Executive Engineer
Electricity Construction and Works Division, P.V.V.N.L., Victoria Park, Meerut
Construction of Double ckt. Line From 132 KV Vedvyaspuri to 33 KV SS Khadauli for feeding of 33 KV SS Lakhvaya, Distt. Meerut
2024_PVVNL_933861_1
02/ECWD/MRT/2024-25
Open Tender
Electrical Works
Lump-sum
90 days
Meerut
please refer tender notice and documents
3 documents required · 3 mandatory
₹3,540
Payable to E.E.E.C.W.D., Meerut
₹26,000
31 Jul 2024
29 Jun 2024
26 Jul 2024
29 Jun 2024
26 Jul 2024
29 Jun 2024
Safe carriage of Poles from any store Centre (Under Jurisdiction fo PVVNL) to Site Store with loading & unloading at both ends respectively 13 M Long STP, SP-72 Round Pole
33 KV 3x300mmsq XLPE cable
33 KV 3x300 Jointing kit O/D/ S.T. T.H.
Loading, Safe carriage & unloading of heavy stock material, conductor (other than pole) from any store center under jurisdiction of PVVNL to site store with proper stacking of material.
Conversion of single ckt line into Double ckt line including dismantling of V type cross arm (01 No.) from single poles, channel (02 No) from double poles, removing of F bracket, removing of pin insulators, removing of disc insulators, opening of jumpers, removing of ACSR Dog conductor from single ckt line, fitting of V type cross arm (03 No) on single poles, fitting of channel (04 No) on double poles, fitting of pin insulator (06 No) on V type cross arm of single pole, fitting of disc insulator (12 No) on DP/TP/Four pole structure and laying, spreading, lifting and final sagging of 3 phases of ACSR Dog conductor for making double ckt. line, jumpering and providing &fixing of P.G. Clamp and other associated work as per site requirement.
Details of work required for conversion from single ckt. to double ckt. of 33 KV line. Excavation of foundation pit in mix soil/normal soil/soft & hard rock and its back filling and leveling etc. The size of the pit will be (450x450)mm and having depth of 1/6th of the full length of the support & Erection of support. The work includes carriage and handling of supports from site store to pit site. 13 M Long STP, SP-72 Round Pole
Fixing of all clamps, Cross Bracing Sets 3.5 Mtr. from M.S. Angle 65×65×6mm/50×50×6mm & other accessories on the supports as per drawing. Work includes cutting of holes and providing M.S. Bolts of 16×40mm size in the middle of cross bracing with 1 no. spring washer. The work also includes carriage & handling of accessories from sectional store to pit site as well as any fabrication work if required. Single Pole (Double Ckt.) 11/13 M Long STP, Round Pole
13 M Long STP, SP-72 Round Pole (Double ckt.)
(ii) Double Pole Structures (b) 11/13 M Long STP, Round Pole
(iii) Cable Riser/End Riser (a) 11/13 M Long STP Round Pole
(iv) Four Pole/Tri pole Structures (a) 11/13 M Long STP, Round Pole
Grouting of supports in CC 1:4:8 (Cement, sand & 40 mm brick ballast) Grouting will be done in the block of size (450×450)mm ×1/6th of full length of the support, up to ground level, 300 mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grit) with muffing as per drawing, work includes back filling and proper ramming. 13 M Long STP, SP-72 Round Pole
Earthing of supports with MS earth Rod of (20×2500)mm long including excavation of pit and driving M.S. Rod 3.0 M apart from support and 0.5m below the ground level and connecting below the earth electrodes with the help of G.I. wire no. 8 SWG and earthing lugs.
Providing & fixing of danger board at each location as per specification of the drawing with clamps etc.
Chopping of branches of trees of eucalyptus, Neem, Keekar and other kind of trees along the route of the line and disposal of the same at suitable place.
Painting of following supports/structures with 2 coats of synthetic enamel paint after one coat of ready mix primer including cost of all material, as well as rubbing/cleaning of surface as required for proper completion of work. Painting will be done by post office red paint from top to cross arm and remaining by Aluminum paint. 13 Mtr, SP-72 Poles including all channels/X-Arms/Clamps etc. (Double Ckt.) Single supports
Making H.T. Connections of the proposed line, on to the existing 33 KV bay/line from where line is emanating and another at the end of line to the terminal gantry at proposed 33 KV Sub-station. The work consists of fixing of tension fitting, insulators, jumpering, clamping and binding etc. at the end as per site conditions.
Wrapping of barbed wire on 33 KV PCC Poles/SP-55/SP-72 ST Poles as anti-climbing device for a length of 0.9 Mtr., wire pitch/gap 13mm and fixing upper and lower end keeping lower end at a height of 2.75 Mtr. from the ground complete with supply and fixing of lower end & upper end clamps made of M.S. Flat 40×5mm complete with nuts & bolts & all other required material.
Numbering of each supports by preparing background with dark yellow paint in the size of 150mm dia and writing support number 100mm high with black paint.
Digging of Trench of 1050x750mm size by excavation of earth for laying 33KV underground line
Safely laying of 33KV, 3x300Sq.mm. XLPE Cable in Cable Trench with Providing & Laying of Ist Class Bricks, along the length on both side of 33KV XLPE Cable in Cable Trench (minimum 18No. Bricks/Mtr per Cable) and Stone Slab (Smooth surface both side) of size 400x600x40mm on top of the Cable, Providing 150mm thickness River sand for cushion beneath and 150mm above the cable as per specification.
Back filling of excavated earth in the cable trench upto the ground level and ramming properly.
Providing & Fixing 150mm dia 2mm thick 3M long G.I.Pipe over 33KV, 3x300Sq.mm XLPE Cable before mounting the 2No. Cable on double pole / Cable support structure. The work includes fixing of Clamp, sealing of top and bottom end of the G.I.Pipe. One end of G.I.Pipe is to be buried under earth about 500mm.
Laying of 33KV, 3x300Sq.mm XLPE Cable in the air on cable Riser Double Pole, existing cable trench, Pucca trench, nala x-ing & G.I.Pipe and making connection with 33KV over head line at both ends.
Making of 33KV Outdoor type cable end termination by heat shrinkable XLPE Cable Jointing Kits/ ST. T.H and crimping with proper size aluminium lugs. Work includes providing Aluminum lugs, insulating tapes etc as per specifications.
Road restoration charges for 1Mtr wide Kachcha Road (Inter locking Tiles, Bricks Road & Developed green belt only) or Deposite charges to take the permission/approval/NOC from any Development Authority/Govt. Body/Forest Deptt./and other concerned Deptt. for restoration of damaged property like Kuccha road, Inter locking Tiles and other utilities.
Road restoration charges for 1Mtr wide Pakka Road (Cemented, Concrete & Black road only) or Deposite charges to take the permission/approval/NOC from any Development Authority/Govt. Body/Forest Deptt./and other concerned Deptt. for restoration of damaged property like Pucca road, Inter locking Tiles and other utilities.
Recived Back Material site to store. MS Scrap of Round Poles.
SHASHI ENTERPRISES
Raj Engineers
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .