Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.6 LAccepted-AOC | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹25.8 L+₹1.6 L (6.49%)Rejected-Finance SHIVAJI NAGAR GALI NO 1 DHANGU ROAD MODEL TOWN PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹32.5 L+₹8.2 L (33.9%)Rejected-Finance | L3 | Rejected-Finance Not Lowest |
Tender Value
Refer Docs
EMD Value
₹77,000
Closing Date
6 Oct 2022, 6:00 pmClosed
GE (SOUTH) PATHANKOT
GE (SOUTH) PATHANKOT
CRTN MAINT TO EM INSTALLATION OF LT FEEDER PLER BOXE LT CABLES MAINT OF DG SET CAPCTOR PANEL AND CONNTD SWTCHGERS ILUMNATON SYSTM INCL LT OH LIN UG CABLE OTM ACCN AT BHADORYA MIRTHAL KANDRORI AND 167 MH DHANGU COMP UNDR GE S PTK
2022_MES_545290_2
GES/PKT/T-33/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (SOUTH) PATHANKOT
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE (SOUTH) PATHANKOT
₹77,000
Yes
21 Feb 2023
14 Sept 2022
8 Oct 2022
14 Sept 2022
6 Oct 2022
22 Sept 2022
Amount
Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth and getting out all as required for laying of cables,Foundation filling of poles or stays.
All as per srl item No. 1 above item but exceeding depth 1.5 mtr and n exceeding 3 mtrs
Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point.
Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm each all as required.
M&L for good quality dry sand cushioning to under ground electric cable on layer of 8 cm thick before laying the cable and second layer of 15 cm thick after laying the cable all as specified in clause 19.75 of MES Schedule part-I (2009) Note :Sand shall be fined sand as specifed and punned thickness shall be measured and paid.
Supply and laying sub class 'B' bricks of old size (230x115x75 mm) or of size locally available, laid along alignment of cable as protection to cable in trenches complete all as specified and directed.
Supply and lay cable XLPE insulated armoured heavy duty electric cable with aluminium counductor, 1100 volts grade of crosssectional area 16 Sq mm 2 core.Note: Earth work (Excavation, Returning & refilling and removal), sand cushining , cable protection cover, GI protection pipe shall be measured and paid for seperately under respective item of Schedule
Same as item No 07 above but of size 16 x 4 core
Same as item No 07 above 25 Sqmm 4 core
Same as item No 07 above 35 Sqmm 3.5 core
Same as item No 07 above 50 Sqmm 3.5 core
Same as item No 07 above 70 Sqmm 3.5 core
Same as item No 07 above 95 Sqmm 3.5 core
Same as item No 07 above 120 Sqmm 3.5 core
Material, labour, testing & commissioning of straight through jointing kit, heat shrinkable type suitable for XLPE/ PVC cables of size 6 to 35 Sqmm 3.5/4 core with working voltage 1100 volts .
M&L for GI pipe light grade 40 mm dia for cable protection on road crossings/ plinth protection with fixed to the pole wall etc. suitable fittings for cable protection.
S&F in replacement of old u/s service cable size 6 sqmm, twin core multistranded 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service with galvanised steel wire,complete all as spd and directed.
All as per Srl item No.17 above item but for service cable of size 10 sqmm,complete all as spd and directed.
Taking down defective street light fitting of any size/ type/ capacity from height of pole/walls/high mast of any location exceeding 7.0 m height for repair work and re-fixing back after repair work including checking, inspecting, testing and commmissioning complete all as directed by Engr-in-Charge. Note:a) The M/L for Items like lamp, electronic drivers, surge protection devices etc shall be measured and paid separately under relevant items here in under this Schedule b) Necessary tools like ladders & other T&P required etc shall be arranged by the Contractor. c) The rate quoted deemed to be inclusive for minor parts nut bolts, circle clips, clamps etc if any required at site.d) The M/L for repairs to LED panel is not included in the scope and shall be measured and paid separately.
S&F in repair Electronic digital Timer (Astronomical) suitable for street light timer DB panels.
Supply only the following spares suitable for LED street/Flood light fittings of
Electronic driver potted type IP-65, suitable for 90 to 120 W LED light fitting
Electronic driver potted type IP-65, suitable for 70 to 80 W LED light fitting
Electronic driver potted type IP-65, suitable for 30 to 60 W LED light fitting
Surge protection device of capacity 10 KV suitable for LED light fitting
Taking down old unserviceable security light fittings roadway lumanarie type from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 10000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 100 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings roadway lumanarie type from any height and S&F LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 6000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 60 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable security light fittings roadway lumanarie type from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 7200 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 100 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items
Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 12000 lumens and suitable wattage for efficiency not less than 100 lumens/ Watt) min wattage 150 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed.
Supply & fix replacement decorative path way light lighting LED decorative post top lantern for 360 degree 40watts 230 volts, 50 HZ, maple shaped in sothing opal/ prismatic finish made up of polycarbonate,including all accessories prewired complete. Note :- (i) Minimum 2 years gaurntee period of LED fittings (ii) Driver shall be IP 66 degree of protection potted seal type. (iii) Power factor more than 0.9
Repairs to High Mast/mid mast pole motor of Capacity 1.0 HP/0.75 KW 415 Volts 50 Hz 3 Phase 930 RPM and necessary rewinding with super enamelled copper wire all as per existing and servicing/greasing of reduction gear box complete all as specified and as directed.
Decarbonising of the control panel of High mast/Mid mast and including sevicing of parts such as contactors/timers including replacement of pitted lugs,thimbles, control wiring etc complete including painting with a coat of synthetic enamel paint
Supply and erect steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-11 (11.0 metres long) all as directed incl dismantling old one. NOTE :- Earth work, Cement concrete in foundation, coping etc will be measured and paid separately under relevant item.
Supply and erect steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.0 metres long) all as directed incl dismantling old one. NOTE :- Earth work, Cement concrete in foundation, coping etc will be measured and paid separately under relevant item.
S&F in repair PVC insulated 3 core 2.5 Sq mm stranded Aluminium conductor cable for connecting OH line/junction box to street light fitting testing and commissioning all as directed.
M&L for PCC 1:4:8 type D2 with 40 mm graded aggregate as in foundation complete.
M&L for PCC 1:3:6 type C1 with 20 mm graded aggregate for coping of poles and stay including form work.
Earthing complete with Galvanised Steel earthplate of size 60x60cmx6.3mm thick electrode and GI wire 8 sqmm dia as earth lead, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below ground level, connected to earth wire 8 sqmm by means of nuts, bolts, check nuts and washers of GI all as shown in electrical plate No.3 of SSR Part-I, including testing on completion (Rates inclusive of neccessary excavation in any type of soil, earth work, PCC pit, CI cover, funnel with watering pipe, suitable size of light grade GI Protection pipe for earth strip in ground etc. all as required at site for complete earthing).
S&F loop-in/ loop-out box of outer size size 250x210x115 mm made out of FRP(Hot moulded type) with weather proof canopy and locking screws along with with 5/6 Amps MCB - 01 No, 50 Amps rated 3 pole connector- 01 Nos, neutral link mounted and Din rail suitable size for mounting MCB/Connector etc complete in the box, duly fixed to to steel tubular/rail/PCC/RCC pole using 25 x 3mm FI clamp, including suitable gland and lugs for connecting cable complete all as directed including dismantling old one.
M&L for Galvanised iron round bracket made out of 40mm dia GI tubing including making provision for fixing of 04/06 no flood light on 11 mtr steel tubular pole ad fixing and connecting up of LED lights (LED lights shall be measured seperately under respective items of sch ) complete all as specified and directed. Note: The inner diameter of ring shall not be less than 1.0 meter
M&L for bracket for street light fitting made out of 40 mm bore pipe light grade GI tube bent to shape required, not less than 1.20 meter long, fixed with and including MS flat iron clamps made out of 40x6 mm FI, bolts, nuts, washers etc complete including dismantling old defective.
M&L for bracket for street light fitting made out of 25 mm bore pipe light grade GI tube bent to shape required,not less than 1.20 meter long, fixed with and including MS flat iron clamps made out of 40x6 mm FI, bolts, nuts, washers etc complete including dismantling old defective.
M&L for disconnecting burnt end or portion of UG Cable, removing the cable from loop including necessary excvation and earth work, relaying and reconnecting the cable by removing burnt portion of cable and preparing fresh terminal for cable of cross sectional area 10 Sqmm 2 core to 95 Sqmm 3.5 core of LT cable to pole, main switch, LT Panel etc complete all as specified and as directed .
Removing existing 1100 volts grade, XLPE/PVC, armoured, electric power cables (heavy duty) with aluminium conductor of sizes 6 Sqmm 4 core to 70 Sqmm 3.5 core from trench/ duct/ pipe carefully for identifying the defects and relaying the same after rectification of defects complete all as directed. Note: Earth work (Excavation, Returning & refilling and removal), sand cushining , cable protection cover, GI protection pipe shall be measured and paid for seperately under respective item of Schedule
M&L for preparation of old painted surfaces of 09/11 m long steel poles incl removing oily/ greasy sports and applying one coat of aluminium paint complete above 1.5 mtr and one coat of synthetic enamel paint of black and yellow in alternate strip of 30 cm witdth upto 1.5 mtr height including applying a coat of white wash on pole cooping and lettering the pole details with white letters/black background etc complete all as directed
S&F in repairs of MCCBs of following current carrying capacity including necessary connecting terminals to bus bar, nut bolts etc complete all as directed .
320-400 Amps, 3P, Adjustable type,415V MCCB, 35KA rating.
200-250 Amps, 3P,Adjustable type, 415 V MCCB, 25KA rating, All MCCB's should have Company Made Spreaders Links.
160-200Amps, 3P,Adjustable type, 415 V MCCB, 25KA rating, All MCCB's should have Company Made Spreaders Links.
125-160Amps, 3P,Adjustable type, 415 V MCCB, 25KA rating, All MCCB's should have Company Made Spreaders Links.
32 to 80 Amps, 3P, 415 V MCCB, 16KA rating, All MCCB's should have Company Made Spreaders Links.
4 Pole MCCB, 415 V, Adjustable type with breaking capacity 35 KA, 320-400 A rated, All MCCB's should have Company Made Spreaders Links.
4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 200-250 A rated, All MCCB's should have Company Made Spreaders Links.
4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 160-200 A rated, All MCCB's should have Company Made Spreaders Links.
4 Pole MCCB, 415 V, Adjustable type with breaking capacity 25 KA, 125A to 160 A rated, All MCCB's should have Company Made Spreaders Links.
M & L for preparation of old painted surfaces of 09/11 m long PCC poles incl removing oily/greasy sports and applying one coat of synthetic enamel paint of black and yellow in alternate strip of 30 cm witdth upto 1.5 mtr height including including applying a coat of white wash on pole cooping and lettering the pole details with white letters/black background etc complete all as directed
S & F in repair 3 pole power contactor with coil voltage 230 volt AC of current carring capacity 32 to 40 Amps complete including control wiring thimbles etc complete all as directed.
Dismentling old feeder pillar & Supply, installing, testing and commissioning of LT feeder pillar box factory made cubicle outdoor type, fabricated out of 3.00 mm thick CRCA sheet floor mounted with angle iron base frame made of 40 x 40 x 6mm , 50 cm height, floor mounted duly bolts and nuts grouted, dust and vermine proof, suitable for voltage 415 V 3 Phase 4 wire ,Square copper bus bar Chamber 320 Amp Capacity weather proof, with IP-54 protection, with separate hinge door for each compartment for incoming and outgoing MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC complete including painting with two coats of epoxy powder paint over a coat of primer complete including supply fixing and making provision of the following :- (a) MCCB 4 pole 415 volts 3 phase 200 Amp 25 KA -01 No (f) LED Indicator RYB -01 Set ( Set of three). Note: The panel shall be as per CPRI certificate. Note : PCC will be measured and paid separately.
S&F in repair Capacitor duty contactor with 1 No Aux contact 230V AC coil voltage suitable for minimum 10 KVAR capacitor.
S&F in repair Double metalised paper and polypropylene technology ( Mixed Dielectric) capacitor cylindrical/box type for power factor correction of 440 V, 50 HZ rated of capacity 3 to 15 KVAR.
S&F in repair Double metalised paper and polypropylene technology ( Mixed Dielectric) capacitor cylindrical/box type for power factor correction of 440 V, 50 HZ rated of capacity 20 to 25 KVAR.
M&L in replacement of existing unserviceable contactor of current carring range 25 A to 40 Amp (AC-3 duty) at different places in APFC panels including required electrical connections with suitable size of single core pvc copper cable & testing all as directed .
M&L in replacement of existing unserviceable contactor current carring range 9 A to 18 Amp (AC-3 duty) at different places in APFC panels including required electrical connections with suitable size of single core pvc copper cable & testing all as directed .
M&L in replacement of existing unserviceable MCB 25-40 Amps TPN 415 volts at different places in LT Panels/APFC panels including required electrical connections & testing all as directed.
M&L in replacement of existing unserviceable MCB 32 - 63 Amps TPN 415 volts at different places in LT Panels/APFC panels including required electrical connections & testing all as directed.
S&F in repair APFC relay with inbuilt PF meter suitable for 5A CTR suitable for 8 Stage.
S&F in repair APFC relay with inbuilt PF meter suitable for 5A CTR suitable for 12 Stage.
Maintenance and servicing of DG set consisting of replacement of fuel filter, air filter and lub oil filter including replacement of eninge oil all as directed and testing on full connected load for the following capacity of DG Sets and any make as per OEM.Note: Engine oil will be measured and paid seperately.
DG Set 7.5 to 50 KVA
DG Set 62 to 110 KVA.
DG Set 320 KVA
M & L for replecement of existing unservicible Fan Belt and testing complete for the following capacity of DG Sets and any make as per OEM.
DG Set 7.5 to 50 KVA
DG Set 62 to110 KVA.
DG Set 320 KVA
M & L for replecement of existing unservicible Hose Pipes with clamps and testing complete for the following capacity of DG Sets and any make:
DG Set 7.5 to 50 KVA
DG Set 62 to110 KVA.
DG Set 320 KVA
Taking out the old unserviceable radiator from the DG set and taking it to work shop for overhauling & cleaning descaling with restore plus solution, removal of leakage, welding brazing & refixing it duly repaired etc complete all as directed for the following capacity of DG Sets and any make as per OEM.
DG Set 7.5 to 50 KVA
DG Set 62 to110 KVA
DG Set 320 KVA
M&L for repair and overhauling of unsv self starter 12 V of any capacity DG set including repair/replacement unsv/ defective spares such as field coil, armature winding, carbon bushes, clutch bushes and pinion assy complete all as specified and directed.
M&L for repair and overhauling of unsv self starter 24 V of any capacity DG set including repair/replacement unsv/defective spares such as field coil, armature winding, carbon bushes, clutch bushes and pinion assy complete all as specified and directed.
M&L for repair and overhauling of unsv dynamo/alternator 12 V of any capacity DG set including repair/replacement unsv/ defective spares such as field coil, armature winding, carbon bushes, clutch bushes and pinion assy complete all as specified and directed.
M&L for repair and overhauling of unsv dynamo/alternator 24 V of any capacity DG set including repair/replacement unsv/defective spares such as field coil, armature winding, carbon bushes, clutch bushes and pinion assy complete all as specified and directed.
S&F in repair AVR with functions to adjust generator output voltage, prevent voltage hunting, set under frequency roll off knee point, set generator droop to 5% at full load, match AVR input to accessory output, set the over excitation cut off level, set intial frequency related voltage dip, over-voltage protection cut off level, maximum short circuit current with sensing input voltage range 170 - 250 V AC max, 50 -60 HZ frequency with output max upto 120 V DC, continuous current 2.7A & transient 6A for 10 sec including necessary control wiring complete from alternator to AVR complete testing & commissioning for DG sets of capacity 160 to 320 KVA.
All as per srl item Srl item No.90 above but for D set capacity 50 to 110 KVA
Taking out the old unserviceable battery from the DG Set and supply and fix new 12 V, 180 AH maintenance free battery including testing and commissioning complete all as specified and directed
Taking out the old unserviceable battery from the DG Set and S&F new 12 V, 100 AH maintenance free battery make Amron/Exide including testing and commissioning complete all as specified and directed
M & L for repair of Water pump of 320 KVA DG set including replacement of defective unsv spare part of any make and model and refix the same after repair complete all as specified and as directed
M & L for repair of Water pump of 50 to 110 KVA DG set including replacement of defective unsv spare part of any make and model and refix the same after repair complete all as specified and as directed
M&L for Calibration of Fuel pump including replacement of unsv/ defective spares of 320 KVA DG Set of any make and model complete all as directed.
M&L for Calibration of Fuel pump including replacement of unsv/ defective spares of 50 to110 KVA DG Set of any make and model complete all as directed.
M&L for overhauling and calliberation of fuel injector assembly including replacement of unsv/defective spares of 320 KVA DG Set of any make and model complete all as directed.
M&L for overhauling and calliberation of fuel injector assembly including replacement of unsv/defective spares of 50 to 110 KVA DG Set of any make and model complete all as directed.
S&F in replacement battery leads set, PVC insulated multisranded, copper conductor of min size 35 sqmm 1 mtr long each duly fixed with brass clamps, copper lugs suitable for DG sets of different capacities.
M&L for replacement of coolant for radiator for DG set at various locations.
M&L for replecement of Lub Oil (Engine Oil) of grade 20W40 for Engine for DG set at various locations.
M&L for replacement of starter ring gear assembly for capacity 320 KVA DG set.
M&L for replacement of starter ring gear assembly for capacity 34 to 50 KVA DG set.
M&L for cleaning the fuel tank both internally and externally by removing all the dust / sediments etc including replacement of PVC pipe fuel level indicator, writing of tank capacity, date of cleaning and next due date for tank to be cleaned for following capacities of DG Set and any make as per OEM.
DG Set 7.5 to 50 KVA
DG Set 62 to110 KVA.
DG Set 320 KVA
Note: In case the tenderer quotes different rates for similar item then lowest rate shall only be applicable for payment and contractor shall not have any claim on this account.
KEWAL SONS
M/s. Aggarwal Engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .