Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.3 LAccepted-AOC | L1 | Accepted-AOC Accepted being lowest on 27 Nov 2021 | |
| 2 | L2₹21.9 L+₹62,012 (2.91%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L2 | Rejected-Finance Rejected | |
| 3 | L3₹28.3 L+₹7.0 L (32.7%)Rejected-Finance | L3 | Rejected-Finance Rejected | |
| 4 | L4₹30.2 L+₹8.9 L (41.8%)Rejected-Finance HOUSE NO 40 CHOTTI BARADARI PART I GARHA ROAD NEAR MEDICAL COLLEGE JALANDHAR PB 144022 | JALANDHAR | JALANDHAR | PUNJAB | 144022 | L4 | Rejected-Finance Rejected | |
| 5 | Rejected-Technical | - | Rejected-Technical Rejected |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
2 Oct 2021, 6:00 pmClosed
GE Faridkot
Garrison Engineer, Faridkot-151203 Punjab 01639-264982
Repair and Maint of LT Panels / Feeder Box and its connected items at Faridkot Mil Stn
2021_MES_472616_1
GE FRD-49/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
Faridkot Mil Stn
Class E Category b i
8 documents required · 8 mandatory
₹500
GE Faridkot
₹50,000
Yes
7 Dec 2021
3 Sept 2021
4 Oct 2021
3 Sept 2021
2 Oct 2021
17 Sept 2021
Amount
Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m in depth; or n exc 10 Sqm on plan and n exc 1.5 m in depth for foundations of poles, struts, stays etc. or laying underground cable etc. in soft/loose soil, & getting out including trimming the sides and forming the sides and forming bottom surfaces to required level complete all as specified and directed .
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed
Removal of excavated surplus (soils) to a distance n.exc 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified & directed .
M&L for sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts, complete all as specified and directed. Note : Punned down thickness (overall 18cm), shall be considered for measurement and payment.
M&L for brick protection with old size sub class 'B' bricks, laid flat , length of bricks across the route of underground cable complete all as specified and directed .
All as per Ser item No 05 here-in-before but except bricks
Material & labour, for cutting existing road for taking out/laying of underground cable through GI pipe of dia 40mm to 100mm including necessary earth work and making good to match with the existing surface with PCC 1:2:4 type B-1 (using 20mm graded crushed stone aggregates) complete all as specified and directed
Supply and laying / fixing , GI pipe, light grade, 40mm dia bore for cable protection fixed to pole/wall with MS clamps, nuts, bolts etc or laid under floor/road/pavement, including taking out old unserviceable pipe complete all as specified and directed. Note : (i) Excavation and earth work shall be measured and paid separately.
Supply and laying / fixing , GI pipe, light grade, 80mm dia bore for cable protection fixed to pole/wall with MS clamps, nuts, bolts etc or laid under floor/road/pavement, including taking out old unserviceable pipe complete all as specified and directed. Note : (i) Excavation and earth work shall be measured and paid separately.
Disconnecting & taking out defective under ground cable of any size from trenches, pole, pipe, floor, wall etc and depositing the same in MT yard of AGE E/M complete all as specified and directed.
Supply, laying, jointing, testing and commissioning of Low Tension (LT) XLPE insulated, armoured, heavy duty, electric power cable, cross sectional area 16Sqmm, 4 core, aluminum conductor, 1100 volts grade under ground cable including both side connection with lugs/thimbles of suitable size etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note: (i) Returning filling, earth work, sand cushioning and brick cover for protection of cable shall be measured and paid separately.
All as per Ser item No 11 here-in-before but LT cable of cross sectional area 25 Sqmm, 4 core
All as per Ser item No 11 here-in-before but LT cable of cross sectional area 35 Sqmm, 3.5 core
All as per Ser item No 11 here-in-before but LT cable of cross sectional area 120 Sqmm, 3.5 core
All as per Ser item No 11 here-in-before but LT cable of cross sectional area 240 Sqmm, 3.5 core
S&F twin core 10 sqmm, nominal cross sectional area, 1100 volts grade, heavy duty cable, PVC insulated, multistranded aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed complete all as specified and directed .
Disconnecting, dismantling and taking down carefully ACSR conductor of any size from LT/HT poles complete all as specified and directed
S&F Aluminium conductor steel reinforced (ACSR), stretched on HT/LT poles without any kink and bends of various sizes complete including fixing to insulator with aluminium binding wire and coloured sleeved jumper connection with PG clamps including cutting of tree branches falling on the site of work complete all as specified and directed . Note: The size of conductor shall be as directed by Engr-in- Charge.
Dismantling unserviceable insulators of any type & size from LT poles complete all as specified and directed.
S&F Shackle type insulator, porcelain, vitreous ,white, brown or green insulator including galvanised mild steel straps,washers, insulator bolts,washers and nuts,working pressure 1100 Volts,height 75 mm ,maximum dia 90 mm including 31x3 mm galvanised steel straps and 12 mm dia of bolts complete all as specified and directed.
S&F pin type, porcelain, vitreous, white, brown or green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 100 mm height, 65 mm dia suitable for 1100 volts grade working pressure complete all as specified and directed.
Dismantling unserviceable cross arms of mild steel channel or angle sections etc with fittings complete all as specified and directed. Note : Cost of cutting of bolts (slag bolts) if reqd shall deemed to be included in the unit rate quoted for this item.
M&L for cross arms, bracings, supports, clamps and back plates, fabricated from mild steel rolled section including nuts, bolts, and washers, bending hot or cold, drilled holes for bolt in any shape as indicated and directed inclusive of two coats of aluminium paint over a coat of red oxide primer after preparation of surface all as specified and directed. .
Re- streching, of existing sagged/broken over head ACSR conductor, any size upto 5 conductors in one span of HT/LT over head line to maintain proper sag and binding with the existing insulators with new binding wire complete all as specified and directed. Note : (i) Linear length centre to centre of the pole shall only be measured. (ii) 4/5 Lines of ACSR Conductor shall be considered as one span for measurement .
Cutting/ trimming of tree branches not exc 30cm girth,sapling,shrubs etc touching/approaching the LT/HT overhead lines upto 3 metre width on each side with hacksaw/axe to clear the LT/HT line including disposal of trimmed branches 100 Metre away inside the cantonment area & clearing site complete all as specified and directed
M&L for Earthing complete with galvanized steel earth plate electrode 60cmx60cmx6.00mm thick, buried directly in ground vertically (depth of pit not less than 2.25m below normal ground level), with top edge of the plate not less than 1.5m below normal ground level, earth plate surrounded by 15cm thick and packed alternate layers of charcoal dust and common salt, connected with and including earth lead of GI wire 4mm dia (8SWG) by means of bolts, nuts, check nuts and washers of galvanized iron or thimbles and other end of the earth wire connected to electrical equipment/GOD/LA and protected by galvanized iron pipe light grade 15mm dia bore including watering pipe 20mm dia bore GI medium grade (ISI marked) with funnel and wire mesh, including all necessary excavation and earth work, PCC chamber in plain cement concrete (1:3:6) type C-1 and pit cover of precast RCC with MS frame etc and all as shown in electrical plate No 3 of MES Schedule Part-I (2009), complete all as specified and directed. Note(s):- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with TMT bar 8mm dia both ways @100c/c. (ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit. (iii) Rate shall include earth lead and protection pipe of length 7.5m, excess beyond 7.5m length required at site shall be measured and paid separately. (iv) Earth resistance should be less than 3Ohm. In case the test results are not found below 3Ohm, complete earthing will be redone without any extra cost to Govt. (v) Quoted lump sum / rate shall be inclusive of above all provisions.
M&L for Earthing complete with galvanized steel earth plate electrode 60cmx60cmx6.00mm thick, buried directly in ground vertically (depth of pit not less than 2.25m below normal ground level), with top edge of the plate not less than 1.5m below normal ground level, earth plate surrounded by 15cm thick and packed alternate layers of charcoal dust and common salt, connected with and including GI strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanized iron or thimbles and other end of the earth wire connected to electrical equipment/GOD/LA and protected by galvanized iron pipe light grade 40mm dia bore including watering pipe 20mm dia bore GI medium grade (ISI marked) with funnel and wire mesh, including all necessary excavation and earth work, PCC chamber in plain cement concrete (1:3:6) type C-1 and pit cover of precast RCC with MS frame etc and all as shown in electrical plate No 3 of MES Schedule Part-I (2009), complete all as specified and directed. Note(s):- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with TMT bar 8mm dia both ways @100c/c. (ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit. (iii) Rate shall include earth lead and protection pipe of length 7.5m, excess beyond 7.5m length required at site shall be measured and paid separately. (iv) Earth resistance should be less than 3Ohm. In case the test results are not found below 3Ohm, complete earthing will be redone without any extra cost to Govt. (v) Quoted lump sum / rate shall be inclusive of above all provisions.
Dismantling unserviceable steel poles/PCC poles complete with all accessories complete all as specified and directed.
S&F pre-stressed cement concrete pole, 9 metre long of cross section 102mm x 172mm at top and 102mm x 279mm at bottom, class 10, complying with requirements of IS-1678-1998, errecting truly in vertical position including painting of poles with two coats of synthetic enamel paint over a coat of primer in alternate strip of 30cm each in black and white colour upto 1.5 metre height from top of PCC pedestal/coping of poles and numbering of poles with synthetic enamel paint black in 80mm high letters over 150mm x 230mm yellow base made from synthetic enamel paint complete all as specified and directed
Dismantling unserviceable stay assembly complete with all accessories complete all as specified and directed.
M&L for Stay assembly comprising of 7/8 SWG galvanised stay strand complete with GI stay rod 16mm dia ,mild steel stay plate, stay bow,connecting bracket of suitable mild steel flat , nuts, bolts, washers,loop type insulators etc complete all as specified in electrical plate No I of SSR-2009 (Part- I) complete all as specified and directed.. Note:- Excavation and earth work , PCC shall be measured and paid separately under relevant items of BoQ’.
M&L for PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregates) as in foundation,filling & mass concrete complete all as specified and directed
M&L for PCC 1:2:4 type B-1 (using 20 mm graded crushed stone aggregates) as in coping of poles etc including weathering, slightly rounded or chamfered angle and throating, necessary form work and fair finishing all exposed faces of concrete without using extra cement complete all as specified and directed
S&F in repair MCCB 63 Amps, 4 Pole, 16 KA, 415 volt 50 Hz, with fixed type thermal magnetic release complete all as specified and directed
S&F in repair MCCB 100 Amps, 4 Pole, 16 KA, 415 volt 50 Hz, with fixed type thermal magnetic release complete all as specified and directed
S&F in repair MCCB 125 Amps, 4 Pole, 16 KA, 415 volt 50 Hz, with fixed type thermal magnetic release complete all as specified and directed
S&F in repair MCCB 250 Amps, 4 Pole, 36 KA, 415 volt 50 Hz, with fixed type thermal magnetic release complete all as specified and directed
S&F in repair MCCB 400 Amps, 4 Pole, 36 KA, 415 volt 50 Hz, with fixed type thermal magnetic release complete all as specified and directed
S&F in repair MCCB 630 Amps, 4 Pole, 36 KA, 415 volt 50 Hz, with fixed type thermal magnetic release complete all as specified and directed
Repair of LT panel by welding broken lid including all material required to make LT panel fuctional including providing new hinges & new locking arrangement (front and back side) and fixing through welding complete all as specified and directed
Surface dressing not exc 15cm deep in soft/ loose soil including cleaning of E/M installations premises, uprooting of tiny trees, tree cutting, cleaning, levelling, spreading bushes, beeds, grass, removing poly bags, brick bats, stone pebbles debries, cleaning of sub station bldg, two pole/ four pole structure area, HT line etc and removing to a distance not exc 50 Mtr complete all as specified and directed
M&L for painting on steel tubular poles 9 metre long including attachments (cross arms, clamps GI pipes etc) complete with one coat of aluminium paint after preparation of steel surfaces and black & white strips 30cm each upto 1.5 metre height from top of PCC coping/ foundation block including writing/ numbering of poles with synthetic enamel paint (white) in 80mm high letters over 150mmx230mm yellow base complete all as specified and directed
M&L for cutting LT cable armoured ends, burn out old lugs, any size and specification, preparing ends for connecting cable end aluminium tube terminals / lugs & dressing, crimping of 25 Sqmm to 35 Sqmm with MS nut bolts and washers of suitable size complete all as specified and directed.
All as per Ser item No 43 here-in-before but of Size 50 Sqmm to 70 Sqmm
All as per Ser item No 43 here-in-before but of Size 95 Sqmm to 120 Sqmm
All as per Ser item No 43 here-in-before but of Size 150 Sqmm to 185 Sqmm
All as per Ser item No 43 here-in-before but of Size 240 Sqmm to 300 Sqmm
S&F in replacement ACB of capacity 800 amps,4 pole,415 volts,with thermal magnetic release(manual fixed type) complete all as specified and directed
S&F in replacement surge protection device (SPD) suitable for 45 watt LED street light fitting complete all as specified and directed .
S&F in replacement driver suitable for 45 watt LED street light fitting complete all as specified and directed . Note :- A Sum of Rs. 65425.00 will be deducted on account of credit for dismantling/demolished/taking down material. Please refer detail on srl page No 19 (Schedule of credit) of Tender Documents.
Raman Electric Trading Co
M/S BSS AND SONS
UNITED ENGINEERING CORPORATION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .