Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.2 CrAccepted-AOC | ₹2.2 Cr | L1 | Accepted-AOC L1 Firm |
| 2 | L2₹2.2 CrRejected-AOC ADD 5 SARDAR PATEL MARG CIVIL LINES PRAYAGRAJ | PRAYAGRAJ | PRAYAGRAJ | UTTAR PRADESH | ₹2.2 Cr | L2 | Rejected-AOC L2 Firm |
Tender Value
₹2.2 Cr
EMD Value
₹4.5 L
Closing Date
27 Apr 2026, 2:00 pmClosed
General Manager, Zone-7, Lucknow
General Manager, Zone-7, U.P. Projects Corporation Ltd. Lucknow. Gomti Barrage, Left Bank, Gomti Nagar Lucknow.
Fire Fighting and Electrical revering renovation work of 100 bedded District Combined Hospital Affiliated by Autonomous State Medical College Auraiya District-Auraiya (U.P.)
2026_UPPRC_1139369_1
11/UPPCL/GM-7/E-TENDER/2026-27 Dated-10.04.2026
Open Tender
Miscellaneous Works
Percentage
180 days
District-Auraiya (U.P.)
Please refer Tender documents.
2 documents required · 2 mandatory
₹17,700
₹4.5 L
7 Aug 2026
20 Apr 2026
27 Apr 2026
20 Apr 2026
27 Apr 2026
20 Apr 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Fire Fighting and Electrical revering renovation work of 100 bedded District Combined Hospital Affiliated by Autonomous State Medical College Auraiya District-Auraiya (U.P.) | - | - | - | - |
| 2 | Main Fire Pump
(A) Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :
(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.
(C) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.
(D) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
(E) Suitable cement concrete foundation duly plastered with anti vibration pads.1620 Ipm at 70 m Head
1620 Ipm at 70 m Head | - | 1 No | - | - |
| 3 | Diesel Driven Pump
(A) Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required
(B) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.
(C) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.
(D) M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required.
(E) Suitable cement concrete foundation duly plastered and with anti
vibration pads.
1620 lpm at 70 m Head Set | - | 1 No | - | - |
| 4 | Jockey Pump
(A) Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of
following, complete in all respects, as required :
(B) Horizontal type, multistage, centrifugal pump of cast iron body and
bronze impeller with stainless steel shaft, mechanical seal conforming to lS: 1520.
(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325.
(D) M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
(E) Suitable cement concrete foundation duly plastered and with anti
vibration pads.
180 Ipm at 70 m Head | - | 1 No | - | - |
| 5 | Terrace Pump
(A) Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)
(B) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520
(C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325.
(D) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required.
(E) Suitable cement concrete foundation duly plastered and with anti vibration pads.900 lpm at 35 m Head
900 lpm at 35 m Head | - | 1 No | - | - |
| 6 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable
doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal :
wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection classIP 42 as required
INCOMING
"630A, 50kA 4 Pole MCCB, Ics=100% lcu rating Digital Voltmeter 0-500V with selector switch Ammeter (0-630 A) with selector swtich & CTs etc.
LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 800Amps"
OUTGOING
( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps)
MAIN FIRE PUMP
200 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 HP pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.
JOCKEY PUMP
100 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.
DIESEL ENGINE CONTROL
Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0 20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine.
SYSTEM CONTROLLER
Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specifications. | - | 1 set | - | - |
| 7 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
(a) 200 MM (Wall thickness 6.3 mm) | - | Rm. | - | - |
| 8 | (b) 150 MM | - | Rm. | - | - |
| 9 | (c) 100 MM | - | Rm. | - | - |
| 10 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, Gl bolts, nuts, washers etc.as required : (a) 100 MM | - | Set. | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.71 MB
BOQ_2127199.xls
BOQ • 0.58 MB
BIDDOC11.pdf
Tender Documents • 22.72 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].