Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.0 CrAccepted-Finance GROUND FLOOR THAKUR COMPLEX BASANTPUR | BASANTPUR | SHIMLA | HIMACHAL PRADESH | 171018 | ₹1.0 Cr | L1 | Accepted-Finance ok |
| 2 | L2₹1.2 CrRejected-Finance V THANA PO BAROTI SUNDER NAGAR DISTT MANDI HP | MANDI | HIMACHAL PRADESH | 175001 | ₹1.2 Cr | L2 | Rejected-Finance ok |
| 3 | Rejected-Technical | - | - | Rejected-Technical ok |
Tender Value
₹1.3 Cr
EMD Value
₹2.6 L
Closing Date
11 Feb 2026, 2:00 pmClosed
XEN Electrical Division No. 1 Shimla
The Executive Engineer Electrical Division No-1 HPPWD Shimla-9
Construction of 100 Bedded Civil Hospital Building at Shillai District Sirmour H.P SH Providing Electrical installation work therein.
2026_PWD_127576_2
Electrical Division-I dated 5.02..2026
Open Tender
Electrical Works
730 days
SHIMLA
As per bidding Document
17 documents required · 17 mandatory
₹5,000
₹2.6 L
30 Apr 2026
5 Feb 2026
12 Feb 2026
5 Feb 2026
11 Feb 2026
5 Feb 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Group-C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc as required.
Group-C
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
2 X 10 sq. mm + 1 X 6 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 1.5 sq. mm
3 x 2.5 sq. mm
Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required.
Armoured cable 6 sq. mm (2 core)
Armoured cable 25 sq. mm (3.5 core)
Armoured cable 35 sq. mm (3.5 core)
Armoured cable 50 sq. mm (3.5 core)
Armoured cable 70 sq. mm (3.5 core)
Armoured cable 95 sq. mm (3.5 core)
Armoured cable 630 sq. mm (3.5 core)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/ 6 amps switch.
3 pin 5/6 A socket outlet
Supplying and fixing following size/ modules, GI box for Step Light but excluding modular base & cover plate in recess etc. as required.Make :- Havells , Anchor or any other Approved by the Engineer In charge
1 or 2 Module (75mmX75mm)
Supplying and fixing electrical switch board, having 3 No. of 5 amp. switches and socket on suitable size of metal box of 75mm deep 12 module (200mmX150mm) on surface or in recess with suitable modular sheet cover in the front i/c providing and fixing 3 No. 5 pin 5/6 amp socket outlet and 5/6 amp modular type switch, connection, painting etc.as req. (For light plugs).Make:- havells, Anchor or any other approved by the Engineer in Charge .
Supplying and fixing PVC batten/ angle holder including connections etc. as required.
Providing and installation of following type of LED retrofit lamp B-22 holder base with polycarbonate body and aluminium heat sink; suitable for input voltage: AC 220-240 V, 50/60Hz, including mounting in existing fixture, testing etc. as required complete in all respects. Make: Havells, Wipro or any other approved by Engineer-in-Charge.
LED Lamp .5 Watt ( Green)
LED Lamp .5 Watt ( Red)
LED Lamp 9 Watt
S/E of LED Batten with polycarboante body and diffuser The fitting should be installed on existing surface/recess The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:-
Wattage of LED fittings :-As per following parameter.
Total lumens of the fittings. :-as below
Diffuser :-Polycarbonate diffuser/PMMA
Operating voltage :-140 V to 270 V, AC supply or better.
Input frequency :-50 Hz + 1 Hz
Power factor :-Minimum 0.90
Luminaire efficacy :->100 lm/w
Color rendering index:-CRI shall be greater than 80
Working/ operating temperature :-0ºC to + 45º C or better
Color temperature :-60000K + 10%
Electronic Driver :-
Drive current (LED):-As per OEM.
Operating voltage :-140 V to 270 V AC supply or better
Type of driver :-Constant current output driver
THD :-Less than 10%
Surge Protection :-2.5 KV minimum
Efficiency Driver:->85%
Protection:-Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver :-2 years against manufacturing defect.
Fixture :-Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model :-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED :-25000 burning hours at 70% lumen maintenance
LED Batten Light 10W (1000 Lm)
S/E of LED Batten with aluminium extrusion housing The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:-
Wattage of LED fittings :-As per following parameter.
Total lumens of the fittings. :-as below
Diffuser :-Polycarbonate diffuser/PMMA
Operating voltage :-140 V to 270 V, AC supply or better.
Input frequency :-50 Hz + 1 Hz
Power factor :-Minimum 0.90
Luminaire efficacy :->110 lm/w
Color rendering index:-CRI shall be greater than 80
Working/ operating temperature :-0ºC to + 45º C or better
Color temperature :-60000K + 10%
Electronic Driver :-
Drive current (LED):-As per OEM.
Operating voltage :-140 V to 270 V AC supply or better
Type of driver :-Constant current output driver
THD :-Less than 10%
Surge Protection :-2.5 KV minimum
Efficiency Driver:->85%
Protection:-Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver :-2 years against manufacturing defect.
Fixture :-Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model:-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED:-50000 burning hours at 70% lumen maintenance
LED Batten Light 20W (2200 Lm)
S/E of LED Panel with PDC body and prismatic diffuser to be mounted in Surface/Recess. The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:-
Wattage of LED fittings :-As per following parameter.
Total lumens of the fittings. :-as below
Diffuser :-Prismatic multilayer diffuser UGR <19
Operating voltage :-140 V to 270 V, AC supply or better.
Input frequency :-50 Hz + 1 Hz
Power factor :-Minimum 0.90
Luminaire efficacy :->120 lm/w
Color rendering index :-CRI shall be greater than 80
Working/ operating temperature :-0ºC to + 45º C or better
Color temperature :-60000K + 10%
Electronic Driver :-
Drive current (LED) :-As per OEM.
Operating voltage :-140 V to 270 V AC supply or better
Type of driver :-Constant current output driver
THD :-Less than 10%
Surge Protection :- 2.5 KV minimum
Efficiency Driver :->85%
Protection :-Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver :-2 years against manufacturing defect.
Fixture :-Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model :-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED :-50000 burning hours at 70% lumen maintenance
Square LED Panel Light 24 W Surface Mounted (1 feet x1 feet) 2880 Lm
Square LED Panel Light 36 W Surface Mounted ( 2 feet x 2 feet ) 4320 Lm
S/E of LED Downlighter round type surface with CRCA/PDC body and diffuser The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:-
Wattage of LED fittings :-As per following parameter.
Lumen output of the fitting:-as below
Diffuser :-Polycarbonate diffuser/PMMA
Operating voltage :- 140 V to 270 V, AC supply or better.
Input frequency :-50 Hz + 1 Hz
Power factor :-Minimum 0.90
Luminaire efficacy :->100 lm/w
Color rendering index:-CRI shall be greater than 80
Working/ operating temperature :-0ºC to + 45º C or better
Color temperature :-60000K + 10%
Electronic Driver
Drive current (LED):-As per OEM.
Operating voltage :-140 V to 270 V AC supply or better
Type of driver :-Constant current output driver
THD :-Less than 10%
Surge Protection :-2.5 KV minimum
Efficiency Driver:->85%
Protection:-Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver :-2 years against manufacturing defect.
Fixture :-Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model:-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED:-50000 burning hours at 70% lumen maintenance
Round LED Down Light Surface ( 500 Lm)
S/E of LED Downlighter surface square with CRCA/PDC body and diffuser The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:-
Wattage of LED fittings :-As per following parameter.
Lumen output of the fitting :-as below
Diffuser :-Polycarbonate diffuser/pmma
Operating voltage :-140 V to 270 V, AC supply or better.
Input frequency :-50 Hz + 1 Hz
Power factor :-Minimum 0.90
Luminaire efficacy :->85 lm/w
Color rendering index :-CRI shall be greater than 80
Working/ operating temperature :-0ºC to + 45º C or better
Color temperature :-60000K + 10%
Electronic Driver :-
Drive current (LED) :-As per OEM.
Operating voltage :-140 V to 270 V AC supply or better
Type of driver :-Constant current output driver
THD :-Less than 10%
Surge Protection :-2.5 KV minimum
Efficiency Driver :->85%
Protection :-Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver :-2 years against manufacturing defect.
Fixture :-Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model :-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED :-50000 burning hours at 70% lumen maintenance
Square LED Down Light Surface ( 1500 Lm)
Square LED Down Light Surface ( 2000 Lm)
S/E of LED bulk head IP 66 rated with aluminium body/PDC housing The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:-
Wattage of LED fittings :-As per following parameter.
Total lumens of the fittings. :-as below
Diffuser :-Polycarbonate diffuser/PMMA
Operating voltage :-140 V to 270 V, AC supply or better.
Input frequency :-50 Hz + 1 Hz
Power factor :-Minimum 0.90
Luminaire efficacy :->80 lm/w
Color rendering index:-CRI shall be greater than 80
Working/ operating temperature :-0ºC to + 45º C or better
Color temperature :-60000K + 10%
Electronic Driver :-
Drive current (LED):-As per OEM.
Operating voltage :-140 V to 270 V AC supply or better
Type of driver :-Constant current output driver
THD :-Less than 10%
Surge Protection :-2 KV minimum
Efficiency Driver:->85%
Protection:-Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver :-2 years against manufacturing defect.
Fixture :-Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model:-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED:-50000 burning hours at 70% lumen maintenance
LED Bulk Head 10 Watt ( 800 Lm)
Providing and installation of LED step light Step light in powder coated cast aluminium body for wall recessed application with IP 65 Protection suitable for input voltage: AC 220-240 V, 50±1 Hz , complete with all accessories, including connection testing etc. as required. Havells, Wipro or any other approved by the Engineer in Charge.
LED Step Light 5 Watt
Supplying and fixing LED flood light with high power LED's assembled on single MCPCB and additional unique peanut lens on each LED, system lumens output with efficacy>120 lm/Watt. luminiare having color temp upto 6500K & 50000 hrs. burning life with minimum @ L 70, The colour rendering index of LED light should be more than 70. Luminiare comprises of driver, PF > 0.90 & surge protection 10KV. Housing made of pressure die cast aluminium with heat resistant flat glass, IP65 protection and relevent LM 79/80 complaince from UN/NABL Lab connection wire, testing etc. to complete the job.
LED Flood Light 30 Watt
Supply, Installation, Testing and Commissioning of following sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.85, Air delivery minimum 215 CMM, 300 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote/ BLDC electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Ceiling Fan 1200 mm sweep
Ceiling Fan 1400 mm sweep
Supplying and fixing Metal fan box as required complete in all respect as per statifaction of Er-in- charge etc .
Providing and installation exhaust fan of following sizes in the existing opening, Double ball bearing type metal frame including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required: of Approved Make Domestic type.
Exhaust Fan, Light duty, (Domestic) 225/230 mm sweep
Providing and installation exhaust fan of following sizes in the existing opening, Double ball bearing type metal frame including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required: of Approved Make Heavy Duty type.
Exhaust Fan, Heavy duty, 300 mm sweep (900/1400rpm)
P/F openable sheet metal shutter suitable for exhaust fan size 300 Inch as required complete in all respect.
Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Supplying and fixing following rating, followings poles 10ka 240/415v 'C' curves miniature circuit braker suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required.
S/E of MCCB 4 Pole 415 Volt. with Thermal Magnetic Release for overload and short circuit protection breaking Capacity (Ics=100% Icu with positive isolation) in Sheet Steel Enclouser with Spreader link i/c Making connection testing commissioing etc. as required complete in all respect.Make:- C&S, Legrand , ABB or any other approved by the Engineer In charge.
MCCB 63 Amp. 25 ka 4 Pole
MCCB 200 Amp. 25 ka 4 Pole
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).
6 way , Double door
8 way , Double door
12 way , Double door
Supplying, Installation, Testing & Commissioning of Modular, Sectionalized (Form 4B Construction) Low Voltage Panel suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply system as per standard IEC 61439 Part 1 & 2 as Totally Type Tested Assembly and of suitable size fabricated in compartmentalized design from CRCA sheet steel of 2mm thick for frame work and covers & doors of 1.6mm thick sheet, 3mm thick for gland plates with stiffeners wherever required, having vibration free structure chemically treated with seven tank process before painting for surface treatment and powder coated, with suitable electrolytic grade high conductivity Copper busbar extensible type, DMC/SMC bus bar supports, bottom base channel of MS section not less than 100mm x 50mm x 5 mm thick, fabrication shall be done in transportable sections, entire LENGTH panel shall have a common copper earth bar of suitable size at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Copper bus bars and control wiring with 2.5 Sq.mm. PVC insulated copper FR conductor S/C cable for voltage & Current respectively. The board shall be dust and vermin proof with degree of protection IP42, free standing type mounted on base channel. The job includes labour, carriage of panel to the site, testing and commissioning as required to complete the job as per drawing of the panel to the satisfaction of the Engineer in charge. The LT Panel should be tested for internal arc withstand capacity of 50KA for 0.3 second as per IEC-61641. The job includes making connection of the outgoing cable with lugs/thimbles duly crimped and making connection with the incoming existing O/H bus trunking or cable as per site requirement. The LT panel should have provision of following switchgear and accessories as mentioned below: -
Incomming
ACB 1000A 4 Pole 50 KA , Microprocssor Based -1 No.
1000A Copper Bus Bar TPN of Electrolytic Grade E91 Having Cross Section 1x80x10 MM Per Phase ,1x80x10MM for Neutral and Earthing Strip 1x40x10 MM
Metering
Digital VAF Meter -1 Set
CT's 800/5A- 3 Nos.
Phase Indication set with control MCB SP-1 Set
OutGoing Section-I (Light Ckt.)
MCCB 500A 36 KA with TMA Protection Release (Ics= 100% Icu)-1 No.
500A , 4P ON Load Change Over Switch -1 N0.
500A Copper Bus bar TPN of Electrolytic Grade E91 Having Cross Section 1x40x10 MM Per Phase, 1x40x10 MM for Neutral and Earthing Strip 1x20x10 MM
MCCB 125A, 36 KA ( Is=100% Icu)-1 No.
MCCB 100A, 36 KA ( Is=100% Icu)-3 Nos.
MCCB 63A, 36 KA ( Is=100% Icu)-5 No.
OutGoing Section-II (Heating Ckt.)
MCCB 500A 36 KA with TMA Protection Release (Ics= 100% Icu)-1 No.
500A Copper Bus bar TPN of Electrolytic Grade E91 Having Cross Section 1x40x10 MM Per Phase, 1x40x10 MM for Neutral and Earthing Strip 1x20x10 MM
MCCB 200A, 36 KA ( Is=100% Icu)-1 No.
MCCB 63A, 36 KA ( Is=100% Icu)-10 Nos.
Size of Panel 3500 MM (W) X 2375 MM (H) X 1000MM (D)
Main LT Panel 1000A
Supplying, Installation, Testing & Commissioning of Low Voltage Panel suitable for 415 V, 3 Phase, 4 wire 50 Hz AC supply system as per standard IEC 61439 Part 1 & 2.The LT Panel Enclosure Cubicles shall be design verified assemblies completely as per IEC61439-1&2 having IP42 enclosure protection having form 4B construction duly tested with IK10, shall be of aesthetic design, dust, damp & vermin proof, shall be modular, extendable and shall have maintenance friendly construction, shall have fully compartmentalized bolted construction, shall be metal clad sheet steel enclosed cubicle, floor mounting type suitable for indoor installations, shall have structural steel framework as per IEC 61439 part 1 & 2, shall have integral base frame with bottom cable entry having removable gland plates. The panel shall be made out of GI Sheet Steel & CRCA Sheet Steel. The CRCA Steel parts shall be powder coated with RAL7035 powder colour after proper 7Tank Chemical Treatment. Gasketing shall be done properly to prevent any ingress of dust & vermin. The LT panel should have provision of following switchgear and accessories as mentioned below: -
Incomming
MCCB 125A 4 Pole 36 KA , TMA Protection Release ( Ics=100 % Icu) -1 No.
200 A Copper Bus Bar TPN of Electrolytic Grade E91 Having Cross Section 1x30x10 MM Per Phase ,1x30x10MM for Neutral and Earthing Strip 1x20x10 MM
Metering
Digital VAF Meter -1 Set
CT's 800/5A- 3 Nos.
Phase Indication set with control MCB SP-1 Set
OutGoing Section-I (Light Ckt.)
MCCB 63A 36 KA with TMA Protection Release (Ics= 100% Icu)-1 No.
63A , 4P ON Load Change Over Switch -1 N0.
63A Copper Bus bar TPN of Electrolytic Grade E91 Having Cross Section 1x25x3 MM Per Phase, 1x25x3 MM for Neutral and Earthing Studs
OutGoing Section-II (Heating Ckt.)
MCCB 100A 36 KA with TMA Protection Release (Ics= 100% Icu)-1 No.
100 A Copper Bus bar TPN of Electrolytic Grade E91 Having Cross Section 1x20x10 MM Per Phase, 1x20x10 MM for Neutral and Earthing Strip 1x25x3 MM
Size of Panel 1000MM (W) X 1550 MM (H) X 300MM (D)
Distribution Panel -125A
Supplying and erection of Distribution (confirming to (IEC code-61439 part 1&2) of dimensions 700mm(H)* 400mm(W)* 200mm (D) with plus 5cm variation,made from CRCA MS sheet enclosure. Panel will be fabricated with 16-SWG CRCA sheet steel for load bearing surfaces and 16-SWG for non load bearing surfaces fully dust & vermin proof,complete with locking arrangements to hose MCCB 63 amp (4 pole) 36 KA with TMA Protection release (Ics=100% Icu) as incommer and 100 Amp Copper busbar TPN of ElectronicGrade E91 Having Cross Section 1x20x10 MM for Phase and Neutral and 1x 25 x 3MM for Earth Strip as outgoing suitable for Light/ Heating Load & 1 set RYB light indicator set and cable alley as required complete in all respects including the cost of switchgear . The cubical pedestal shall have cable entry box at one side,with epoxy powder coated approved paint and bonding to the existing earth etc.(i) Distribution Pantel-100A
Supplying and erection of light sub - panel (confirming to (IEC code-61439 part 1&2) of dimensions 700mm(H)*400mm(W)*200mm(D) with plus 5cm variation,made from CRCA MS sheet enclosure. Panel will be fabricated with 16-SWG CRCA sheet steel for load bearing surfaces and 16-SWG for non load bearing surfaces fully dust & vermin proof,complete with locking arrangements to hose MCCB 63 amp (4 pole) 36 KA with TMA Protection release (Ics=100% Icu) as incommer and 63 Amp Copper busbar TPN of ElectronicGrade E91 Having Cross Section 1x25x3 MM for Phase and Neutral and 1x 25 x 3MM for Earth Studs as outgoing suitable for Light/ Heating Load & 1 set RYB light indicator set and cable alley as required complete in all respects including the cost of switchgear . The cubical pedestal shall have cable entry box at one side,with epoxy powder coated approved paint and bonding to the existing earth etc. (i) Distribution Panel -63A.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Providing and installation of stationary storage type Electric water heater (Geyser) of various sizes with 8 bar pressure rating Five star BEE rating and safety valve installation by means of expansion-bolts with nuts and washers, including embedding of expansion-bolts in the wall, making good the damages, electrical connections, testing etc. complete as required:-
15 Liter capacity water heater (Cat-A)
25 Liter capacity water heater (Cat-A)
35 Liter capacity water heater (Cat-A)
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
Armoured cable 6 sq. mm (twin core)
S/E of 7 Mtr. long Hot dipped Galvanized pole of octagonal cross-section continuously tapered made out from high tensile steel of minimum thickness 3mm complete with the base plate of minimum size 220mm x220mm x12mm alongwith inbuilt lockable junction box which should be operated with single key with connectors of Elmax / Connectwell / Essen / Wago make for the cable termination as per site requirement and one no. 6 Amps. Single pole MCB for each luminaire. The diameter across from the dimensions of the base and top should be minimum 130 mm and 70mm A/F (Across Face). The size of the poles and foundation bolts shall be suitable to withstand the maximum wind speed/ pressure as per IS-875. There should be no any circumferential welding on the pole. The method and material shall comply with as BSEN-10025 grade S355 or equivalent poles should be hot dipped galvanized in single dip to 65 microns min. confirming to IS 2629-1966. The material and specifications of flange plate/base plate shall be as per IS 2062. The street light poles shall be as per IS 2062. The street light poles shall be erected in the existing RCC foundation with 4 nos. special foundation bolts ‘J’ type minimum 700mm long galvanized M.S. rod of duly threaded of minimum 20mm dia in existing RCC foundation of suitable size as per the approved drawing. The material of steel foundation belts shall be confirming to grade EN-8 exposed threaded portion of foundation bolts shall be hot dipped galvanized. The octagonal pole should be of Bajaj / Transrail / Utkarsh / Valmont/ Salasarmake only. (The cost of 7Meter long S/L octagonal poles is including with 4 nos. x M20 x 600mm long ‘J’ type bolts with nuts, carriage of pole at site & installation complete as required.
GI Octagonal Light Pole-7m Long
Foundation for Pole;- Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 Sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soiwithin a lead of 50m.All kinds of soil
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size)
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.Thermo-Mechanically Treated bars
Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement:1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size)
Centering and shuttering including strutting, propping etc. and removal of form for :Foundations, footings, bases of columns, etc. for mass concrete
Supply, Fabrication and erection of GI pipe (medium class) bracket with suitable size of nipple for mounting the existing street light fitting with the following specifications.
The bracket shall be made by Medium Class GI pipe of 2” dia with an angle of inclination of as 105 degree to vertical
The 2” dia G.I. pipe shall be connected to a 4” dia G.I. pipe (45 cms) as required & canopy with top end closed with 14 G MS sheet to avoid entry of rain water in the pole.
The 2” dia pipe shall be welded at a distance of 2” from the close end with 4” dia GI pipe
The bracket shall be slipped over the top section of octagonal pole & fixed with 2 Nos. ½” dia GI nuts & bolts.
A triangular 14 G MS sheet pieces of 2” shall be welded between two pipes.
Single arm bracket made out of 2” dia. G.I. pipe 3’ overhang.
S/E of LED Street Light IP 66 rated with aluminium body/PDC housing.The job includes carriage, erection, making connections testing and commissioning of the fittings.The Specification of the Fittings is as under :-
Wattage of LED fittings :-As per following parameter.
Total lumens of the LED fittings
Body of fitting :-Pressure dia cast aluminium body with Extruded Aluminium heat sink
Input frequency :-50 Hz + 1 Hz
Operating voltage- 140 V to 270 V, AC supply or better.
Power factor :-Minimum 0.90
Luminaire efficacy :->110 lm/w
Color rendering index:-CRI shall be greater than 70
Working/ operating temperature :-00 to + 450c or better
Color temperature :-60000K to 65000K
Electronic Driver :-
Drive current (LED) :-As per OEM.
Operating voltage :-140 V to 270 V AC supply or better
Type of driver :-Constant current output driver
THD :-Less than 10%
Surge Protection :-(10 KV minimum External) ( 4 KV Internal)
Efficiency Driver:->85%
Protection:-Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver :-2 years against manufacturing defect.
Fixture :-Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model:-Havells/Bajaj/Panasonic with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED:-50000 burning hours at 70% lumen maintenance
LED Street Light 60 Watt
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
63 mm dia (OD-63 mm & ID-50 mm nominal)
90 mm dia (OD-90 mm & ID-75 mm nominal)
120 mm dia (OD-120 mm & ID-102 mm nominal)
Supplying,installation,testing and commissioning of Passive Infrared(PIR) technology based occupancy sensor having high preformance, non regulating programmable type, suitable for connected load upto 10 A , for mounting height up to 2.8 mtr and for 5 m diameter coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required.
Conditions:-
The work shall be carried out according to CPWD/ HPPWD General Specifications.
The work shall be completed to the entire satisfaction of the Engineer-in-charge.
The firm will have to follow fair wage clause.
Sub-standard work will not be accepted.
No claim on account of fluctuation in prices due to any reason shall be considered.
The quantity can be increased or decreased as per actual requirement at site.
The conditional tenders shall not be accepted.
No premium will be allowed on M.R. Items, abatement, if any shall be applicable on all items including market rates.
The contractor has to employ qualified Engineer for the supervision of work at site.
Any error or omission in nomenclature or unit can be corrected at any stage.
The quality of material shall be strictly in accordance with the specification given in DNIT.
All the material shall be inspected by the Engineer-in-charge of work before installation at site.
The boards & M.S. boxes should be painted with 2 coats of superior quality paint after one coat of primer.
Separate colour of wires shall be used for phase and neutral so as to distinguish it for live conductor.
All the cable/ wire connections should be done through lugs / thimbles duly crimped with proper crimping tools & no extra payment shall be made on this account.
The department reserves the right to issue any amendment to the work order as emergency demands or allow of altogether cancel the contract without assigning any reason. The department reserves the right to delete / add any item.
The extra/ substitute items will not be allowed against this work without the prior approval of the competent authority.
Security shall be deducted on each running/ Final bill of the firm
The firm shall ensure, the availability a licensed electrician/ supervisor/ qualified Engineer during the erection, testing and commissioning.
The contractor will have to produce invoice/ gate pass of the manufacturer for major items of material to be installed against S/E of work for genuine of the material.
The firm shall be quote the rates inclusive all the taxes/ GST whatever required and no extra payment shall be made in this respect.
The fittings/ material shall be inspected by the concerned Engineer-in- Charge with the representative of the firm and necessary certificate shall be signed by the representative of the firm for its genuineness.
Any deviations to the clauses in the tender specifications must be clearly and separately indicated otherwise it shall be presumed that the offer is in line with requirements of tender.
The work of S/E material except LED fittings/ fans shall be guaranteed for a period of one year against any manufacturing defect from date of handing over to the department. No extra payment shall be made on the account of labour charges, installation at site.
The LED fittings/ LED drivers/ LED tube rods/ fans shall be guaranteed for a period of two years for free replacement from the date of completion of work / taking over the department.
The firm will submit the test report for LM-79 & IEC standards for safety, performance and Efficacy of LED fittings from Govt./ NABL/ UL accredited lab.
The firm will submit the LM-80 report from the chip manufacturer of LED fittings.
One Number LED fitting of each type i.e. 2’x2’ LED Fitting surface Type,2’x2’ LED Fitting recess Type and 1’x1’ LED Fitting surface Type taken from lot of fitting and shall be got tested for Photometric Test, Electrical Parameters, THD, Surge Protection, IP Rating from the 3rd party NABL Govt. approved lab before installation at site. The cost in respect of testing LED fittings shall be borne by the Department. If the fitting fails the test, the firm has to install the other approved make of the fitting and the cost for the testing of other make fitting from the lab shall be borne by the firm if required.
Approved Makes.
Steel Conduit :-BEC,AKG,RKG, Precision Pipes
PVC Conduit:-Anchor, AKG,RKG, Precision Pipes, Diplast.
FRLS Wires:-Havells, Finolex, RR Kabel, KEI, Plaza, Polycab.
Switches/ sockets (Premium):- Havells, (Athena), Goldmedal (AIR) (GIFA). Anchor (Penta) Legrand (Arteor), L&T (Entice)
MCB’s and Distribution board:- Havells, ABB, Legrand, L&T, Schneider. ( Distribution board and MCB has to be of same company).
MCCB’s and switchgear:- Havells, ABB, Legrand, L&T, Schneider.
Bus bars Copper:- Havells, Anchor
Geyser:- Havells, racold, bajaj,Goldmedal, jaguar ( 5 star rated).
Cat 6:- Havells, Legrand, R&M, Systimax, Panduit, Molex
Ceiling fan, BLDC:- Atomberg (Efficio), Havells (Efficia Neo), Orient (hector 500), Gold Medal (Marut), Bajaj (efficial) (5star rated)
Ventilating fans BLDC Plastic body:- Atomberg, Havells, Orient, Gold Medal, Bajaj.
Exhaust fans:- Atomberg, Havells, Orient, Gold Medal, Bajaj.
LED lights polycarbonate body:- Bajaj, havells, Goldmedal,Panasonic, Philips, Wipro, Changi ( If quantity of LED fittings exceeds 50 in number then testing of fittings is mandatory ), L&T.
LED lights PDC/CRCA body:- Bajaj, Havells, Panasonic, Philips, Wipro, L&T, Changi. ( If quantity of LED fittings exceeds 50 in number then testing of fittings is mandatory )
LED Lights UGR<19:- Bajaj, Havells, Philips, Wipro, L &T, Changi.
Armoured Cables/ Unarmoured Cables:- Univesal, KEI, Havells, Grandley, Polycab.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.97 MB
SBD_100BeddedShillai.pdf
Tender Documents • 3.67 MB
DeclarationNEW.pdf
Additional Documents • 0.01 MB
BOQ_188437.xls
BOQ • 0.60 MB
Download all tender documents and submit your bid