Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.5 LAccepted-AOC | ₹38.5 L | L1 | Accepted-AOC qualified |
| 2 | L2₹41.5 LRejected-AOC 3 JAINANDAN NIWAS NEAR MITALI APARTMENT OPP KORUM MALL KHOPAT THANE 400602 | THANE | THANE | MAHARASHTRA | 400602 | ₹41.5 L | L2 | Rejected-AOC qualified |
| 3 | Rejected-Technical | - | - | Rejected-Technical Uploded Experience Certificate is not as per NIT, hence disqualified |
| Sl No | Description | Qty | Unit | National Electricals L1 | Kevla Engineering L2 |
|---|---|---|---|---|---|
| 0.00Sub Estimate | |||||
| 1.00 | 1. Designing, providing, erecting & commissioning of Main L T Panel fabricated with 16 SWG CRCA sheet base wall mounted with supporting angles, painted with powder coating/ epoxy paint of required shade, incomer side consist of L&T make 250A, 25KA, 4P, MCCB with RHOM-1 No, Control MCB, 6A,SP,10KA- 3 Nos, L&T make Load Manager- 01 No, Newtek make CTs, 250/5A, CL-1, 10VA – 4 Nos, RYB lamps and Outgoing side consist of L&T make 100A, 4P, MCCB, 10KA ROHM – 10 Nos, L&T make 63A, 4P, MCB, 10KA- 2 Nos having aluminum bus bar with epoxy insulator, degree of protection-IP-55, control wiring 1.5 Sq.mm and CT wiring by 2.5 Sq.mm Flexible copper wire. | 1 | Number | 6,30,000 ₹6.3 L | 4,50,000 ₹4.5 L |
| 2.00 | 2. LT Cables (Aluminum) (CB-LT/AL)
2.1. Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL | 1,250 | Meter | 390 ₹4.9 L | 395 ₹4.9 L |
| 3.00 | 3. Cable Enclosures (CB-CE)
3.1 Supplying and laying (including excavation of suitable width & depth up to 90 cm) 120 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete. | 800 | Meter | 350 ₹2.8 L | 390 ₹3.1 L |
| 3.10 | 3.2. Supplying & laying (including excavation) reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. | 75 | Meter | 600 ₹45,000 | 610 ₹45,750 |
| 4.00 | 4. Supplying, installing, testing and commissioning of 30V/100 AH VRLA Battery Bank consisting of 15 Nos. Cells @ 1.75ECV with standard accessories like racks/stands, inter-cell connectors, etc. | 15 | Number | 19,500 ₹2.9 L | 15,000 ₹2.3 L |
| 5.00 | 5. Supplying, installing, testing and commissioning of Battery Charger: 30V/25A Float Cum Boost Charger (FCBC) with Inbuild DCDB - [ I/C - 63A -1 nos. & O/G - MCB-10A-2P-DC-2 Nos. MCB-16A-2P- DC-6 Nos, 25A MCB- 2nos, 32A - MCB - 2nos]. (NS swift), 3 Phase 3/4 Wire, Full Wave, Full Controlled, Suitable for 30V- 100AH VRLA Battery of 15 Cells as per enclosed TSP. [33.75V in Float mode & 34.5V in Boost mode] | 1 | Number | 4,00,000 ₹4 L | 3,85,000 ₹3.9 L |
| 6.00 | 6. Repairing of the 375 KVAR Static Var Generator panel (Insta sine make)with the replacement of necessary components such as 1) Wire Harness for 125 KVAR SCG 2) 4 inch AC Fan 3) DC Cooling fans ( 4 Nos ) 4) Main ControlCard 3L Module ( repairing charges ) 5) 7 inch TFT Touch Screen Display.6) Display Card ( repairing Charges ) 7) IGBT Driver Card 8) LCL Capacitor 40uF,3 Ph 9) Semifuse 200 A 10 ) Backlight Strip 11) Main Contactor Link Set for Main Contactor 150 A 12) Aux Contactor including Retro- fitting charges ,packing,shipping,and forwarding ( to and fro ) and recommissioning charges of 375 KVAR Static Var Generator | 1 | Job | 3,50,000 ₹3.5 L | 3,86,000 ₹3.9 L |
| 7.00 | 7. Accessories
7.1 Supplying and erecting copper strip of required sizes used for earthing on wall and/or any other purpose with necessary aluminium clamps fixed on wall painted with bituminous paint with joints required as per specification no EA-EP. | 70 | kilogram | 750 ₹52,500 | 1,100 ₹77,000 |
| 8.00 | 8. Plate, Pipe type Earthing (EA-EP)
8.1. Supplying, installing and testing earthing with copper earth plate size 60 x 60 x 0.315 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover with minimum 25 kg Carbon based environment friendly back fill ground ehancing compound complete with all accesories of copper materials & recording the results as per specification no EA-EP/EF | 6 | each | 16,500 ₹99,000 | 15,000 ₹90,000 |
Tender Value
₹39.6 L
EMD Value
₹39,600
Closing Date
24 Apr 2026, 5:00 pmClosed
SE E and M Comm Mumbai
Office of the Superintending Engineer (E and M) Comm MIDC HQ Andheri.
AMBERNATH E and M M and R to Shahad Water Work Providing, erecting and commissioning of LT panel and cables for lighting load separation and other misc. works at WTP Shahad
2026_MIDC_1294477_1
MIDC/E and M/AMB/38380/02/2026-27
Open Tender
Electrical and Maintenance Works
120 days
Shahad
Please refer Tender documents.
2 documents required · 2 mandatory
₹10,030
₹39,600
5 Jun 2026
11 Apr 2026
28 Apr 2026
11 Apr 2026
24 Apr 2026
15 Apr 2026
11 Apr 2026 - 13 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 0Sub Estimate | |||||
| 1 | 1. Designing, providing, erecting & commissioning of Main L T Panel fabricated with 16 SWG CRCA sheet base wall mounted with supporting angles, painted with powder coating/ epoxy paint of required shade, incomer side consist of L&T make 250A, 25KA, 4P, MCCB with RHOM-1 No, Control MCB, 6A,SP,10KA- 3 Nos, L&T make Load Manager- 01 No, Newtek make CTs, 250/5A, CL-1, 10VA – 4 Nos, RYB lamps and Outgoing side consist of L&T make 100A, 4P, MCCB, 10KA ROHM – 10 Nos, L&T make 63A, 4P, MCB, 10KA- 2 Nos having aluminum bus bar with epoxy insulator, degree of protection-IP-55, control wiring 1.5 Sq.mm and CT wiring by 2.5 Sq.mm Flexible copper wire. | 1 | Number | - | - |
| 2 | 2. LT Cables (Aluminum) (CB-LT/AL)
2.1. Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 50 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL | 1,250 | Meter | - | - |
| 3 | 3. Cable Enclosures (CB-CE)
3.1 Supplying and laying (including excavation of suitable width & depth up to 90 cm) 120 mm outside dia. double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface, complete. | 800 | Meter | - | - |
| 3.1 | 3.2. Supplying & laying (including excavation) reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. | 75 | Meter | - | - |
| 4 | 4. Supplying, installing, testing and commissioning of 30V/100 AH VRLA Battery Bank consisting of 15 Nos. Cells @ 1.75ECV with standard accessories like racks/stands, inter-cell connectors, etc. | 15 | Number | - | - |
| 5 | 5. Supplying, installing, testing and commissioning of Battery Charger: 30V/25A Float Cum Boost Charger (FCBC) with Inbuild DCDB - [ I/C - 63A -1 nos. & O/G - MCB-10A-2P-DC-2 Nos. MCB-16A-2P- DC-6 Nos, 25A MCB- 2nos, 32A - MCB - 2nos]. (NS swift), 3 Phase 3/4 Wire, Full Wave, Full Controlled, Suitable for 30V- 100AH VRLA Battery of 15 Cells as per enclosed TSP. [33.75V in Float mode & 34.5V in Boost mode] | 1 | Number | - | - |
| 6 | 6. Repairing of the 375 KVAR Static Var Generator panel (Insta sine make)with the replacement of necessary components such as 1) Wire Harness for 125 KVAR SCG 2) 4 inch AC Fan 3) DC Cooling fans ( 4 Nos ) 4) Main ControlCard 3L Module ( repairing charges ) 5) 7 inch TFT Touch Screen Display.6) Display Card ( repairing Charges ) 7) IGBT Driver Card 8) LCL Capacitor 40uF,3 Ph 9) Semifuse 200 A 10 ) Backlight Strip 11) Main Contactor Link Set for Main Contactor 150 A 12) Aux Contactor including Retro- fitting charges ,packing,shipping,and forwarding ( to and fro ) and recommissioning charges of 375 KVAR Static Var Generator | 1 | Job | - | - |
| 7 | 7. Accessories
7.1 Supplying and erecting copper strip of required sizes used for earthing on wall and/or any other purpose with necessary aluminium clamps fixed on wall painted with bituminous paint with joints required as per specification no EA-EP. | 70 | kilogram | - | - |
| 8 | 8. Plate, Pipe type Earthing (EA-EP)
8.1. Supplying, installing and testing earthing with copper earth plate size 60 x 60 x 0.315 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover with minimum 25 kg Carbon based environment friendly back fill ground ehancing compound complete with all accesories of copper materials & recording the results as per specification no EA-EP/EF | 6 | each | - | - |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.93 MB
TenderDocument.pdf
Tender Documents • 0.32 MB
ItemSpecification.pdf
Other Document • 0.07 MB
BOQ_2224261.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid