| 1.00PLANT ROOM ACOUSTIC INSULATION | ||||
| 1.01Plant Rooms or AHU Rooms wherever called for or as shown in drawings shall be provided with acoustic insulation to reduce noise levels in such rooms. | ||||
| 1.02Acoustic insulation would be with glass wool and finished with powder coated GI perforated sheet. Acoustic panels of size 1.2m x 1.2m would be used for this purpose. 50mm x 25mm aluminium box sections would be used to form a square framework of 1.2m x 1.2m. | ||||
| 1.03Chicken wire mesh 24G x 1/2" mesh size shall be fixed over one side of this framework tightly. 50mm thick glass wool of density 24Kg/cum would be fixed into this grid over the wire mesh. | ||||
| 1.04The insulation shall be finished with RP tissue and 26G powder coated GI sheets with at least 60% perforation. These panels would then be fixed to the wall with suitable brackets such that the chicken wire mesh faces the wall side and the frame is at least 25mm from the wall. The gaps between the panels would be sealed with silicon sealant. | ||||
| 1.05After fixing of all the panels in a particular wall area, the gap in the periphery between the frame and wall shall be closed with 1mm thick powder coated GI sheet which will be screwed to the framework. | ||||
| 1.06 | SITC of acoustic insulation of plantroom by fixing 1.2m x 1.2m acoustic panels in walls/ceiling of Plantroom as per specification.( Rate taken from the approved estimate rate of High side HVAC works vide Estimate No…… | 700 | Sqm | 2,375 ₹16,62,500 Lowest |
Tender Value
₹17.8 L
EMD Value
₹35,520
Closing Date
18 Sept 2025, 3:00 pmClosed
Executive Engineer (Electrical)
Engineering Unit, Admin Block 3rd Floor, IIT Madras CHENNAI-600036
Provision of plant room acoustic Insulation at NAC-II AC plant room in IIT Madras
2025_IITM_247576_1
23/2025-26/ELDB
Open Tender
Electrical Works
Item Rate
60 days
IIT MADRAS CHENNAI
All required documents as specified in the tender
2 documents required · 2 mandatory
₹0
₹35,520
1 Oct 2025
4 Sept 2025
19 Sept 2025
4 Sept 2025
18 Sept 2025
6 Sept 2025
4 Sept 2025 - 6 Sept 2025
Amount
PLANT ROOM ACOUSTIC INSULATION
Plant Rooms or AHU Rooms wherever called for or as shown in drawings shall be provided with acoustic insulation to reduce noise levels in such rooms.
Acoustic insulation would be with glass wool and finished with powder coated GI perforated sheet. Acoustic panels of size 1.2m x 1.2m would be used for this purpose. 50mm x 25mm aluminium box sections would be used to form a square framework of 1.2m x 1.2m.
Chicken wire mesh 24G x 1/2" mesh size shall be fixed over one side of this framework tightly. 50mm thick glass wool of density 24Kg/cum would be fixed into this grid over the wire mesh.
The insulation shall be finished with RP tissue and 26G powder coated GI sheets with at least 60% perforation. These panels would then be fixed to the wall with suitable brackets such that the chicken wire mesh faces the wall side and the frame is at least 25mm from the wall. The gaps between the panels would be sealed with silicon sealant.
After fixing of all the panels in a particular wall area, the gap in the periphery between the frame and wall shall be closed with 1mm thick powder coated GI sheet which will be screwed to the framework.
SITC of acoustic insulation of plantroom by fixing 1.2m x 1.2m acoustic panels in walls/ceiling of Plantroom as per specification.( Rate taken from the approved estimate rate of High side HVAC works vide Estimate No……
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .