount
M&L for complete cleaning of ducts by using HEPA filtered vaccum unit to create negative pressure in the duct system, by placing the same outside the occupied space by using variety of tools to agitate and loosen the dust, which shall be then drawn into the vaccum unit and contained therein. The cleaning should be done by using robotic tool ,monitored & operated remotely video camera for cleaning the hard to reach areas, which are out of reach for most duct cleaning equipments. Access cutting can be made, if required and shall later be refitted with screw and sealant. All floors and furnishing where the work will be carried on shall be covered and complete care shall be taken to avoid minimum amount of cross- contamination upon completition of work the system shall be sanitized by fogging the ducts to ensure all mold and bacteria spores and foul smell is eradicated the entire process shall be caried out with Air compressor with bib, pneumatic air whips and power jobs, Rotary brush Drum vaccum with pipe. Negative machine HEPA and 10" hose pipe and Robo camera with control unit.
Ser. Item No. 1 Contd..... All cleaning agents/chemicals used shall be inaccordance with the regulation and shall be certified for use in the respective system for OT 1 & 2 plant AICTS (70TR running). During the inspection process collect particulate samples from the duct interior to provide with a complete laboratory analysis of the particulate content to identify hazards such as asbestos. Microbial samples are also taken to evaluate the duct surface for bacteria and mould growth as directed and specified by Engr-in Charge. (Note : PVC sheets wherever reqd for ingress Protection of medical equipments will be arranged by the contractor and its cost is included in unit rate)
All as per Item No.1 here-in-above but for Cardiac ICU plant (34TR running) at AICTS.
All as per Item No.1 here-in-above but for Cardiac OPD AC plant (51TR running) AICTS.
All as per Item No.1 here-in-above but for PICU AC plant (17.5 TR running) AICTS.
All as per Item No.1 here-in-above but for Surgical ICU AC plant (44TR running) AICTS.
All as per Item No.1 here-in-above but for Old CHSC ICU plant (54TR running).
All as per Item No.1 here-in-above but for prepost old CH (SC) AC plant (15 TR running).
All as per Item No.1 here-in-above but for New OT at Old CH (SC) AC plant (15TR running).
All as per Item No.1 here-in-above but for Lower OT AC plant (30 TR running).
All as per Item No.1 here-in-above but for medical storage AC plant upto 5TR (running).
All as per Item No.1 here-in-above but for DIAC AC plant MINTSD (40TR running).
All as per Item No.9 here-in-above but for plant Negative pressure room at AICTS (4TR running).
M&L in replacement for brass ball valve from liquid lie of size 1 -1/8 " from the liquid line in a suitable way including necessery jointing and joining material complete all as specified and directed.
M&L in replacement for brass ball valve from liquid lie of size 7/8" " from the liquid line in a suitable way including necessery jointing and joining material complete all as specified and directed.
Taking out Old Unserviceable compressor oil, supply and charge by topping up compressor oil N-68, Make :- Sheetal / Servo or equivalent
S&F following spare part of Compressor model AC 470, Make: Kirloskar or equivalent
Piston Ring
Strainer suction assembly
Oil Pump Assembly
Oil filter
'O' Ring set
Gasket set
Suction & Discharge valve reeds
Magnetic Strainer
S&F following spare part of Compressor model No. SMC-465 Make :Accel
Piston Ring
Strainer suction assembly
Oil Pump Assembly
Oil filter
'O' Ring set
Gasket set
Suction & Discharge valve reeds
S&F spare part of Compressor model No. FK - 450 & 500 Make : Frizking
Piston Ring
Strainer suction assembly
Oil Pump Assembly
Oil filter
'O' Ring set
Gasket set
Suction & Discharge valve reeds
S&F spare part of Compressor model No. 05040S Make : Voltas
Strainer suction assembly
Oil Pump Assembly
Oil filter
'O' Ring set
Gasket set
Suction & Discharge valve reeds
Cap Control valve without bellow
S&F following spare part of Compressor model SMC - 8- 65, Make: Accel
Piston Ring
Strainer suction assembly
Oil Pump Assembly
Bearing bush
Oil filter
'O' Ring set
Gasket set
Suction & Discharge valve reeds
Gudgen pin
Magnetic Strainer
Supply only Refrigerant gas R-22, Make : Mafron
Supply only Refrigerant gas R-134a, Make : Mafron
Supply only Refrigerant gas R-407a, Make : Mafron
Supply only Refrigerant gas R-404a, Make : Mafron
Taking down carefully defective /unserviceable Shaft seal assembly complete from existing compressor installed at site and supply and fix new shaft seal assembly for Compressor model AC-470, Make : Kirloskar
All as per item No 25 here- in- above but for Compressor model No SMC-4-65, Make: Accel
All as per item No 25 here- in- above but for Compressor model No. FK-450, & 500 Make : Frizking
All as per item No 25 here- in- above but for Compressor model No. 05040S, Make : Voltas
All as per item No 25 here- in- above but for Compressor model No. 865, Make : Accel
Supply and fix in repairs to suction and discharge valve of following models of compressor by means of replacing the teflon washer sheet, suction and discharge valve ring, spring, 'O' Rings, gasket complete and testing for proper holding of Compressor model AC-470, Make :- Kirloskar
All as per item no 30 here- in- above but for Compressor model No SMC-465, Make: Accel
All as per item no 30 here- in- above but for Compressor model FK - 450 & 500 Make:Kirloskar
All as per item no 30 here- in- above but for Compressor model 05040S, Make:Voltas
All as per item no 30 here- in- above but for Compressor model 865, Make : Accel
S&F in replacement of Oil pressure cut Off switch. Make: Indfoss/Danfoss
S & F in replacement of compound gauge for low pressure 32 to 250 Kg/cm2 working on F-12 and F-22 gas Make : FIEBIG
S & F in replacement of HP/LP cut off switch, Make - Indfoss/Danfoss
S&F in replacement pressure gauge suitable for working on F-22 & F-12 gas of ranges 0-300 Kg/Cm2as per site requirement Make : Fibics
S & F in replacement of thermostatic expansion valve of suitable flare size including Brazing, Welding work etc. for the following type/model working on F -12,F-22& 134a gas complete.
Thermostatic expansion valve model HVE-16, CP-100 Make : Sporlon or Equivalent
Thermostatic expansion valve model SVE-8, VCP-100 Make : Sporlon or Equivalent
Supply, Install, test and commissioning compressor of capacity 5 to 12 TR model DPA-1202 Make - BlueStar / Kirloskar copeland or equivalent for Package type AC
S & F in replacement of thermostatic expansion valve of suitable Flaire size including brazing/ welding works etc for Package type AC 5 TR to 12 TR complete all as specified and as directed. (Make : Danfoss or equivalent)
S & F in replacement of Solenoid valve for package AC 5 to 12 TR complete all as specified and as directed.
S & F in replacement of Solenoid coil of suitable size complete all as specified and as directed. (Make :- Sporlon or equivalent )
S & F in replacement of strainer for 5 to 12 TR Package type Acs complete all as specified and as directed.
S & F in replacement of unserviceable/leakage Service Valve suitable for 5 to 12 TR capacity Package AC Plant complete all as specified and as directed.
S&F in repairs to cooling Coil of 75 TR capacity by means of opening the cooling coil, with pressure air and water, charge the Nitrogen gas for pressure leak test complete and repairing the same by means of soldering / brazing, repairs to drain water bottom portion by means of replacement of old rusty GI Sheets with 22 gauge of new GI sheet complete with fabrication work etc of size 2400x1800 MM and making good thermal insulation with glass wool, wire mesh plaster for blower portion complete all as specified and directed.
M&L for repairs to cooling Coil of 50 to 60 TR capacity by means of opening the cooling coil, with pressure air and water, charge the Nitrogen gas for pressure leak test complete and repairing the same by means of soldering / brazing, repairs to drain water bottom portion by means of replacement of old rusty GI Sheets with 22 gauge of new GI sheet complete with fabrication work etc of size 2400x1800 mm and making good thermal insulation with glass wool, wire mesh plaster for blower portion complete all as specified and directed.
M&L for repairs to cooling Coil of 30 to 35 TR capacity by means of opening the cooling coil, with pressure air and water, charge the Nitrogen gas for pressure leak test complete and repairing the same by means of soldering / brazing, repairs to drain water bottom portion by means of replacement of old rusty GI Sheets with 22 gauge of new GI sheet complete with fabrication work etc of size 2400x1800 MM and making good thermal insulation with glass wool, wire mesh plaster for blower portion complete all as specified and directed.
Disconnecting & Dismantling the old Power cables, Circuit wiring and controlling accessories like MCCBs, Contactors , relays and timers from the existing pannel board of 50 to 80 TR capacity AC plant replacing the power cables and circuit wiring with 16 sq mm and 2.5 Sq mm stranded copper cables including repairs/ replacing Contactors, timers and Relays complete all as specified and directed. (Note:- Contactor ML1.5, ML 2, ML 3, Timers and relays will measure and paid separately under respective items of schedule.)
Disconnecting & Dismantling the old Power cables, Circuit wiring and controlling accessories like MCCBs, Contactors , relays and timers from the existing pannel board of 20TR capacity AC plant replacing the power cables and circuit wiring with 10 sqmm and 4 Sqmm stranded copper cables including repairs/ replacing Contactors, timers and Relays complete all as specified and directed. (Note:- Contactor ML1.5, ML 2, ML 3, Timers and relays will measure and paid separately under respective items of schedule.)
Disconnecting & Dismantling the old Power cables, Circuit wiring and controlling accessories like MCCBs, Contactors , relays and timer from the existing pannel board of 30 to 35 TR capacity AC plant, Replacing the new Copper multi strand Power cables 10 Sq mm, Circuit wiring with Copper multi strand Power cables 4 Sq mm including controlling accessories like MCCBs, Contactors , relays and timer etc. complete all as specified and directed. (Note :- Controlling accessories like MCCBs, Contactors , relays and timer will be measure and paid separately under respective items of schedule.)
Disconnecting & Dismantling the old Power cables, Circuit wiring and controlling accessories like MCCBs, Contactors , relays and timer from the existing pannel board of Cold storage AC plant upto 10 TR capacity and replacing the new Copper multi strand Power cables 6 Sq mm, Circuit wiring with Copper multi strand Power cables 2.5 Sq mm including controlling accessories like MCCBs, Contactors , relays and timer etc . complete all as specified and directed. (Note :- Controlling accessories like MCCBs, Contactors , relays and timer will be measure and paid separately under respective items of schedule.)
Supply and fix in replacement Ammeter as per sample of following ratings:-
S&F contactor ML-1.5 with coil voltage 230 volt AC complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F contactor ML-2 with coil voltage 230 volt AC complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F contactor ML-3 with coil voltage 230 volt AC complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&Fcontactor MNX 25 ,3 pole with coil voltage 230 volt AC complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F contactor MNX 32 ,3 pole with coil voltage 230 volt AC complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F ADD ON Block 2NO+2NC for MNX contactor complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
Supply and fix in replacement CT's 100/5,5 VA as per sample
S&F electronic timers, Model GT-200 240 volts AC complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F electronic star delta timers / Timer ET, 240 volts AC complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F bimetal overload relay, direct mounting type suitable for ML series of range 1.5 to 2.5 Amps complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F bimetal overload relay, direct mounting type suitable for ML series of range 2.5 to 4.1 Amps complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F bimetal overload relay, direct mounting type suitable for ML series of range 4 to 6.5 Amps complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F bimetal overload relay, direct mounting type suitable for ML series of range 6 to 10 Amps complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F bimetal overload relay, direct mounting type suitable for ML series of range 9 to 14 Amps complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F bimetal overload relay, direct mounting type suitable for ML series of range 13 to 21 Amps complete all as specified and directed. (Make : L&T or equivalent in BCH /Schneider)
S&F bimetal overload relay, direct mounting type suitable for ML series of range 24 to 32 Amps complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F bimetal overload relay, direct mounting type suitable for ML series of range 28 to 42 Amps complete all as specified and as directed. (Make : L&T or equivalent in BCH /Schneider)
S&F MCCB 200 Amp, 3 pole 25 KA breaking capacity, 440V, AC complete all as specified and as directed.
S&F MCCB 250 Amp, 3 pole 25 KA breaking capacity, 440V, AC complete all as specified and as directed.
S&F MCCB 100/125 Amp, 3 pole 25 KA breaking capacity, 440V, AC complete all as specified and as directed.
S&F MCCB 63 Amp, 3 pole 16 KA breaking capacity, 440V, AC complete all as specified and as directed.
S&F in replacement of MCB TPN 63 Amp, 3 pole 10 KA breaking capacity 440V, AC complete all as specified and as directed.
S&F in replacement of MCB TPN 40 Amp, 3 pole 10 KA breaking capacity 440V, AC complete all as specified and as directed.
S&F in replacement of MCB TPN 32 Amp, 3 pole 10 KA breaking capacity 440V, AC complete all as specified and as directed.
S & F in replacement of unserviceable Solid state indicating lamps 230 Volt AC with RYB and green indication (LED type ) including adopter ring / washer and cable connection complete. Make: Altos
S&F in replacement of digital type temperature indicator including sensor and multicore copper cable ( Length of cable as per requirement )
Taking out burnt/unserviceable fan/blower motor of Package type AC and S&F new fan/blower motor double shaft single/double speed, single phase, 230 VAC complete suitable fixing arrangement for existing phase (as per sample) Suitable for upto 5 to 12 TR capacity Package AC complete all as specified and as directed. (Make : AUE/ Flugmaster/Pophler )
Supplying & laying in replacement insulating mat of size 2000x1000x12mm thick with ISI mark of LT side complete all as specified and as directed.
S&F in replacement of HP/LP cut off switch, MP-15 complete all as specified and as directed (Make : Danfoss/Indofoss)
S&F in replacement single phase preventer of model VSP D-1A/SP-3 complete all as specified and as directed. Make : Minilec
S&F in replacement Contactor 3T II complete all as specified and as directed., Make : Siemens
Repairs to cooling tower by means of replacement of unserviceable filters, cleaning the filters and replacing the Gun metal / Nylon Nozzles etc complete all as specified and as directed. (Note :- Gun metal/Nylon Nozzles shall be measured and paid separately under respective items of sch.)
S&F Nylon Nozzles as per sample complete all as specified and as directed.
Taking down motor 40HP from foundation by disconnecting electrically and mechanically, transporting to workshop for rewinding with ISI marked copper winding wire, ISI marked insulating paper, varnish, replacement of bearings two Nos. of DE and NDE etc transporting back the motor, installing on foundation, aligning the same reconnecting electrically and mechanically and testing on Full load for two hours for satisfactory functioning complete all as specified and as directed.
All as per Item No. 87 here-in-above but for 30HP motor complete all as specified and as directed.
All as per Item No.87 here-in-above but for 25HP motor complete all as specified and as directed.
All as per Item No.87 here-in-above but for 20HP motor complete all as specified and as directed.
All as per Item No.87 here-in-above but for 7.5 HP motor complete all as specified and as directed.
All as per Item No.87 here-in-above but for 5 HP motor complete all as specified and as directed.
All as per Item No.87 here-in-above but for 2 HP motor complete all as specified and as directed.
Dismantling the AHU complete and taking out blower shaft for repairs and transport to workshop for weight balancing ( Dynamic ) and reassembling the complete unit including replacement of old worn out bearings, with housing & sleeves complete for following cap of central AC plant :-
20 TR to 40 TR capacity
45 TR to 95 TR capacity
S & F Condenser unit suitable for Package Acs Suitable for upto 12 TR capacity Package AC complete all as specified and as directed.
Taking down the old filters of any type and size from AHU/duct of Central type AC plant at MH (CTC),CH(SC), ALC and MITS&D by means of unservicing nut bolts, washers etc.including cleaning of AHU/duct as directed by Engineer-in-Charge
S&F filters "HEPA"(Absolute)Model 131-C with fibre glass paper filtering media ,capacity 1000CFM efficiency 99.97% down to particle size of 0.3 microns aluminium frame of nominal size 24"x24"x6" or nearest as directed by Engineer-in-Charge (Make:Kirloskar/Dyna.)
S&F filter"Microvee" non woven fabric filter media efficiency 99.98% down to particle size of 5 microns,MS casing flanged type of nominal 24"x24"x6" or nearest complete all as specified and as directed.(Make:Kirloskar/Dyna )
All as per Item No. 98 above but of size 22.5"x 22.5"x 3" or nearest size
All as per Item No. 98 above but of size 17" x 24" x 2" or nearest size complete all as specified and as directed. (Make : Dyna, Kirloskar)
S&F panel air filters, dry type, washable rated air flow capacity 1600 CFM efficiency 99.9% down to article size 17" x 24" x 2" or nearest size complete all as specified and as directed.. (Make Dyna,Kirloskar)
S&F panel air filters, dry type, washable rated air flow capacity 1600 CFM efficiency 99.9% down to article size 24" x 24" x 1.8" or nearest size complete all as specified and as directed. (Make Dyna,Kirloskar)
S&F panel air filters, dry type, washable rated air flow capacity 1600 CFM efficiency 99.9% down to article size 24" x 20" x 4" or nearest size complete all as specified and as directed.(Make Dyna,Kirloskar)
S&F panel air filters, dry type, washable rated air flow capacity 1600 CFM efficiency 99.9% down to article size 42" x 26" x 2" or nearest size complete all as specified and as directed. (Make Dyna,Kirloskar)
S&F panel air filters, dry type, washable rated air flow capacity 1600 CFM efficiency 99.9% down to article size 32" x 20" x 0.2" or nearest size complete all as specified and as directed. (Make Dyna,Kirloskar)
Supply, Install, testing and commission of Hepa plenum with Hepa Filter (99.97% particulate efficiency) Size : 305mmx610mmx69mm for each bed side ,HEPA shall made up of high quality aluminium diffuser grill to secure the unidirectional air flow according to EN ISO 14644.MOC of Plenum & diffuser grill - SS 304, matt polish, sheet thickness 0.8mm complete all as specified and as directed.
All as item 106 but of size 610mmx1220x75mm complete all as specified and as directed.
All as item 106 but of size 610mmx915 x 75mm complete all as specified and as directed.
S&F in repair V belt A-28, Make : Fenner
S&F in repair V belt A-32, Make : Fenner
S&F in repair V belt B-38, Make : Fenner
S&F in repair V belt B-39, Make : Fenner
S&F in repair V belt A-41, Make : Fenner
S&F in repair V belt B-53, Make : Fenner
S&F in repair V belt B-60, Make : Fenner
S&F in repair V belt B-73, Make : Fenner
S&F in repair V belt B-76, Make : Fenner
S&F in repair V belt B-78, Make : Fenner
S&F in repair V belt B-82, Make : Fenner
S&F in repair V belt C-82, Make : Fenner
S&F in repair V belt B-88, Make : Fenner
S&F in repair V belt B-92, Make : Fenner
S&F in repair V belt B-102, Make : Fenner
S&F in repair V belt B-105, Make : Fenner
S&F in repair V belt B-108, Make : Fenner
S&F in repair V belt B-110, Make : Fenner
S&F in repair V belt C-144, Make : Fenner
S&F framed chicken mesh with 25mmx3mm flat iron frame in corner and center with stiffners of Size with
M&L for dismantling the condenser inlet pipe and outlet pipe for opening both end plates of condenser by loosing nuts bolts. Brushing the copper tubes with the help of nylon brush to remove the scale without damaging the surface and cleaning the tube with descaling regent Dilute HCL or equivalent) for the following model :-
Compressor model AC -470, Make : Kirloskar
Compressor model SMC - 4- 65, Make : Accel
Compressor model FK - 450 & 500 Make : Kirloskar
Compressor model 05040S Make : Voltas
Compressor model DXT type Seal type
Compressor model SMC 8-65, Make : Accel
M&L for cleaning the cooling tower of any type by removing all type of fins and scraping the Fungus of fins and make up tank by applying Dilute HCL solution and drawing out including cleaning and filling with fresh water as directed and specified by Engineer-in-charge
Taking down carefully defective /unserviceable Suction valve assembly complete from existing compressor installed at site and supply and fix new Suction valve assembly for Compressor model AC-470, Make : Kirloskar
Taking down carefully defective /unserviceable Suction valve assembly complete from existing compressor installed at site and supply and fix new Suction valve assembly for Compressor model SMC 4-65, Make : Kirloskar
Taking down carefully defective /unserviceable Suction valve assembly complete from existing compressor installed at site and supply and fix new Suction valve assembly for Compressor model SMC 8-65, Make : Accel / Saebro
Taking down carefully defective /unserviceable delivery valve assembly complete from existing compressor installed at site and supply and fix new delivery valve assembly for Compressor model AC-470, Make : Kirloskar
Taking down carefully defective /unserviceable delivery valve assembly complete from existing compressor installed at site and supply and fix new delivery valve assembly for Compressor model SMC 4-65, Make : Kirloskar
Taking down carefully defective /unserviceable delivery valve assembly complete from existing compressor installed at site and supply and fix new delivery valve assembly for Compressor model SMC 8-65, Make : Accel / Saebro
Taking down carefully defective /unserviceable Liquid line valve assembly complete from existing installed at site by cutting the line and supply and fix new Liquid line valve assembly by doing brazing/welding as directed and specified by Engineer- in- charge.
M & L for preparing existing surfaces of steel exc 10cm width or girth by scrapping rusted part and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed
M & L for replacement of FRP louvers of size 1220 * 330 * 3mm thick complete all as specified and directed
S&F contactor MNX 70 ,3 pole with coil voltage 230 volt AC Make L&T
M&L for surface excavation n.exc(not exceeding) 30 cm deep and averaging 15cm deep and getting out and getting out soft/loose soil.
M&L in replacement of Mild steel chequered plate 10mm thick for ducting edges beaded if directed,holes punched included round headed screws complete all as specified and directed by Engn-In-Charge.
Suplly and fixing in replacement of Cast Iron butterfly valve of 100mm dia as per IS: 13095, having epoxy coated disc, carbon steel shaft, EPDM/nitrile rubber field replacible body lining and of approved make. including a set of MS flanges, required nos of nut & bolts all complete.
Supply & fixing in replacement of 100 mm dia pot type strainers with copper cage and flange type complete all as per direction of Engr- in -charge.
Supply and lay in trenches/on ground, jointing, testing and commissioning in replacement of MS pipe heavy grade including all necessary pipe fittings/accessories like socket, unions, tees elbows etc of the following sizes :-
150 mm bore
100 mm bore
Maintenance and Serviceing including attending faults on day to day basis of AC plant of 54 TR including taking down unserviceable parts, refixing new parts wherever necessary complete including leak testing with nitrogen gas complete,cleaning all type of filters including all accessories and cleaning and maintaining equipment and plant room as specified and directed by Engineer in charge and testing the plant for satisfactory. Make : Kirloskar Location - CH (SC) ICU
Supply and replace in a suitable 20 way copper distributer for cooling coil of AHU for 50 TR AC plant
Caliberation micro processor system of Voltas compressor or and seting the same to for smooth function of compressor and acplant from autherised agency Location - MH (CTC) / MITS & D
All as per item No 148 here- in- above but for AC plant Cap 35 TR Make : Accel, Location : CH(SC) OT Prepost
All as per item No 148 here- in- above but for AC plant Cap 17.5 TR Make : Accel, Location : CH(SC) New OT
All as per item No 148 here- in- above but for AC plant Cap 40TR Make : Accel, Location : MITS&D DIAC Bldg
All as per item No 148 here- in- above but for AC plant Cap 34TR Make : Accel, Location : CH(SC) lower OT
All as per item No 148 here- in- above but for AC plant Cap 3TR Make : Frizking, Location : CH(SC) Medical store& AICTS med store
All as per item No 148 here- in- above but for AC plant Cap 80TR Make : Voltas, Location : CTC OT 1& 2
All as per item No 148 here- in- above but for AC plant Cap 50TR Make : Accel, Location : ALC OT
All as per item No 148 here- in- above but for AC plant Package type ,Cap 66TR Location : CTC ICU/ NICU
All as per item No 148 here- in- above but for Negative pressureAC plant Package type ,Cap 4TR Location : AICTS
All as per item No 148 here- in- above but for Cardiac ICU AC plant ,Cap 34TR Location : AICTS
All as per item No 148 here- in- above but for Cardiac OPD AC plant ,Cap 51 TR Location : AICTS
NOTE :- (a) Spares required for the above maintenance shall be measured & paid as Supply only under appropriate items of Schedule 'A'. (b) Every day checklist as approved by Engr-in-charge has to be produced by technician giving the details of the AC plant (c) Routine checking/testing/servicing of the AC plants and Oxygen plants shall be done on weekly basis including greasing and oiling , if not Rs. 3000 will be imposed as penalty for every week & machinery missed and completion of servicing be produced to Engr-In-Charge. (d) Every day one technician has to be deployed for day to day maint and rectification of faults if any and failing which Rs. 800 will be charged as penalty for every day. Technician should report attendance to Engr-in-charge. (e) Providing Gland, oil, gresaing and other neccessary items for better functioning of machinery to be provided by the contractor and cost is included in the per month maintenance of the machinery. (f) THE QUOTED RATES ARE INCLUSIVE COMPLETE TESTING OF MACHINE TO THE ENTIRE SATISFACTION OF ENGR-IN-CHARGE.
S&F in repairs PVC insulated FRLS copper wire 1.5sqmm,1100V grade of colour code red,yellow ,blue,black or green laid down from motor to panel or inside panel all as specified and directed
S&F in repairs PVC insulated FRLS copper wire 2.5sqmm,1100V grade of colour code red,yellow ,blue,black or green all as specified and directed
S&F in repairs PVC insulated FRLS copper wire 4.0sqmm,1100V grade of colour code red, yellow, blue, black or green all as specified and directed
S&F in repairs PVC insulated FRLS copper wire 6.0sqmm,1100V grade of colour code red, yellow, blue, black or green all as specified and directed
S&F in repairs PVC insulated FRLS copper wire 10.0sqmm,1100V grade of colour code red,yellow ,blue,black or green all as specified and directed
M&L for painting of panels,cooling water pipe line,and other connected items ,compressors and motor of central AC plant of capacity upto 50 TR with synthetic enamel paint of approved colour after preparartion of surface all as specified and directed by engineer in charge.
M&L for painting of panels,cooling water pipe line,and other connected items ,compressors and motor of central AC plant of capacity 51 to 90 TR with synthetic enamel paint of approved colour after preparartion of surface all as specified and directed by engineer in charge.
Supply and fix in repairs/replacement of Variable frequency drive (VFD) input power 380-480V, 50/60Hz,51.9A,22 KW,30 HP Model OPTIDRIVE E3 Make : Invertek or equivalent
M/S - SAKET ENTERPRISES
BRILLIANT AIRCONDITIONING AND REFRIGERATION WORKS
SHREE ATHARVARATHI ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .