Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹62,900
Closing Date
4 Sept 2023, 4:00 pmClosed
Executive Engineer Electric Division UdhampurJPDCL
Executive Engineer Electric Division UdhampurJPDCL
(1) Improvement of line for Creation of sub stn. and Creation of 63 KVA Sub Station at village 1. Thanger SC Mohalla Chakhar 2. Garhi Haspari 3. Paddar Pallar Lehnu 4. Baraga Mohalla Mand East 5. Lohar Mohalla Seen Thakran
2023_PDD_224201_1
ED/UDH/51 of 2023-24 dt. 31-07-2023
Open Tender
Electrical Works
Turn-key
120 days
In District Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electric Division UdhampurJPDCL
₹62,900
22 Sept 2023
31 Jul 2023
6 Sept 2023
31 Jul 2023
4 Sept 2023
31 Jul 2023
31 Jul 2023 - 2 Sept 2023
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for improvement of HT/LT line for creation of 63 KVA Sub Station at Thanger SC Mohalla Chakhar (HT Line).
9 mtr. Long PCC Pole (PCC-WL-300 kg)
GI V Cross -arm with top Bracket including clamps
30 mm sq. ACSR Weasel conductor
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanized Nuts and Bolts
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Thanger SC Mohalla Chakhar.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (Transformer to be provided by the department Electric Division JPDCL Udhampur at the Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long PCC Pole (PCC-WL-300 kg)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Danger Plates with clamps
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for improvement of HT/LT line for creation of 63 KVA Sub Station at Thanger SC Mohalla Chakhar (LT Line).
8 mtr. Long PCC Pole (PCC-WL-200 kg)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
16 KN LT Shackle Insulator
Galvanized Nuts and Bolts
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for improvement of HT/LT line for creation of 63 KVA Sub Station at Garhi Haspari (HT Line).
9 mtr. Long PCC Pole (PCC-WL-300 kg)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Garhi Haspari.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (Transformer to be provided by the department Electric Division JPDCL Udhampur at the Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long PCC Pole (PCC-WL-300 kg)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Danger Plates with clamps
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for improvement of HT/LT line for creation of 63 KVA Sub Station at Garhi Haspari (LT Line).
8 mtr. Long PCC Pole (PCC-WL-200 kg)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
16 KN LT Shackle Insulator
Galvanized Nuts and Bolts
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for improvement of HT/LT line for creation of 63 KVA Sub Station at Paddar Pallara Lehnu (HT Line).
9 mtr. Long PCC Pole (PCC-WL-300 kg)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Paddar Pallara Lehnu.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (Transformer to be provided by the department Electric Division JPDCL Udhampur at the Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long PCC Pole (PCC-WL-300 kg)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Danger Plates with clamps
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for improvement of HT/LT line for creation of 63 KVA Sub Station at Paddar Pallara Lehnu (LT Line).
8 mtr. Long PCC Pole (PCC-WL-200 kg)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
16 KN LT Shackle Insulator
Galvanized Nuts and Bolts
Danger Plates with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for improvement of HT/LT line for creation of 63 KVA Sub Station at Baraga Mohalla Mand East (HT Line).
9 mtr. Long ST Pole (ST-410 SP33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Painting on 9 mtr long ST poles with two coat of Aluminium Paint
Cement Bottoming 1:2:4 mix as per REC Standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Baraga Mohalla Mand East.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (Transformer to be provided by the department Electric Division JPDCL Udhampur at the Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-15)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Danger Plates with clamps
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for improvement of HT/LT line for creation of 63 KVA Sub Station at Baraga Mohalla Mand East (LT Line).
8 mtr. Long ST Pole (ST-410 SP15)
GI U clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
16 KN LT Shackle Insulator
Galvanized Nuts and Bolts
Danger Plates with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting on 9 mtr long ST poles with two coat of Aluminium Paint
Cement Bottoming 1:2:4 mix as per REC Standard 0.5 cum per pole
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for improvement of HT/LT line for creation of 63 KVA Sub Station at Lohar Mohalla Seen Thakran (HT Line).
9 mtr. Long ST Pole (ST-410 SP33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Painting on 9 mtr long ST poles with two coat of Aluminium Paint
Cement Bottoming 1:2:4 mix as per REC Standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Lohar Mohalla Seen Thakran.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (Transformer to be provided by the department Electric Division JPDCL Udhampur at the Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long PCC Pole (PCC-WL-300 kg)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Danger Plates with clamps
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for improvement of HT/LT line for creation of 63 KVA Sub Station at Lohar Mohalla Seen Thakran (LT Line).
8 mtr. Long ST Pole (ST-410 SP15)
8 mtr. Long PCC Pole (WL 200kg)
GI M clamps for Shackle Insulator
30 mm sq. ACSR Weasel Conductor
16 KN LT Shackle Insulator
Galvanized Nuts and Bolts
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
G.I U Clamps
Painting on 9 mtr long ST poles with two coat of Aluminium Paint
Cement Bottoming 1:2:4 mix as per REC Standard 0.5 cum per pole
LT line spacers
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
M/S NEW TRIKUTA TECHNOCRATES
Parbat and Sons
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .