Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.8 LAccepted-AOC KG 115 SABIRA MANZIL HBR 2ND STAGE VENKATESH PURAM BANGALORE 560 045 | BENGALURU URBAN | KARNATAKA | 560045 | L1 | Accepted-AOC Being lowest and reasonable | |
| 2 | L2₹19.9 L+₹1.3 L (7.18%)Rejected-Finance | L2 | Rejected-Finance Not being lowest | |
| 3 | L3₹20.1 L+₹1.6 L (8.49%)Rejected-Finance | L3 | Rejected-Finance Not being lowest | |
| 4 | L4₹20.5 L+₹1.9 L (10.3%)Rejected-Finance | L4 | Rejected-Finance Not being lowest | |
| 5 | L5₹21.3 L+₹2.8 L (14.9%)Rejected-Finance NO 7 3RD MAIN ROAD MUNI REDDY LAYOUT HORAMAVU MAIN ROAD BANASAWADI BANGALORE 560043 | BENGALURU URBAN | KARNATAKA | 560043 | L5 | Rejected-Finance Not being lowest |
Tender Value
₹23 L
EMD Value
₹46,000
Closing Date
24 Jul 2023, 6:00 pmClosed
GARRISON ENGINEER I R nd D WEST BANGALORE
GARRISON ENGINEER I R nd D WEST BANGALORE, DRDO COMPLEX, CV RAMAN NAGAR
REPAIR AND REPLACEMENT OF LT PANELS AND CAPACITOR PANELS MCCBs DBs AND ALLIED WORKS AT CAIR DCA DAD QTRS AND SERVICE CENTRE NO 3 AREA UNDER GE I R an D WEST BENGALURU
2023_MES_599184_1
GE(I)/R ND D/BAN/TOKEN/25 OF 2023-24 8179/E8
Open Tender
Civil Works
Item Rate
180 days
GARRISON ENGINEER I R nd D WEST BANGALORE
Class and category as per NIT
9 documents required · 9 mandatory
₹500
GARRISON ENGINEER I R nd D WEST BANGALORE
₹46,000
20 Nov 2023
12 Jun 2023
31 Jul 2023
13 Jun 2023
24 Jul 2023
10 Jul 2023
13 Jun 2023 - 27 Jun 2023
Amount
Excavation in trenches in hard / dense soil not exceeding 1.5 metres wide not exceeding 1.5 metres in depth; for laying of cables, not exceeding 10 Sqm on plan and getting out , trimming sides, forming bottom surface to required level complete all as specified and as directed .
Returning and filling in, soils, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick all as directed.
Removing excavated surplus soil to a distance not exceeding 50 metres and depositing where directed at a level not exceeding 1.5 metres above the starting point all as directed.
Material and labour for Unreinforced precast concrete cable covers, class LV, type 1, flat size 300mm x 180mm x 40mm complete all as specified and as directed.
Taking down existing 11 KV grade cable upto 35 sqmm size and Supply and laying New XLPE insulated, screened, bedded galvanized steel strip / wire armoured heavy duty with aluminum conductor, of cross sectional area 10 sq mm 4 core with cable protection works (as applicable) laid in trenches/ ducts/ fixed on pole/ wall/ laid under road/ path/ culvert/ drains/ encased in pipe, jointing and testing complete all as specified and as directed.
Taking down existing 11 KV grade cable 50 to 95 sqmm size and Supply and laying New XLPE insulated, screened, bedded galvanized steel strip / wire armoured heavy duty with aluminum conductor, of cross sectional area 70 sq mm 3.5 core with cable protection works (as applicable) laid in trenches/ ducts/ fixed on pole/ wall/ laid under road/ path/ culvert/ drains/ encased in pipe, jointing and testing complete all as specified and as directed.
Screening excavated earth (passing through 12 mm square mesh), laying riddled earth in trenches for cable protection, under and above Cable all as specified in SSR Part - I (Clause No 19.75) and as directed by Engineer-in-Charge. Note : Punned thickness of riddled earth of 18 cm will be measured and paid.
Material and labour for plain cement concrete 1:3:6, type C2 (using 40 mm graded stone aggregate as in mass concrete foundations of poles, stays etc., including necessary formwork, complete all as specified and as directed.
Supply and fix in replacement of light grade Galvanised mild steel pipe 32mm bore complete with all fittings, laid under roads, drain, paths, fixed to poles/ walls with suitable mild steel clamps , bolts , nuts and washers complete all as specified and directed as for cable proction . (Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule)
Supply and fix in replacement of light grade Galvanised mild steel pipe 40mm bore complete with all fittings, laid under roads, drain, paths, fixed to poles/ walls with suitable mild steel clamps , bolts , nuts and washers complete all as specified and directed as for cable proction . (Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule )
M & L for taking down and providing earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level, connected to galvanized iron strip 32 x 6 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, all as shown in Electrical Plate No 3 of SSR Part - I, including necessary excavation and earth work, P.C.C (1:3:6) type C-I with 50 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8 mm dia deformed bar @ 15 cm C/C both ways and suitable handle of 10 mm dia round bar), including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel and 20 mm bore galvanized iron watering pipe (light grade), wire mesh, aluminium lugs, complete in all respect, GI earth strip protected by 40 mm bore (medium grade) galvanized iron pipe and other end connected with main switch board or Earthing test point as directed, including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessary testing on completion complete all as specified and as directed by the Engineer-in-Charge. (Note : 1. If the desired earth resistance is not found earthing shall be re-done by the Contractor at no extra cost paid by Dept.)
Taking out old existing coarse aggregate of any size , levelling and making good the surface and Supply and spread graded coarse aggreagate 40mm graded loose staking inside the chain fencing area of transformer or any area all as directed at site .
Disconnecting Incoming cable and all out going cables of any sizes from the Indoor/ outdoor panel, taking out all cables carefully as per site conditions and kept aside for reuse and reconnections in the new panel and taking out the panel from the site carefully complete all as directed by Engineer-in-charge.
Supply, installation , Commissiong and Testing of LT Panel OUT DOOR, CPRI type tested, LT 440 Volts, 50 Hz , 3 Phase 4 wire supply , floor mounted factory fabricated weather and vermin proof protection class IP 54 made out of 3 mm thick MS Sheet CRCA Sheet on angle iron 50X50X6mm frame of size suitable to incorporate following accessories with front and rear opening double doors each side including separate compartment of door for each MCCB, handle type locking arrangement including suitable size SS Exterior type Aldrop, powder coated internally and externally shall have channel base of appropriate size and mounted on PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 , using 40 mm graded crushed stone aggregate as recommended by manufacturer or directed by the Engr -in - charge including earth work complete comprising of following :
Incoming (a) Bus bar chamber comprising 4 Nos 400Amps Aluminium bus bars with heat shrinkable colour code sleeves, PVC insulated made of copper wire for internal connections. (b) MCCB 350A, 415V, 4 Pole, 36 kA, Ics=100%Icu, Adjustable Overload 80-100%, Adjustable Short Circuit 5-10 In, AC 415 Volts with thermal release complete with spreader links. Make C&S Cat Part No Cat. No. CSE3N400ATM4P or Equivalent or of make Legrand /L&T /ABB/Siemens- 01 No Outgoing : (a) MCCB 100A, 415V, 4 Pole, rapturing capacity 18 kA, Ics=100%Icu, Adjustable Overload 80-100%, Fixed Short Ciruit 10 In with thermal release complete with spreader links. Make C&S No CSESL125FMU4P4P or Equivalent or equivalent of make Legrand /C&S/ABB/Siemens- 07 Nos (b) (b) Digital Panel Meter, 3 Phase Current Measurement, Accuracy Class 1, True RMS Measurement, Smart Keys for Easy access of Parameters, Conforming to IEC62053-21. Make – C&S, Cat. No. CSM-A-I3-S1 or equivalent or equivalent of make Schneider or AE:-01 Nos
Outgoing Contd.. (c) Digital Panel Meter, 3 Phase Voltage Measurement, Accuracy Class 1, True RMS Measurement, Smart Keys for Easy access of Parameters, Conforming to IEC62053-21. Make – C&S, Cat. No. CSM-A-V3-S1 or equivalent of make Schneider or AE:-01 Nos (d) All accessories pre-wired with suitable size PVC insulated copper conductor cables for control wiring and PVC insulated copper strips of appropriate size for power circuits, (e) Red Yellow Blue Integral LED pilot Lamp suitable for operating at Operating voltage 240 V AC. Make – C&S, Cat. RCB7-IVL74 or Equivalent as per standard engineering practice and required at site and suitable foundation for panel as per manufacturer recommendation.
Supply, installation , Commissiong and Testing of feeder pillar box / LT Panel OUT DOOR, CPRI type tested, LT 440 Volts, 50 Hz , 3 Phase 4 wire supply , floor mounted factory fabricated weather and vermin proof protection class IP 54 made out of 3 mm thick MS Sheet CRCA Sheet on angle iron 50X50X6mm frame of size suitable to incorporate following accessories with front and rear opening double doors each side including separate compartment of door for each MCCB, handle type locking arrangement including suitable size SS Exterior type Aldrop, powder coated internally and externally shall have channel base of appropriate size and mounted on PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 , using 40 mm graded crushed stone aggregate as recommended by manufacturer or directed by the Engr -in - charge including earth work complete comprising of following :
Incoming (a) Bus bar chamber comprising 4 Nos 500Amps Aluminium bus bars with heat shrinkable colour code sleeves, PVC insulated made of copper wire for internal connections. (b) MCCB 400A, 415V, 4 Pole, 36 kA, Ics=100%Icu, Adjustable Overload 80-100%, Adjustable Short Circuit 5-10 In, AC 415 Volts with thermal release complete with spreader links. Make C&S Cat Part No Cat. No. CSE3N400ATM4P or Equivalent or of make Legrand /L&T /ABB/Siemens- 01 No Outgoing : (a) MCCB 100A, 415V, 4 Pole, rapturing capacity 18 kA, Ics=100%Icu, Adjustable Overload 80-100%, Fixed Short Ciruit 10 In with thermal release complete with spreader links. Make C&S No CSESL125FMU4P or Equivalent or equivalent of make Legrand /C&S/ABB/Siemens- 08 Nos (b) Digital Panel Meter, 3 Phase Current Measurement, Accuracy Class 1, True RMS Measurement, Smart Keys for Easy access of Parameters, Conforming to IEC62053-21. Make – C&S, Cat. No. CSM-A-I3-S1 or equivalent or equivalent of make Schneider or AE:-01 Nos
Outgoing Contd..: (c) Digital Panel Meter, 3 Phase Voltage Measurement, Accuracy Class 1, True RMS Measurement, Smart Keys for Easy access of Parameters, Conforming to IEC62053-21. Make – C&S, Cat. No. CSM-A-V3-S1 or equivalent of make Schneider or AE:-01 Nos (d) All accessories pre-wired with suitable size PVC insulated copper conductor cables for control wiring and PVC insulated copper strips of appropriate size for power circuits, (e) Red Yellow Blue Integral LED pilot Lamp suitable for operating at Operating voltage 240 V AC. Make – C&S, Cat. RCB7-IVL74 or Equivalent as per standard engineering practice and required at site and suitable foundation for panel as per manufacturer recommendation.
Supply and fix, Aluminium lugs suitable for cable of size upto 95 Sq mm complete all as specified and as directed.
Pacific Enterprises
Sahara Engineers
M/s Prem Associates
ARUNOTHAYA TRADERS
RASI AND COMPANY
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .