Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.6 CrAccepted-AOC AT MALANI COMPLEX 58 KOTECHA NAGAR KALAVAD ROAD RAJKOT 360001 GUJARAT INDIA | RAJKOT | GUJARAT | 360001 | ₹4.6 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹4.7 Cr+₹12.8 L (2.79%)Rejected-AOC DADRA AND NAGAR HAVELI DN | DADRA AND NAGAR HAVELI | THE DADRA AND NAGAR HAVELI AND DAMAN AND DIU | 396193 | ₹4.7 Cr+₹12.8 L (2.79%) | L2 | Rejected-AOC L2 |
Tender Value
₹4.2 Cr
EMD Value
₹8.4 L
Closing Date
1 Aug 2024, 4:00 pmClosed
Executive Engineer,PWD,Project Cell,DNH,Silvassa
PWD Campus Block No.I(Bldg),DNH, Silvassa
Additional Requirements of MEPF and Civil Works for Phase-I of Shri Vinoba Bhave Civil hospital, Silvassa.
2024_UTDNH_7153_1
E-TENDER NOTICE NO. 08 OF 2024-25 (BLDG)
Open Tender
Civil Works
Item Rate
90 days
UT OF DNH
As per NIT refer
3 documents required · 3 mandatory
₹3,000
Executive Engineer,PWD,Project Cell,DNH,Silvassa
₹8.4 L
Executive Engineer,PWD,Project Cell,DNH,Silvassa
3 Aug 2024
24 Jul 2024
2 Aug 2024
24 Jul 2024
1 Aug 2024
24 Jul 2024
27 Jul 2024
Amount
Relocation Shifting leveling at new location of existing LT panel from ground floor to upper basement with removing existing cables & termination, making proper joint as per required and joint new cables to extend the length of cables as per specification and to laid on cable tray aesthetically with require all material except 70sqmm cable & Cable tray. Complete in all respect including all required for the same.
Plywood + laminates Acoustic False ceiling Providing material and labour for fixing 12 mm thick water resistant ply confirming IS 303 BWR of approved make for false ceiling, which includes GI framing like GypSerra of Saint Gobain or equivalent. 1.0mm thick laminates of approved make and shade shall be paste on external side of 12mm thick ply with adhesive of approved make. Exposed edges of ply shall be covered with 12mm thick 1st class teak wood bedding in total depth. Bedding patti shall be finished with Lacquer polish of approved make and shade. Contractor shall cut perforations/ round holes of various sizes in uniform/ rendom pattern on ply and laminates panel as per the drawing and approved by EIC/ Architect. The holes shall be CNC cut in computer. Framing includes Perimeter Channel is fixed along the perimeter of existing wall/partition with the help of screws at 600mm centres. Ceiling Angle is suspended at up to suitable height as per sight conditions by fixing it to the soffit clit with Soffit Cleat and Rawl Plug creating 1220mm x 1220mm grid. Intermediate channel is fixed to the Ceiling Angle with 2 Nos of 4.2x13 metal to metal screw. The Ceiling Section is then fixed to the Intermediate Channel with the help of Connecting Clip and in direction perpendicular to the Intermediate channel at 457mm c/c. Suggested/ Mentioned board/ ply is then screw fixed to ceiling section with 25mm drywall screws at 230mm centres. All members of ceiling system i.e perimeter channel, angle, soffiet cleat, intermediate channel, connecting clip etc is GI (IS513) having YS-300Mpa, Finish-Galvanised 150GSM (IS 277). Knurled steel section has effective thickness of 2T (2 x depth). Only plan area shall be measured and paid without considering any wastage. Rates shall be inclusive of cost of making cut outs/ openings for electrical fixtures, tube lights /air-conditioners, grills, diffusers etc & providing additional sections for strengthening the openings/cut-outs, making grooves between wall & board etc complete for all floor, all level, all height. Area of cut-outs shall not be deducted and no extra payment shall be considered for additional sections provided. Contractor shall prepare shop drawing based on concept drawing and get approved by engineer in charge. Sample of all loose material shall be approved. Contractor shall prepare mock-up (minimum 2.0 Sqm) with complete finish and get approved by engineer in charge. Necessary MS structure for frame and hanging system should be paid in relevant items. Complete in all respect including all required for the same.
Plywood + laminates Acoustic wall panelling with GI framing : Providing material and labour for fixing 1) 12 mm thick water resistant ply confirming IS 303 BWR of approved make for wall panelling, which includes GI framing like GI CLOSED STUD partition of approved make. 2) 1.0mm thick laminates of approved make and shade shall be paste on external side of 12mm thick ply with adhesive of approved make. 3) Exposed edges of ply shall be covered with 12mm thick teak wood bedding with total depth. Bedding patti shall be finished with lacqure polish of approved make and shade. Contractor shall cut perforations/ round holes of various sizes in uniform/ rendom pattern on ply and laminates panel as per the drawing and approved by EIC/ Architect. The holes shall be CNC cut in computer. Framing - 48x0.6mm CLOSED STUD should be placed at 600mm c/c in 50x0.5mm floor channel. Floor channel should be cut & bend and braced with Wall and closed stud at every 900mm c/c vertically. Floor channel is anchored to the floor & True ceiling using Rawl plug of Ø8x45mm (Material-IS 513 CR1 grade, Zinc coating, Pull Out Load-7.5kN for M20 concrete grade) with suitable anchor fasteners at 600mm c/c in centerline manner. GI noggin channel of 48x0.5mm width has to be provided at the horizontal joints of the two boards. End of paneling shall be closed with same thickness of ply. Only elevation area shall be measured and paid without considering any wastage. Rates shall be inclusive of cost of making cut outs/ openings for electrical fixtures, tube lights /air-conditioners, grills, diffusers etc & providing additional sections for strengthening the openings/cut-outs, making grooves between wall & board etc complete for all floor, all level, all height. Area of cut-outs shall not be deducted and no extra payment shall be considered for additional sections provided. Contractor shall prepare shop drawing based on concept drawing and get approved by engineer in charge. Sample of all loose material shall be approved. Contractor shall prepare mock-up (minimum 2.0 Sqm) with complete finish and get approved by engineer in charge. Necessary MS structure for frame and hanging system/ service elements shall be paid in relevant items. Complete in all respect including all required for the same.
Providing and fixing chlorinated polyvinyl chloride (CPVC) Ball valves with CPVC ball valve, having pressure bearing capacity up to 7.0 kg/cm² at 82°C, of the following sizes including cutting the pipes, solvent welding, complete as per the manufacturers standards and the direction of the Engineer-in-charge. Make: Astral / Supreme / Ashirvad. a) 50 mm nominal bore Complete in all respect including all required for the same.
Providing and fixing chlorinated polyvinyl chloride (CPVC) Ball valves with CPVC ball valve, having pressure bearing capacity up to 7.0 kg/cm² at 82°C, of the following sizes including cutting the pipes, solvent welding, complete as per the manufacturers standards and the direction of the Engineer-in-charge. Make: Astral / Supreme / Ashirvad. a) 40 mm nominal bore Complete in all respect including all required for the same.
Providing and fixing chlorinated polyvinyl chloride (CPVC) Ball valves with CPVC ball valve, having pressure bearing capacity up to 7.0 kg/cm² at 82°C, of the following sizes including cutting the pipes, solvent welding, complete as per the manufacturers standards and the direction of the Engineer-in-charge. Make: Astral / Supreme / Ashirvad. a) 15 mm nominal bore Complete in all respect including all required for the same.
Providing and fixing Gun metal gate valve with C.I. wheel of approved quality (screwed end). (a) 15mm dia nominal bore. Complete in all respect including all required for the same.
Providing and fixing Horizontal Brass Non-Return Valve. (a) 15mm dia nominal bore. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 15 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 20 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 25 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 32 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. 40 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. - Exposed on wall 15 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. - Exposed on wall 20 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. - Exposed on wall 25 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. - Exposed on wall 32 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. - Exposed on wall 40 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. - Exposed on wall 50 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. - Exposed on wall 65 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing material, Equipment and labour for fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. - Exposed on wall 80 mm nominal outer dia Pipes. Complete in all respect including all required for the same.
Providing and fixing CPVC tank connector on each tank for inlet and outlet connections, including drilling holes in the tanks at required levels, inserting the coupling in place, sealing the hole with silicon sealant, as directed and approved by the Engineer-in-charge. (A) 80mm diameter Complete in all respect including all required for the same.
Providing and fixing CPVC tank connector on each tank for inlet and outlet connections, including drilling holes in the tanks at required levels, inserting the coupling in place, sealing the hole with silicon sealant, as directed and approved by the Engineer-in-charge. (A) 65mm diameter Complete in all respect including all required for the same.
Providing and fixing CPVC tank connector on each tank for inlet and outlet connections, including drilling holes in the tanks at required levels, inserting the coupling in place, sealing the hole with silicon sealant, as directed and approved by the Engineer-in-charge. (A) 50mm diameter Complete in all respect including all required for the same.
Providing and fixing CPVC tank connector on each tank for inlet and outlet connections, including drilling holes in the tanks at required levels, inserting the coupling in place, sealing the hole with silicon sealant, as directed and approved by the Engineer-in-charge. (A) 40mm diameter Complete in all respect including all required for the same.
Providing and fixing CPVC tank connector on each tank for inlet and outlet connections, including drilling holes in the tanks at required levels, inserting the coupling in place, sealing the hole with silicon sealant, as directed and approved by the Engineer-in-charge. (A) 32mm diameter Complete in all respect including all required for the same.
Providing and fixing CPVC tank connector on each tank for inlet and outlet connections, including drilling holes in the tanks at required levels, inserting the coupling in place, sealing the hole with silicon sealant, as directed and approved by the Engineer-in-charge. (A) 25mm diameter Complete in all respect including all required for the same.
Supply, installation, testing and commissioning of cabinet type Floor Mounted / Loft Mounted Type single skinned Centrifugal Exhuast Air Unit; unit shall have leakproof canvass connection along with damper at suction side & descharge side cowl; ready to start unit hooked upwith 4P TEFC with IP 55 protection motor with pully / belt drive arrangement on adjustable frame; fan motor assembly mounted on corrossion proof-painted MS baseframe; baseframe to rest on vibration isolation pads. The unit shall be supplied with Starter Panel of required motor capacity. 2800 CFM / 40mm Static Pressure For Septic O.T, Septic Labour & Recovery Room at Sixth Floor Complete in all respect including all required for the same.
SITC Air cooled condensing unit for DX cooling coil in OT Area AHU's 4 TR Complete in all respect including all required for the same.
SITC of copper piping for 4 TR condensing unit with copper piping with suction line insulation of 13 mm thikc nitrile rubber, expansion valve and cathc all drier wth ball valves Complete in all respect including all required for the same.
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 150 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of raw plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering up to 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification. In ceiling, drop down patta of any width shall be measured and paid. Rate shall also including the cost of making openings for light fittings, grills, diffusers, cut-outs made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of putty and painting. Contractor shall prepare shop drawing with coordination of all services and opening/ excess. Sample, shop drawing and mock up shall be approved by Engineer in charge. Measurements shall be wall to wall (plan area) and drop down patta without any deductions for lights, diffusers, columns etc. Nothing extra shall be paid for making provisions for providing light, diffusers, AC grill, fire alarm, sprinkler system and other such fittings. 12.5 mm thick Dampline Gypsum Boards (Confirming to EN520) complying to IS: 2095 : 2011 including 2 coats of white cement based putty, 1 coats of water-based alkali resistant primer with having low VOC, scaffolding etc. including all required for the same. Complete in all respect including all required for the same.
Perforated Gypsum having micro perforation Fully Perforated Gypsum Plaster Board of size 1200 x 2400 x 12.5 mm having approx. 15% perforated area with perforation size and pattern as approved by the Engineerin- charge and as per manufacturer's specification, with all 4 side tapered and backed by acoustical tissue with NRC value not less than 0.60 including 2 coats of white cement based putty, 1 coats of water-based alkali resistant primer with having low VOC, scaffolding etc. including all required for the same.
Providing material, Equipment and labour for Old Wall / Ceiling painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour (Two coats) including scraping of old putty wall surface to prepare the surface even and smooth complete & Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound) content : Modified acrylic, water-based alkali resistant primer with having low VOC complete as directed by engineer in charge etc. including all required for the same.
Providing material & labour for Finishing walls with Acrylic Smooth exterior paint with exterior primer for New work (Two coat including priming coat of exterior primer as per manufacturer's specification) of approved make and shade, having VOC (Volatile Organic Compound) content less than 50 grams/ litre of required shade etc. including all required for the same.
Desing Supply installation testing & commissioning & Modification as per SLD of MAIN PANEL ZONE-1 Complete in all respect including all required for the same.
Desing Supply installation testing & commissioning & Modification as per SLD of MAIN PANEL ZONE-2 Complete in all respect including all required for the same.
Desing Supply installation testing & commissioning & Modification as per SLD of MAIN PANEL ZONE-3 Complete in all respect including all required for the same.
Desing Supply installation testing & commissioning as per Single line diagram of Waste Plant Room Main Panel. Complete in all respect including all required for the same.
Desing Supply installation testing & commissioning as per Single line diagram Laundry Plant Room Main Panel. Complete in all respect including all required for the same.
Desing Supply installation testing & commissioning as per Single line diagram Pneumatic Tube System Panel. Complete in all respect including all required for the same.
Supply, Installation & Commissioning of air curtain units at the Main Entrance for opening dimensions 3m w x 2.45m h. - Air curtains to be installed for Dust & Thermal barrier purpose. - 02 nos. of 5 feet units to generate air draft of avg. velocity10-12 m/sec. & combine cfm of 2 units 2360 x 2 = 4720 CFM. - Each unit powered by 0.33HP, 1-phase, 220V, 50Hz motor. - Functioning of the units to be synchronized with the working of automatic main door. - Metal structure mounted installation on glass façade (The Metal structure shall be provided by client.) Complete in all respect including all required for the same.
Providing material and labour for pest control for above false ceiling. The details shall mentioned below, all as per specification and as per directions of Engineer-in-charge. 1) Rat Control Chemical Name: Bromadiolone Chemical Formula: C30H23BrO4 Place baits in areas with signs of rodent activity, such as ducts, along walls, or in dark corners. 2) Other Crawling Insects Chemical Name: Cypermethrin Chemical Formula: C22H19Cl2NO3 Sprays: Use emulsifiable concentrates or wettable powders to prepare sprays.2 ltrs / sqm Complete in all respect including all required for the same.
VALVES WITHOUT INSULATION Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. BUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified. 200 mm dia Complete in all respect including all required for the same.
VALVES WITHOUT INSULATION Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. BUTTERFLY VALVE (MANUAL) with CI body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified. 150 mm dia Complete in all respect including all required for the same.
VALVES WITHOUT INSULATION Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. 350 mm dia Complete in all respect including all required for the same.
Providing and applying required coats (min two coats) of white cement based putty after thoughly brushing the surfaces free from mortar dropping and other foreign matter, of approved brand and manufacturer, over the any surface to prepare the surface even and smooth complete. After application of putty work applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound) content : Modified acrylic, water-based alkali resistant primer with having low VOC Complete in all respect including all required for the same.
Supply, Installation, Testing and Commissioning of Electric driven pressurization pump (Working & Standby) suitable for automatic operation and consisting of following: complete in all respect as required. a) Horizontal Type, single stage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal and flow of 180 lpm at 120 m.head conforming to IS standards. b) Squirrel cage induction motor with suitable HP with synchronous speed 3000 RPM, Suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class-F insulation, Conforming to IS standards. c) Common Base plat for Pump and motor and coupling, coupling guard, vribration pad, cables and other accessories as required for complete installation of pump set. Complete in all respect including all required for the same.
Dis-assemble OT AHU and Relocation Shifting at new location and reassemble at new location and making proper silicone joint as per required with all require material. Complete in all respect including all required for the same.
SHANTI PROCON LLP
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .