Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance PLOT NO F28 COMPLETE COOLING SOLUTIONS LLP PHASE 8 INDUSTRIAL AREA SAS NAGAR MOHALI PUNJAB 160055 | S A S NAGAR | PUNJAB | 160055 | Admitted-Finance |
| 2 | Admitted-Finance PLOT NO 729 INDUSTRIAL AREA PHASE 2 | Admitted-Finance |
| 3 | Rejected-Technical 131 SITANATH BOSE LANE BLOCK B GR FLR SALKIA HOWRAH WEST BENGAL 711106 | HOWRAH | HOWRAH | WEST BENGAL | 711106 | Rejected-Technical Not Qualified |
Tender Value
₹1.6 L
EMD Value
₹31,300
Closing Date
15 Aug 2022, 9:00 amClosed
Director
IISER MOHALI
Preparation of labs of Dr Samrat Mukhopadhyay, Dr Vidya Negi and Dr Sadhan C Das, SH HVAC Work
2022_IISRM_705479_1
IISER/EE-EO/EstimateP/22-23/02
Open Tender
Electrical Works
Works
60 days
IISER MOHALI
Please refer Tender documents.
6 documents required · 6 mandatory
₹590
Yes
Registrar IISER Mohali
₹31,300
Yes
20 Aug 2022
6 Aug 2022
16 Aug 2022
6 Aug 2022
15 Aug 2022
6 Aug 2022
Supply Installation,Testing &Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating,having all hermetically sealed in vertertype Scroll Compressor(s) ,minimum two compressors for above14HPmodules, microprocessor based Controller,top discharge type condensing unit(s),with R410A Refrigerant,vibration isolators,with suitable foundation etc.complete as required.The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperaturewithouttripping.Theunitshallbesuitabletoworkon400V+/-10%,3Phase,50HzACpowersupply.Theunit shallbefilledwithfirstchargeoftherefrigerantandreadyforuseasrequired.TheCOPatAHRI conditions shall not be less than 3.1 and IEER not less than 6.5 . of 14HP
Supply of following Double skin Air handling unit with Thermal break, 2 nos DX copper cooling coil (1 working + 1 standby) as per the attached specifications & lifting. Positioning, connecting at all floor.
900 CFM, 1 coiling coil, Backward curved blower, 110 mm-125 mm static pressure having box type pre filters, fine filters and hepa filters with MS stand
Supply, assembly erection, Testing and commissioning of AHU VRV kit of following capacity
(Supply of Y-joints.)
Refrigerant Piping
Supply,Installation,testingandcommissioningincludingvaccumiazationandNitrogentestingoffollowingnominalsizesofsoft/harddrawncopperrefrigerantpipingforVRV/VRFsystem,completewithfittings,withsuitableadjustableringtypehangersupports,jointing/brazingincludingaccessories,insulatedwithXPLEClass-Otubularinsulation/withClass-OclosedcellelastometricnitrilerubbertubularsleevessectionsofspecifiedthicknessasgivenbelowforSuctionandLiquidlines,allaccessoriesasperspecifications etc. as required :
28.58mmdia(OD)(Harddrawn)withtubethickness1.2mmwith19mm thick insulation
22.2mmdia(OD)(Harddrawn)withtubethickness1.2mmwith19mm thick insulation)
15.86mmdia(OD)(Softdrawn)withtubethickness1.2mmwith19mm thick insulation
12.7mmdia(OD)(Softdrawn)withtubethickness1.2mmwith19mm thick insulation
9.5mmdia(OD)(Softdrawn)withtubethickness1.2mmwith19mmthick insulation
Instrumentation cable (copper armoured).
4 x 16 sqmm
4x 4 sqmm
CONTROL & TRANSMISSION WIRING
Supply, Installation, Testing and Commissioning of control cum transmission wiring of copper wire in suitable PVC conduits between indoor & outdoor units to central remote controllers & for connections between indoor unit to remote control
6 sq. mm x 4 Core
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.
speaker cable Two pair, 2-core, 1.5 sqmm
Drain Piping
With Following Rigid PVC Piping complete with fittings, supports as per specifications and duly insulated with 6mm thickness of XLPE closed cell nitrile rubber as per direction of Engineer-in-charge & specifications enclosed as reqd.
32 mm dia
Supply, installation, testing and commissioning of Site fabricated sheet metal ducting complete with supports, dampers etc. as per IS 655 and approved drawing and as per specifications of below gauges:
Thickness 0.63 mm sheet
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.
Inside the building
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications..
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required..
COMPLETE COOLING SOLUTIONS LLP
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .