Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.5 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹18.0 L+₹2.0 L (12.5%)Rejected-Finance 29 MODEL TOWN BEHIND GURUDWARA PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L2 | Rejected-Finance High | |
| 3 | L3₹20.5 L+₹4.5 L (27.9%)Rejected-Finance | L3 | Rejected-Finance High | |
| 4 | L4₹24.4 L+₹8.4 L (52.4%)Rejected-Finance HOUSE NO 40 CHOTTI BARADARI PART I GARHA ROAD NEAR MEDICAL COLLEGE JALANDHAR PB 144022 | JALANDHAR | JALANDHAR | PUNJAB | 144022 | L4 | Rejected-Finance High | |
| 5 | L5₹24.5 L+₹8.5 L (53.0%)Rejected-Finance | L5 | Rejected-Finance High |
Tender Value
Refer Docs
EMD Value
₹44,000
Closing Date
9 Nov 2020, 6:00 pmClosed
GE Gurdaspur
Garrison Engineer, Gurdaspur (Tibri)
Repair and maint of street light and security light at Zone-II area of Tibri Mil Stn under GE Gurdaspur
2020_MES_379487_2
GE GSR-41/2020-21
Open Tender
Civil Works
Item Rate
180 days
Garrison Engineer, Gurdaspur (Tibri)
As per tender documents
8 documents required · 8 mandatory
₹500
GE Gurdaspur
₹44,000
2 Dec 2020
20 Oct 2020
11 Nov 2020
20 Oct 2020
9 Nov 2020
28 Oct 2020
Amount
M & L for dismantling/taking down carefully by disconnecting of electric connection from any situation/ loction, place and depositing to MES store yard street light fittings of type 1X36/40 watts, HPSV, HPMV, LED of any wattage, flood lights, post top lanterns etc. complete all as specified and directed by Engineer-in-Charge.
Supply & fixing LED Street light 90 Watt WARM WHITE 4000K with silicon gasket for IP 66 (no glue) protection suitable upto 50mm OD holder fixed on existing poles. LED street light shall be made up of pressure die cast alluminium LM 6 aloy housing with toughend glass and high power LEDs and secondary lenses with IP 66 protections ( of any one of maufacturers of LED viz; Nichia, Cree, OSRAM, Philips), top opening for separate driver compartment with frame, brand, logo embossed, toughened glass cover. High power ceramic base, CRI > 70,and bolted inside the luminaire panel. Average life class of 50000 hrs metal body fully coated phase to phase protection at 440 V upto 4 hours and > 300 V auto cut and restart feature. Luminaries and driver shall be of same make to avoid any dispute and service issue later all as directed and specified Note :- LM 79 test report, LM 80 report with minimum 9000 hrs testing to support 50K life TTC and dirver NABL accreditated report shall be submitted before execution of work to the Engineer - in - Charge .
All as per Srl item No 3 above but 72 Watt all as directed by Engineer-in-Charge
All as per Srl item No 3 above but 60 Watt all as directed by Engineer-in-Charge
All as per Srl item No 3 above but 120 Watt all as directed by Engineer-in-Charge
Supply and fixing energy saving environmental friendly, long life , exclusive innovative die-cast aluminium IP 66 flood light with high power LEDs as light source , suitable for highlighting spaces/ areas 200 watt LED luminaries complete with all accessories ,connecting up with twin core twisted flexible copper conductor cable of size 1.0 Sqmm all as specified & directed by Engr-in-Charge.
All as per Srl item No 7 above but 120 Watt all as directed by Engineer-in-Charge
Supply of 45 watt LED Inverter RTC Street Light with inbuilt RTC (Real Time Clock) for AUTO ON/ AUTO OFF and must have DIMMING facility from 10 to 100% of Rated wattage as per user defined timeline. Housing made of Pressure Die Cast Aluminium, TOP MAINTAINABLE and with clear heat resistant toughened glass, have secondary lens for better optics, should have LM80 certified LED of CREE, NICHIA, OSRAM, SEOUL make only with constant current RTC enabled electronic driver with 5KV SPD, IP66. Street light shall have inbuilt Li-ion battery of 5200m AH and shall have > 1.5 hrs battery backup at inverter load in case of power failure, Efficacy >100 LPW, CRI >70, THD < 10%, PF > 0.95, Cut off voltage at 300 Volt + 10% and suitable for 50mm mounting pipe all as per Halonix Model : HLSLD-ML04-45-CWL-INV-RTC-DIMM or equivalent.
Supply of 60 watt LED Inverter RTC Street Light with inbuilt RTC (Real Time Clock) for AUTO ON/ AUTO OFF and must have DIMMING facility from 10 to 100% of Rated wattage as per user defined timeline. Housing made of Pressure Die Cast Aluminium, TOP MAINTAINABLE and with clear heat resistant toughened glass, have secondary lens for better optics, should have LM80 certified LED of CREE, NICHIA, OSRAM, SEOUL make only with Constant current RTC enabled electronic driver with 5KV SPD, IP66. Street light shall have inbuilt Li-ion battery of 5200m AH and shall have > 1.5 hrs battery backup at inverter load in case of power failure, Efficacy >100 LPW, CRI >70, THD < 10%, PF > 0.95, Cut off voltage at 300 Volt + 10% and suitable for 50mm mounting pipe all as per Halonix Model : HLSLD-ML04-60-CWL-INV-RTC-DIMM or equivalent.
Supply and fixing in repair LED Street light fitting driver of 150/250 Watt of any make and type as required at site all as specified and directed by Engineer-in-Charge.
All as per Srl item No 11 above but 90/120 Watt all as directed by Engineer-in-Charge
All as per Srl item No 11 above but 70/72 Watt all as directed by Engineer-in-Charge
All as per Srl item No 11 above but 30/60 Watt all as directed by Engineer-in-Charge
Supply and fixing in replacement GI pipe bracket made out of GI pipe light grade 40mm dia and bend to shape 1.5 mtr long, including fixing with MS clamps made out out of MS flat iron of size 40X4mm thick with nuts & bolts, washers complete including dismantling the existing GI pipe bracket and drilling of holes for nuts & bolts etc all as specified and directed by Engineer-in-Charge.
Supply and fixing of three phase 8 KW Automatic Street Light Control Switch using Infrared Sensor based NATURE SWITCH for automatic switching of Street lights. Nature switch operation should be based on Natural Light Lux level. Switching on illuminance level should be of minimum 30 Lux and Switching off illuminance should be greater than or equal to 10 Lux. The sensor should also have part night operation facility of min 4 hrs to maximum 12 hrs. The circuit shall have a provision for manual over ride operation. The sensor along with suitable power contactors and incoming-outgoing MCBs should be enclosed in a pole/wall mountabl enclosure made of rust proof, electric shock proof, termite proof and FR grade SMC junction box conforming to IP54 complete all as directed by Engr-in-Charge.The Make of Nature switch : Kakatiya Energy Systems/Havells/Healer, Contactor: BCH/L&T/Schneider, MCBs : Hager/Schneider/L&T/C&S, SMC enclosure & circuit sheet: Sintex/Hensel
Repair / tightening of end terminals of street light fitting of any size and capacity and repair the street lights having minor faults i.e loose connections, carbon deposition , shifting of LED, refixing etc and making the light functional all as specified and directed by Engineer in charge
M & L for repair of the Timer panel switch of street lights shifting and refixing of street light after repair of minor nature such as checking faults/ tightening/ replacing thimbles, copper/ alluminium wires, including make good by welding/brazing and painting of one coat of paint all as dircted by Engineer-in-Charge. Provision of 01 No 04 lever Godrej pad lock with locking arrangement made out of suitable MS latches into existing timer switch panel.
S&F Analog type timer switches (without battery backup) front mounted programmable current capacity 15-16 amps with 1 change over all as directed.
S&F digital type timer switches front mounted programmable per 1 min, current capacity 15-16 amps with 1 change over, total 28 programes all as directed
S&F MCCB 100 Amp, 3 pole 50 Hz 16KA all as specified and directed.
S&F MCB TPN 63 Amp, 3 pole 50 Hz all as specified and directed.
S&F 3 pole power contactor of amp rating 30 to 50Amp as per existing make and rating all as directed by Engineer in charge.
Supply and fixing analog type switch all as specified and directed.
Supply and fixing in replacement LED post top lantern 30 Watt with die cast housing cum heat sink with PMMA diffuser in IP-66 fitting complete all as specified and directed.
Supply and fixing PVC cable aluminium conductor of size 10 sqmm 2 core all as specified and directed by Engineer-in-Charge.
Supply and fixing PVC cable aluminium conductor of size 1.5 sqmm 3 core all as specified and directed by Engineer-in-Charge.
S & F junction box poly corbonate with glass fibre reinforced , environment friendly, recylable, UV resistant , halogen and silicon free anti acid and anti corrosive IP 66/67 in accordance with IE rule internally embedded gasket, junction box including 3 phase 415 volt aluminium bus bar and one No. MCB SP 6A 10KA to control the street light including clamps made of MS flat at size 25 x 3mm , nuts bolts to fix the junction box with poles all specified and directed.
Supply and fixing shackle type insulator porcelain vitrous white, brown or green insulator incl galvanised mild steel straps washers insulators bolts washers of size 75x90 mm all as specified and directed.
Earthing complete with galvansed steel earth plates electrode 60cmX600cmX6mm thick burried directly in ground ( earth pit not less than 2.25 mtr deep below the ground level ) with edge of the plate not less then 1.5 mtr below the ground level connection to GI galvanised Iron strp 25mmX4mm as earthing lead by means of bolts/nuts chick nut & washers of GI or steel all ghown in electrical plate No 5 of SSR part I connection to feeder piller all as specified including watering GI pipe 40mm bore medium grade PCC chamber using PCC 1:3:6 type C2 C1 cover funnel & wire mesh complete all as specified & directed by Engr-in-Charge.
M & L in replacement of surge Protection Device of capacity 5KV for LED security lights all as directed by Engineer-in-Charge.
M & L in replacement of surge protection device of capacity 10 KV for LED security lights all as directed by Engineer-in-charge
M & L for preparation of old painted surfaces of electric pole removing complete dust and other deposited materials by cleaning from steel tubular pole of length upto 9 metres cross arms, bracing, clamps etc and painting with one coat of aluminium paint, retaining and repainting existing marking, numbering at poles, painting of cross arms, brackets, clamps, bracing etc on pole and replacement of reflective band of 3M brand RED-YELLOW-RED alternate coloured 3 numbers of minimum 5 cm in height wrapped all around the pole all as specified and directed by Engineer in Charge .
M & L for preparation of old cement based painted surfaces of RCC poles 9 to 11 Mtr height cleaning the dust and other deposited materials and painting with one coat of exterior weather coat paint of approved make and colour, retaining and repainting existing marking for numbering of poles etc on pole and replacement of reflective band of 3M brand RED-YELLOW-RED alternate coloured 3 numbers of minimum 5 cm in height wrapped all around the pole all as specified and directed by Engineer in Charge
M & L for fault detection in damaged UG cable by using cable fault detector / locator vehicle mounted to a accuracy of 2 mtr for various location inside the station of any size and type upto 1.1KV including excavation & earthwork in any type of stratra of size 4 x 2 x 0.6m to usually inspect / reapair the damaged cable when and where required and dircted by Engineer in Charge
Re-Stringing of existing ACSR conductor of any size any type as required sag fixed on OH line incl unwindinding the conductor & insulators/cross Arms on poles properly binding with alumminum all as specified and directed.
M & L aluminium conductor steel reinforced (ACSR) over size of ferret/ weasels/ mink/ beaver etc fixing stretching and jumppering joining with aluminium wire complete all as specified.
M&L for cross arms in replacement, bracing, supports, clamps and back plates, fabricated from structural steel section including nut bolts washers including welding, bending, cold or hot drilling holes for bolts in any shape or size as indicated in drawings or as directed including two coats of aluminium paint over a coat of red oxide comlete all as specified and directed.
kailu construction co
RATTAN CHAND CHANDAN AND CO
UNITED ENGINEERING CORPORATION
INDERJIT SINGH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .