Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.5 LAccepted-AOC 704 SILVER DEAL DAFFODIL WING 1 B T KAWADE ROAD PUNE 411 001 | PUNE | PUNE | MAHARASHTRA | 411001 | L1 | Accepted-AOC Being lowest and reasonable | |
| 2 | L2₹18.7 L+₹5.2 L (38.5%)Rejected-Finance FLAT NO S 4 DOOR NO 10 4 107 17 SRINIVASA TOWERS SRI RAMNAGAR GAJUWAKA VISAKHAPATNAM 530 026 | VISAKHAPATANAM | ANDHRA PRADESH | 530026 | L2 | Rejected-Finance Not being lowest |
Tender Value
Refer Docs
EMD Value
₹28,000
Closing Date
14 Nov 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE WELLINGTON
Headquarters, Commander Works Engineers, Wellington, Barracks-Post, The Nilgiris, PIN 643231
PROVN OF HT 11 KV VACUUM CIRCUIT BREAKERS INCL CONNECTED WORKS AT SS NO-02 UNDER GE DSSC WELLINGTON
2020_MES_386470_1
84697/E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
Wellington
CLASS E
CATERGORY b(ii)
6 documents required · 6 mandatory
₹500
GE DSSC WELLINGTON
₹28,000
Yes
1 Dec 2020
14 Oct 2020
16 Nov 2020
14 Oct 2020
14 Nov 2020
30 Oct 2020
60 days
Amount
Supply, install, commissioning & testing of indoor type HT Vacuum Circuit Breaker ICOG Switchgear Panel comprising of the following features/accessories complete: VACUUM CIRCUIT BREAKER 12 kV, 3Phase, 50 Hz, 800A, 25kA / 3 Sec, Horizontal Draw out and Horizontal isolation TYPE : HVX-X fitted with Manual as well as Motor operated spring charging mechanism, with 230V AC Motor, Shunt trip coil of 110V DC, Closing coil of 110V DC, Aux Contact 6NO+6NC, Mechanical ON/OFF indicator, Mechanical operation counter, Automatic safety shutter and Push buttons etc.complete all as specified and as directed. ENCLOSURE CRCA Sheet Steel Enclosure suitable for Indoor Protection - IP:4X TREMINATION Incoming : Bottom Cable Entry Outgoing : Bottom Cable Entry Shade No/Ref : Siemens Grey RAL 7032 BUS CONNECTION : COPPER BUS BAR 800A Main Bus : (1R X 50 X 12 mm ) Cu.Bus bar with Heat shrinkable sleeves insulation Earth Bus : (1R X 20 X 6 mm) Cu. Bus bar with Heat shrinkable sleeves insulation CURRENT TRANSFORMER 11 KV Epoxy Resin Cast CT, Single Phase CTR : 100-50/1-1A - 03 Nos Core 1 : Class 0.5, Burden : 15VA (For Metering) Core 2 : Class 5P10, Burden : 15VA (For Protection) Type : Wound Primary, ILV : 12/28/75 kVp, STC : 18.4KA /1 Sec
POTENTIAL TRANSFORMER 11kV, Epoxy Resin cast single phase PT with HT Fuses - 03 Nos PTR : 11KV/RT3/110V/RT3 Core : Class 0.5, Burden : 100VA Voltage Factor : 1.2 Cont. / 1.5 for 30 sec, ILV : 12/28/75 kVp PROTECTION RELAY Numerical type 3 O/C + 1 E/F Relay without RS 485 port Type : Micom P111 L, Aux. supply : 110 V DC, In=5A or 1A MASTER TRIP RELAY Type : CLR H -3 , Aux. supply : 110V DC, 3NO+1NC TRANSFORMER AUXILIARY RELAY Type : CAR H-2-3-3, Aux Supply : 110V DC, 3 Element - 02 Nos METERING (a) Multifunction Meter EM6400NG with RS 485 comm CL : 1.0 of make (b) 8 Window Annunciator . (c) Hooter
INDICATION LAMPS (a) 22.5 dia Red colour LED Indication Lamp - 110V DC (VCB ON). (b) 22.5 dia Green colour LED Indication Lamp - 110V DC (VCB OFF) (c) 22.5 dia Amber colour LED Indication Lamp - 110V DC (VCB TRIP) (d) 22.5 dia White colour LED Indication Lamp - 110V DC (TCH) (e) 22.5 dia Blue colour LED Indication Lamp - 110V DC (SPRING CHARGED) (f) 22.5 dia Red colour LED Indication Lamp - 63.5V AC (R PHASE) (g) 22.5 dia Yellow colour LED Indication Lamp - 63.5V AC (Y PHASE) (h) 22.5 dia Blue colour LED Indication Lamp - 63.5V AC (B PHASE) CONTROL SWITCHES (a) T-N-C Switch Breaker Control Switch Spring return type with Sequence lock (b) Local/Remote Switch 2 position 2 in local 2 in remote (c) Toggle ON/OFF Switch for Space Heater, 10A, 230V AC (d) Door Limit Switch for LED 1NO+1NC, 230V AC (e) Push Button with 2 No Contacts (White)
MINIATURE CIRCUIT BREAKER (a) 4P, 2A, AC MCB (b) 2P, 10A, DC MCB (c) 2P, 10A, AC MCB COMMON FOR SWITCH GEAR (a) Space heater (b) Thermostat (c) Cubicle Illumination lamp with holder (d) 3 pin plug & socket with ON/OFF switch (e) Anti Pumping, Contactor 110V DC, 2NO+2NC (f) Power Pack, Input : 230V AC, Output : 24V DC (g) 11 KV Surge Arrester (9 KV,10 KA) - 03 Nos
Supply, install, commissioning & testing of indoor type HT Vacuum Circuit Breaker O/G Switchgear Panel comprising of the following features/accessories complete : VACUUM CIRCUIT BREAKER 12 kV, 3Phase, 50 Hz, 800A, 25kA / 3 Sec, Horizontal Draw out and Horizontal isolation TYPE : HVX-X fitted with Manual as well as Motor operated spring charging mechanism, with 230V AC Motor, Shunt trip coil of 110V DC, Closing coil of 110V DC, Aux Contact 6NO+6NC, Mechanical ON/OFF indicator, Mechanical operation counter, Automatic safety shutter and Push buttons etc. ENCLOSURE CRCA Sheet Steel Enclosure suitable for Indoor Protection - IP:4X TREMINATION Incoming : From Existing 11 KV Panel Board with necessary additions/alterations to match with the existing VCB system/assy complete. Outgoing : Bottom Cable Entry, Shade No/Ref : Siemens Grey RAL 7032 BUS CONNECTION : COPPER BUS BAR 800A Main Bus : (1R X 50 X 12 mm ) Cu.Bus bar with Heat shrinkable sleeves insulation Earth Bus : (1R X 20 X 6 mm) Cu. Bus bar with Heat shrinkable sleeves insulation CURRENT TRANSFORMER 11 KV Epoxy Resin Cast CT, Single Phase CTR : 25-50/1-1A - 03 Nos Core 1 : Class 0.5, Burden : 15VA (For Metering) Core 2 : Class 5P10, Burden : 15VA (For Protection) Type : Wound Primary, ILV : 12/28/75 kVp, STC : 6 KA /1 Sec
PROTECTION RELAY Numerical type 3 O/C + 1 E/F Relay without RS 485 port Type : Micom P111 L, Aux. supply : 110 V DC, In=5A or 1A MASTER TRIP RELAY Type : CLR H -3 , Aux. supply : 110V DC, 3NO+1NC TRANSFORMER AUXILIARY RELAY Type : CAR H-2-3-3, Aux Supply : 110V DC, 3 Element - 02 Nos METERING (a) Multifunction Meter EM6400NG with RS 485 comm CL : 1.0 (b) 8 Window Annunciator (c) Hooter
INDICATION LAMPS (a) 22.5 dia Red colour LED Indication Lamp - 110V DC (VCB ON). (b) 22.5 dia Green colour LED Indication Lamp - 110V DC (VCB OFF) (c) 22.5 dia Amber colour LED Indication Lamp - 110V DC (VCB TRIP) (d) 22.5 dia White colour LED Indication Lamp - 110V DC (TCH) (e) 22.5 dia Blue colour LED Indication Lamp - 110V DC (SPRING CHARGED) (f) 22.5 dia Red colour LED Indication Lamp - 63.5V AC (R PHASE) (g) 22.5 dia Yellow colour LED Indication Lamp - 63.5V AC (Y PHASE) (h) 22.5 dia Blue colour LED Indication Lamp - 63.5V AC (B PHASE). CONTROL SWITCHES (a) T-N-C Switch Breaker Control Switch Spring return type with Sequence lock (b) Local/Remote Switch 2 position 2 in local 2 in remote (c) Toggle ON/OFF Switch for Space Heater, 10A, 230V AC (d) Door Limit Switch for LED 1NO+1NC, 230V AC (e) Push Button with 2 No Contacts (White)
MINIATURE CIRCUIT BREAKER (a) 4P, 2A, AC MCB (b) 2P, 10A, DC MCB (c) 2P, 10A, AC MCB COMMON FOR SWITCH GEAR (a) Space heater (b) Thermostat (c) Cubicle Illumination lamp with holder (d) 3 pin plug & socket with ON/OFF switch (e) Anti Pumping, Contactor 110V DC, 2NO+2NC (f) Power Pack, Input : 230V AC, Output : 24V DC (g) 11 KV Surge Arrester (9 KV,10 KA) - 03 Nos NOTES FOR ITEM NO 01 & 02 :- 1) Design / drawing / BOM / technical specifications of the VCBs showing the dimensions including foundation/grouting/platform details etc. is to be obtained from OEM / Auth Channel Partner / Supplier & IS to be got approved from Engr-in-charge & GE before placing final order. 2) The cost of periodical/routine servicing/maintenance including minor repairs/replacement of spare parts (if required) including periodical checking of the complete VCBs for the complete defect liability period (2 Years from certified date of completion of work) from the authorized service dealer/rep as & when required/due is deemed to be included in the unit quoted rates.
3) The complete installation, commissioning & testing of the VCBs is to be got done from the OEM or their auth Rep/Sister Concern/Channel Partners only & reports submitted to GE in duplicate. 4) Any item/work etc. missed out in the technical specifications but technically required for efficient working & matching with the existing VCB Assy is deemed to be included in the quoted rates. 5) Necessary electric connections/fixing arrangements/bus-bar modifications/ additions/ alterations or any other related work/job etc. required to match with the existing system/set-up of VCBs shall be as per the recommendations of OEM & cost of the same is deemed to be included in the quoted rates. 6) Necessary foundation/grouting/MS works incl fabrication/welding work/Cement work etc. required for installation of VCBs & matching with the existing VCB Assy shall be provided as per manufacturer's recommendation and the cost for the same shall be deemed to be included in the unit quoted rates. 7) Control cables as per manufacturer's recommendations shall be provided by the contractor and the cost for the same shall be deemed to be included in the unit quoted rates. 8) Contr/Firm is required to visit the site of work for any doubts/clarifications w.r.t. specifications/qty etc. before quoting of the Tender. Any query/clarifications etc. after conclusion of the Contract shall NOT be entertained & decision of the AO shall be final & binding. 9) Quoted rate is deemed to be inclusive of factory Inspection/ Testing of the VCBs before dispatch by an E/M Officer nominated by the Accepting Officer.
Supply, laying, jointing & testing XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade (Earthed), of size 95 sqmm, 3 core with FRLS PVC outer sheath in trenches / through GI pipe / fixed along with pole structure etc complete all as specified and as directed. NOTE : Necessary earthwork, PCC etc. shall be measured and paid separately under relevant items of work.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for INDOOR termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 95 sq mm complete all as specified and as directed.
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for OUTDOOR termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 95 sq mm complete all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of pipe/cables etc. and getting out in hard dense soil complete all as specified and directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as directed.
Removing of excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as directed.
M&L for GI pipe light grade with all running fittings, laid in trenches, under road or fixing on wall/pole/crossing drain/nallah etc. of bore 80 mm complete all as specified and directed. NOTE: Whereever the protection pipes are to be fixed on poles/walls, the cost of suitable type/size/qty of MS clamps with nuts, bolts, washers etc. is deemed to be included in the unit quoted rates as decided by the Engr-In-Charge & GE.
M&L for providing sand cushioning for protection of UG cable in trenches with dry (coarse) sand approved quality including filling, spreading and punning down to desired thickness complete. NOTE: Only punned thickness of sand shall be considered for payment purpose.
Supply and laying un-reinforced precast concrete cable cover, class HV, Type 1, flat, size 300 x 180 x 40 mm in trenches for protection of UG Cable with width equal to length of PCC cover, laid dry and flat complete all as specified and as directed.
M&L for earthing complete with copper plate electrode 600 x 600 x 3.15 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below normal ground level with the top edge of the earth plate not less than 1.5 mtr (B.G.L.) and connected to copper strip 20 x 3 mm by means of bolts, nuts, check nuts, and washers of galvanized iron including PCC chamber & cover with suitable handle, including necessary excavation and earth work in any type of soil, 20 mm dia med grade galvanized steel tube for watering with one end fixed with cast iron funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection & common salt, charcoal in alternate layers etc. complete all as shown in EP No 3 of SSR Part 1 and testing on completion complete.
M.V.K.ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .